# AMIC-5010: insulation resistance tester

https://amperis.com/en/products/insulation-resistance-meters/5kv/amic-5010/

> AMIC-5010: 5 kV insulation tester, 50 kΩ to 15 TΩ with ±(3% m.v. &#43; 10 digits), PI, DAR, SV and DD, 200 mA continuity, works next to live HV.

5 kV insulation resistance meter measuring up to 15 TΩ under strong interference

**Measuring the insulation of transformers, generators and medium-voltage cables next to live high-voltage equipment takes a 5 kV meter that withstands induced voltages without aborting the test and reaches the teraohm range.** The AMIC-5010 keeps measuring with interference voltages below 50 V DC or 500 V AC, stabilises the reading with 10, 30 or 60 s digital filters and covers 50 kΩ to 15 TΩ per IEC 61557-2, with ±(3% m.v. &#43; 10 digits) up to 99.9 GΩ, PI, DAR, SV and DD indices and a 200 mA continuity test per EN 61557-4.

## AMIC-5010 key data

- **Test voltage and current:** the AMIC-5010 sets 50 to 1000 V in 10 V steps and 1 to 5 kV in 25 V steps, with a test current of 1.2 or 3 mA and a maximum short-circuit current of 3.6 mA ±15%.
- **Range and accuracy:** up to 500 GΩ at 250 V, 1 TΩ at 500 V, 2 TΩ at 1000 V, 5 TΩ at 2500 V and 15 TΩ at 5000 V; at 5 kV, ±(3% m.v. &#43; 10 digits) up to 99.9 GΩ and ±(10% m.v. &#43; 10 digits) from 10 to 15 TΩ.
- **Interference immunity:** with interference voltages below 50 V DC or 500 V AC the test continues with additional uncertainty; 10, 30 or 60 s digital filter and three-lead measurement with the G terminal adding only 0.05% error.
- **Diagnostics:** t1, t2 and t3 times from 1 to 600 s for DAR/PI or Ab1/Ab2, total time up to 99 min 59 s, SV in five steps of 30 s to 5 min, DD with 1 to 60 min charging and a minimum RISO limit adjustable from 1 kΩ to 15 TΩ.
- **Continuity:** 0.12…999 Ω per EN 61557-4 with 200…250 mA in both directions, ±(2% m.v. &#43; 3 digits) up to 199.9 Ω and ±(4% m.v. &#43; 3 digits) up to 999 Ω, with test-lead autozeroing.
- **Leakage current and capacitance:** leakage current from 0.01 nA with ±(1.5% m.v. &#43; 2 digits) and capacitance from 1 nF to 49.99 µF with ±(5% m.v. &#43; 5 digits).
- **Battery and environment:** 13.2 V, 5.0 Ah LiFePO4 battery for at least 1000 RISO measurements per EN IEC 61557-2, 990-cell memory (11 880 records), operation from -20 to &#43;50 °C up to 3000 m.

## Advantages

**Fine-stepped voltage up to 5 kV**
The test voltage is set from 50 to 1000 V in 10 V steps and from 1 to 5 kV in 25 V steps, with test currents of 1.2 or 3 mA that charge large objects quickly and a range that reaches 15 TΩ at 5 kV.

**Measures where others cannot**
Unique algorithms recognise the nature of the voltage present on the object: mains voltage blocks the test, while voltage induced by electromagnetic fields does not — so measurements succeed next to live HV equipment, helped by 10, 30 and 60 s digital filters.

**Complete time diagnostics**
T1, T2 and T3 times from 1 to 600 s deliver the absorption coefficients, PI and DAR, the step-voltage test (SV) and the dielectric discharge (DD) complete the picture, and capacitance and leakage current are read during the test.

**Safe accessories up to 11 kV**
The supplied leads withstand 11 kV and the probes and crocodile clips 5.5 kV; leads up to 20 m can be used thanks to the high interference immunity, and the object is always discharged after the test.

## Applications

- Insulation diagnostics of transformers, motors and generators.
- Medium-voltage cables and switchgear in substations.
- Measurements near live busbars and in strong electromagnetic fields.

## About the product

The AMIC-5010 is a 5 kV insulation meter whose range — 50 kΩ to 15 TΩ — and interference immunity up to 500 V place it in the premium class. Basic accuracy is ±(3% m.v. &#43; 10 digits), the timer runs to 99&#39;59&#39;&#39; and adjustable limits qualify each result; a mobile app shows live graphs on an Android device.

It is powered from a LiFePO4 13.2 V battery or from the 90-260 V mains, performs at least 1000 measurements per EN 61557-2 on one charge, and its case reaches IP67 when closed (IP40 open). Safety follows EN 61010-1 with CAT IV 600 V (CAT III 1000 V) and double insulation.

Available accessories: 3 m, 11 kV leads, 11 kV probes and crocodile clips, mains cable, carrying case, USB cable and calibration certificate; optionally 15 kV leads up to 20 m, the PRS-1 probe and the CS-1 simulator.

## Technical specifications

Test voltage | 50…5000 V; 10 V steps to 1 kV, 25 V steps above
Measuring range | 50 kΩ…15 TΩ per IEC 61557-2 (UISO = 5 kV)
Test current | 1.2 mA or 3 mA
Diagnostics | PI, DAR, Ab1, Ab2, SV, DD; timer up to 99&#39;59&#39;&#39;
Digital filters | 10 / 30 / 60 s; immunity up to 500 V
Continuity | &gt;200 mA per EN 61557-4; 0.12…999 Ω
Memory and interface | 990 cells (11 880 records); USB and Bluetooth
Safety | CAT IV 600 V (CAT III 1000 V); IP67 (case closed)
Accuracy by sub-range (5 kV) | ±(3.5% m.v. &#43; 10 digits) up to 999 GΩ; ±(7.5% m.v. &#43; 10 digits) up to 9.99 TΩ; ±(10% m.v. &#43; 10 digits) up to 15 TΩ
Continuity accuracy | ±(2% m.v. &#43; 3 digits) up to 199.9 Ω; ±(4% m.v. &#43; 3 digits) up to 999 Ω
Leakage current and capacitance | From 0.01 nA, ±(1.5% m.v. &#43; 2 digits); 1 nF…49.99 µF, ±(5% m.v. &#43; 5 digits)

## Frequently asked questions

**What interference voltage can the AMIC-5010 tolerate without stopping the test?**
The AMIC-5010 keeps measuring if the object carries less than 50 V DC or 500 V AC of interference voltage, with additional uncertainty; above those values it blocks the test and lights the red LED. The 10, 30 or 60 s digital filters stabilise the reading in noisy environments.

**How accurate is the continuity test of the AMIC-5010?**
It measures from 0.12 to 999 Ω per EN 61557-4 with 200 to 250 mA in both directions, with ±(2% m.v. &#43; 3 digits) up to 199.9 Ω and ±(4% m.v. &#43; 3 digits) up to 999 Ω; the open-circuit voltage is 4 to 24 V and the leads are compensated by autozeroing.

**What range corresponds to each test voltage?**
500 GΩ at 250 V, 1 TΩ at 500 V, 2 TΩ at 1000 V, 5 TΩ at 2500 V and 15 TΩ at 5000 V, following the RISO limits of IEC 61557-2.

**How does it measure under strong interference?**
Its algorithms distinguish mains voltage from voltage induced by electromagnetic fields and the digital filters average over 10, 30 or 60 s, so tests can run next to energised equipment.

**Which diagnostic indices does it calculate?**
The polarization index (PI), the dielectric absorption ratio (DAR), the Ab1 and Ab2 coefficients, step-voltage tests (SV) and the dielectric discharge (DD).

**Can it check protective conductors?**
Yes. It tests continuity with a bidirectional current above 200 mA per EN 61557-4, with autozeroing and compensation of the test leads.