# SF6 leak detectors for switchgear &amp; GIS

https://amperis.com/en/products/switch-testing/sf6/sf6-leak-detectors/

> Amperis SF6 leak detectors for substations: sniffer and optical gas imaging for GIS and breakers, supporting EU F-gas leak-check duties (2024/573).

**SF6 leak detectors** locate and quantify leaks in gas-insulated switchgear, breakers and other SF6 equipment, protecting both dielectric reliability and the environment. The Amperis range for the electrical sector includes sniffer-type detectors and optical gas imaging options for leak surveys and F-gas compliance checks.

## What it measures and how it works

Two complementary technologies are used. **Sniffer** detectors draw air across a sensor near joints and seals, flagging concentrations down to very low levels and helping pinpoint and quantify a leak (often expressed in g/year). **Optical gas imaging (OGI)** cameras visualise the escaping plume from a distance, ideal for scanning a whole bay quickly. Used together they survey wide areas and then localise the exact source.

## How to choose the right detector

- Decide between sniffing (pinpoint and quantify) and imaging (fast wide-area survey) — or both.
- Check sensitivity, expressed as a detectable leak rate (g/year).
- Consider behaviour in draughts and outdoor conditions.
- Look for quantification and logging to document F-gas leak checks.
- Confirm the detector suits the gases in your fleet (SF6 and mixtures).

Planning a leak survey? Do not hesitate to [contact us](https://amperis.com/en/contact/).

## Applications

- Routine leak surveys of GIS and breakers
- Tightness checks at commissioning
- Investigating the cause of a density/pressure alarm
- Documented F-gas leak-check compliance

## Applicable standards

Amperis detectors support the IEC/EN and EU framework (not national PN/PL designations):

- IEC 62271-1 — permissible leakage rate for switchgear (design target ≤0.5%/year)
- IEC 62271-4 — SF6 handling procedures
- Regulation (EU) 2024/573 — F-gas leak-check duties and prompt repair
- IEC/EN 61010-1 — instrument safety

## Frequently asked questions

### How often must SF6 equipment be leak-checked?

Under Regulation (EU) 2024/573, switchgear holding 6 kg of SF6 or more must be checked, unless it is tested below 0.1%/year leakage or fitted with pressure/density monitoring and an automatic alert. Any detected leak must be repaired without delay.

### Sniffer or camera — which should I use?

Use an optical gas imaging camera to scan a substation quickly and find the area, then a sniffer to pinpoint and quantify the exact leak. Many maintenance teams keep both.

### Why does a small leak matter so much?

SF6 has a global warming potential around 23,500 times that of CO₂, so even small emissions are significant. A leak also lowers gas density, eventually weakening the insulation.

## Technical resources

Combine leak detection with [SF6 gas analysers](https://amperis.com/en/products/switch-testing/sf6/gas-analysers/), [handling and recovery equipment](https://amperis.com/en/products/switch-testing/sf6/sf6-gas-servicing-equipment/) and [infrared and corona cameras](https://amperis.com/en/products/cameras/). [Request a quote](https://amperis.com/en/contact/).

- [D-TEK: SF6 leak detector](https://amperis.com/en/products/switch-testing/sf6/sf6-leak-detectors/d-tek-sf6-leak-detector/)
- [TC706: SF₆ leak location on GIS and circuit breakers](https://amperis.com/en/products/switch-testing/sf6/sf6-leak-detectors/gas-detection-tc706/)
- [SF6 leak detector](https://amperis.com/en/products/switch-testing/sf6/sf6-leak-detectors/sf6-leak-detector/)