Timing, coils and substation battery in a 1.6 kg handheld device
Timing circuit breakers with one break per phase in the field, without carrying a case-sized analyzer, only takes a handheld device that measures timing, pole synchronisation and coil currents with the accuracy that breaker standards call for, and that also operates the breaker. The CAT-H does it in 1.6 kg: its built-in ±300 V, ±35 A coil control drives the trip and close coils from the device itself; it times 3 main contacts with 0.05 ms resolution and 0.05% of reading accuracy, records coil currents up to ±35 A and the substation battery voltage up to ±300 V, and runs up to 8 hours on its Li-ion battery.
CAT-H key data
- Main contacts: 3 inputs, one per phase; closed ≤ 10 Ω, pre-insertion resistors from 10 Ω to 5 kΩ and open ≥ 5 kΩ, with 20 V DC ±20% open-circuit voltage and 50 mA short-circuit current.
- Time measurement: resolution of 0.05 to 10 ms depending on test duration (sampling up to 20 kHz) and accuracy of 0.05% of reading ± resolution; bounce and pre-trigger times.
- Built-in coil control: 2 channels (trip and close) of ±300 V DC / AC peak and ±35 A from DC to 5 kHz, with electronic drivers and overcurrent and overvoltage protection.
- Coil current: 2 channels with Hall-effect sensor, ±35 A from DC to 5 kHz, accuracy ±(0.5% of reading + 0.1% FS) and curve with 0.1 ms resolution; additional input for a 30/300 A DC clamp.
- DC voltage: ±300 V with typical accuracy of ±0.5% of reading ±0.5% FS, for the substation battery or another analog signal.
- Operations: O, C, CO, O-C, C-O and O-C-O, with predefined delay or contact-position sensing; measurement triggering from the coil channel, the DC clamp or the voltage channel.
- In the field: 2 × 3.7 V, 2900 mAh Li-ion battery for 8 h, 5.7-inch colour touch screen, memory for over 30,000 results, IP40, 310 × 170 × 58 mm and operation from −10 to +55 °C.
Advantages
Operation and measurement in one device
The built-in coil control opens and closes the breaker from the CAT-H, with no external modules, while it measures contact timing and coil currents.
Diagnosis from the coil curve
The coil current curve, recorded with 0.1 ms resolution, reveals plunger or latch friction, burnt insulation, shorted turns and auxiliary contact faults, as recommended by IEC 62271-100.
Analysis in the substation itself
It overlays up to four records on the screen to compare operations and spot defects without going back to the office; the memory keeps over 30,000 results.
A full day of work on one charge
The internal Li-ion battery lasts up to 8 hours of testing, and the device also accepts the 12 V DC adapter with a 90 to 264 V AC input.
Applications
- LV, MV and HV circuit breakers with one break per phase, out of service, in substations, factories or workshops.
- Main contact and pre-insertion timing and pre-insertion resistor values.
- Pole synchronisation according to IEC 62271-100 and ANSI C37.09.
- Trip and close coil currents and auxiliary contact timing.
- Substation battery condition and control circuit wiring integrity.
About the product
The CAT-H is a handheld digital instrument for assessing circuit breaker condition. It records the trip and close coil current curves, the timing of the main arcing contacts and the substation DC battery voltage, and measures the pre-insertion resistors if the breaker has them. It displays numerical and graphical results; with the PC software they are downloaded, compared, printed and exported. For the first trip test with the breaker in service, there is the sister model CAT-P.
Standard accessories: 8 m main contact cables, contact and ground connection, 5 m coil control cable, 2 × 5 m coil supply and voltage measurement cables, test probes, clips, jumpers, cable bag, stylus and transport case.
Technical specifications
| Main contacts | 3 inputs (1 per phase); pre-insertion 10 Ω – 5 kΩ |
| Time resolution | 0.05 – 10 ms; sampling up to 20 kHz |
| Time accuracy | 0.05% of reading ± resolution |
| Coil control | 2 channels; ±300 V DC / AC peak, ±35 A from DC to 5 kHz |
| Coil current | 2 channels, Hall effect; ±35 A; ±(0.5% rdg + 0.1% FS) |
| DC clamp | 30/300 A ranges; DC to 20 kHz |
| DC voltage | ±300 V; typical accuracy ±0.5% ±0.5% FS |
| Internal battery | Li-ion 2 × 3.7 V, 2900 mAh; up to 8 h of use |
| Display | 145 mm (5.7-inch) colour touch screen |
| Memory | Over 30,000 results |
| Dimensions and weight | 310 × 170 × 58 mm; 1.6 kg |
| Standards | IEC 62271-100 and ANSI C37.09 (timing); EN 61010-1; EN 61326-1 |
Frequently asked questions
What timing difference between poles does the standard allow?
According to IEC 62271-100, pole discrepancy must not exceed 1/6 of a cycle on opening (3.33 ms at 50 Hz; 2.78 ms at 60 Hz) or 1/4 of a cycle on closing (5.0 ms at 50 Hz; 4.17 ms at 60 Hz). The CAT-H times all three poles with 0.05 ms resolution and 0.05% of reading accuracy.
Does it need an external module to operate the breaker?
No. The CAT-H has built-in 2-channel coil control of up to ±300 V and ±35 A; you only need to connect the coil supply and the control cable.
What is the difference between the CAT-H and the CAT-P?
The CAT-H integrates coil control to operate the breaker out of service. The CAT-P does so through an optional external module and adds the online first trip test, with the breaker in service, based on the secondary currents of the current transformers.
How long does the battery last?
Its 2 × 3.7 V, 2900 mAh Li-ion battery gives about 8 hours of testing in normal use. It also runs from the 12 V DC adapter with a 90 to 264 V AC input.
Does it suit breakers with several breaks per phase?
No: the CAT-H measures one break per phase. For two or more breaks per phase and additional channels, there are the case-sized analyzers of the CAT standard and advanced series.
How do I get the results to a computer?
Over USB or with a USB memory stick connected to the device; the PC software lets you view, edit, compare, print and export the records.