# GRIDSCAN5000 hydrogen sensor

https://amperis.com/en/products/transformers-testing/hydrogen-sensor-gridscan5000/

> GRIDSCAN5000: solid-state hydrogen sensor for transformers, 25-5,000 ppm in oil, ±20 % or ±25 ppm, self-calibrating, Modbus and DNP3.

Solid-state dissolved hydrogen sensor for continuous monitoring of power and distribution transformers

**Continuous monitoring of dissolved hydrogen, the first gas to reveal an arc, a partial discharge or a hot spot, calls for a hydrogen-specific sensor that mounts on a tank valve and needs no calibration gases and no periodic calibration.** GRIDSCAN5000 measures 25 to 5,000 ppm H2 in oil, or its in-oil equivalent from the head space, with ±20 % of reading or ±25 ppm accuracy (±10 % or ±15 ppm on the 5000-HP version), T90 response under 60 minutes and patented self-calibration, and delivers the reading over Modbus RTU or DNP3 on RS-485 from a 12 to 48 VDC supply.

## GRIDSCAN5000 key data

- **Measuring principle:** hydrogen-specific solid-state palladium-alloy element, with cross-sensitivity below 2 % to H2O, CO2, C2H2, C2H4 and CO. GRIDSCAN5000 runs automatic reference cycles that remove drift, with no calibration gases, membranes or pumps.
- **Range and accuracy:** 25-5,000 ppm H2 dissolved in oil, or 25-5,000 ppm in-oil equivalent on the gas-phase version; accuracy ±20 % of reading or ±25 ppm, whichever is greater (±10 % or ±15 ppm on the 5000-HP); repeatability ±10 % or ±15 ppm.
- **Response and compensation:** T90 under 60 minutes once hydrogen reaches the sensor; GRIDSCAN5000 measures oil temperature with a built-in RTD to compensate the dissolved gas reading.
- **Oil limits:** −40 to 105 °C within calibration (up to 135 °C without damage), −40 to 80 °C in gas phase and 0.1 to 10 bar pressure; supports mineral oil, silicone, natural ester and synthetic ester.
- **Communication and power:** galvanically isolated two-wire RS-485, Modbus RTU and DNP3 (Modbus address 1, DNP3 source 4 and destination 3, 19,200 baud); 12-48 VDC and 10 W maximum; 4-20 mA output with the GRIDSCAN AO-1 module, scalable from 0-100 to 0-5,000 ppm.
- **Mounting:** 3/4&#34;-14 NPT thread on a ball or gate valve ≥ DN20, horizontal with air bleed in oil or horizontal or vertical in the head space; 151 × 39.6 × 39.6 mm and 387 g, with a single 4-wire M12 connector.
- **Outdoor duty:** IP68 (7.62 m of water for 14 days), C5M marine corrosion class, ambient −40 to 70 °C and 30 g shock for 18 ms to IEC 60068-2-27.
- **Certifications and logging:** FM 6520:2022 in liquid phase, CE marking, IEC 61010-1 and IEC 61326; GRIDSCAN5000 stores 1 year of history and carries a 3-year warranty on the unit and 10 years on the sensing element.

## Advantages

**It warns before any other signal**
Hydrogen is the first gas generated by an incipient arc, a partial discharge or a hot spot. Watching it rise in real time leaves room to schedule the intervention instead of discovering the problem in the six-monthly oil analysis.

**No calibration, no consumables**
The sensing element is solid state and calibrates itself: no membranes, no calibration gases, no pumps and no chromatography columns, and nothing to replace between transformer inspections.

**Affordable fleet-wide**
Its price and its simple installation make it viable to equip not only the critical assets but the whole fleet, which is where continuous monitoring really pays.

**Built for outdoor service**
IP68 ingress protection — 7.62 m of water for 14 days —, C5M corrosion class equivalent to a marine environment and operation from −40 to 70 °C, with vibration testing and a 30 g shock rating to IEC 60068.

**Immediate integration**
It communicates over Modbus RTU or DNP3 on two-wire RS-485, both stand-alone and inside third-party multi-gas monitors, and supports a 4-20 mA output through the matching module.

## Applications

- Power and distribution transformers, new or in service.
- Wind and solar farm transformers, with high harmonic content.
- Network transformers installed in underground vaults.
- Offshore platforms and substations in salt-laden air.
- Railway traction and industrial transformers.

## About the product

The oil-calibrated version mounts horizontally with the air-bleed assembly; the gas-calibrated version accepts horizontal or vertical mounting in the head space. Both need a 3/4&#34; ball or gate valve (≥ DN20) and thread sealant, with no galvanised fittings.

A single shielded four-conductor 18 AWG cable, with a female M12 connector and IP67/IP68 rating, carries power and communications to the control cabinet over typical runs of 5 to 30 m; from there, the RS-485 bus reaches up to 1,000 m. The sensor itself keeps one year of history, so a communications outage leaves no gap in the data.

The Windows configuration utility connects over RS-485 or through an Ethernet-to-RS485 bridge and gathers the whole commissioning process into four tabs: real-time data with capture to CSV, protocol and address, clock synchronisation, owner, substation and transformer identification, and selection of the insulating liquid — mineral, silicone, natural ester or synthetic ester with its own Ostwald slope and offset.

The range is completed by the high-performance version, accurate to ±10 % or ±15 ppm, the continuously self-calibrating version, which calibrates without interrupting the measurement, and an extended-range version from 250 to 50,000 ppm for nitrogen blankets with high concentrations.

## Technical specifications

Measuring range | 25 to 5,000 ppm in oil; 25 to 5,000 ppm in-oil equivalent on the gas-phase version
Accuracy | ±20 % of reading or ±25 ppm (±10 % or ±15 ppm on the high-performance version)
Repeatability | ±10 % of reading or ±15 ppm, whichever is greater
Response time | Under 60 minutes
Cross-sensitivity | Below 2 % to H2O, CO2, C2H2, C2H4 and CO
Data logging | 1 year of history held in the unit
Insulating liquids | Mineral oil, silicone, natural ester and synthetic ester
Temperatures | Ambient −40 to 70 °C; oil −40 to 105 °C; gas phase −40 to 80 °C
Communications | Two-wire RS-485, Modbus RTU and DNP3; 19,200 baud, 8N1 as shipped
Power supply | 12 to 48 VDC; 10 W maximum consumption
Connection | 3/4&#34;-14 NPT thread; 4-wire M12 electrical connector
Dimensions | 151 × 39.6 × 39.6 mm
Ingress protection | IP68 to IEC 60529; C5M marine corrosion class
Certifications | CE marking, FM 6520:2022 in liquid phase, RoHS 2011/65/EU, IEC 61010-1 and IEC 61326
Warranty | 3 years on the unit and 10 years on the hydrogen sensing element
Measuring principle | Hydrogen-specific solid-state palladium-alloy element; self-calibration through automatic reference cycles
Oil limits | Pressure 0.1 to 10 bar; up to 135 °C without damage (calibrated up to 105 °C)
Weight | 387 g

## Frequently asked questions

**Which online hydrogen sensor is best for monitoring a whole transformer fleet?**
One that is hydrogen-specific, needs no consumables or periodic calibration and installs on a tank valve. GRIDSCAN5000 screws onto a 3/4&#34; valve, measures 25 to 5,000 ppm with ±20 % of reading or ±25 ppm, is powered at 12-48 VDC through a single four-wire M12 cable and communicates over Modbus RTU or DNP3, so it integrates into the SCADA of the whole fleet.

**Is it installed in the oil or in the head space?**
There are two factory-calibrated versions. The oil version mounts horizontally with the air-bleed assembly, on a ball or gate valve of at least DN20 and away from turbulent oil flow; the gas-phase version mounts horizontally or vertically in the head space and reports hydrogen as an in-oil equivalent, because the head-space concentration is about 20 times higher than the dissolved one. Both GRIDSCAN5000 versions measure 25 to 5,000 ppm.

**Does it need periodic calibration?**
No. The sensor self-calibrates and corrects drift, so the reading stays valid without calibration or removal throughout its service life.

**Does it work with ester or silicone transformers?**
Yes. It supports mineral oil, silicone, natural ester and synthetic ester; the liquid type is selected in the configuration software.

**How long before the first reliable reading?**
The unit runs its self-test and a start-up sequence once powered which, on a new installation or after a long outage, can last up to 16 hours before it delivers stable, accurate readings; after a short outage it gives approximate readings within about 30 minutes.

**How does it integrate with SCADA?**
Through Modbus RTU or DNP3 on two-wire RS-485. Factory settings are Modbus address 1, DNP3 source 4 and destination 3, 19,200 baud and 8N1. A 4-20 mA signal is also available through the matching module.

**Can it be fitted with the transformer in service?**
It mounts on a 3/4&#34; valve, following the bleed procedure that matches the sensor type. Installation must be carried out by qualified personnel authorised to work on the transformer.