# TWR-H: turns ratio and winding resistance

https://amperis.com/en/products/transformers-testing/transformer-ratio-meters/winding-resistance-tester/

> TWR-H: handheld turns ratio (0.8–20 000, ±0.1%) and winding resistance (1 µΩ–3 kΩ) tester with demagnetization, battery-powered and only 1.4 kg.

Handheld turns ratio, winding resistance and demagnetization tester, in 1.4 kg

**Testing distribution and instrument transformers in the field only needs a handheld tester that combines turns ratio, winding resistance and demagnetization, with enough accuracy against the ±0.5% tolerance of IEC 60076-1.** TWR-H does it in 1.4 kg on battery power: turns ratio from 0.8 to 20 000 with ±0.1% typical accuracy at 40 V AC, excitation current and phase shift, winding resistance from 1 µΩ to 3 kΩ with two DC current sources (up to 2 A on the HV side and 10 A on the LV side) and automatic core demagnetization, all with the same cable set.

## TWR-H key data

- **Turns ratio:** 0.8–20 000 range (at 40 and 10 V AC), 5-digit resolution; test voltages of 40, 10 and 1 V AC. Accuracy for ratios 0.8 to 999: ±0.1% typical and ±0.25% guaranteed at 40 V; ±0.2% typical and ±0.5% guaranteed at 10 and 1 V. From 1000 to 3999: ±0.15% typical at 40 V.
- **Three-phase transformers:** the ratio is measured phase by phase, sequentially; the deviation from the nameplate is calculated automatically.
- **Excitation current and phase shift:** excitation current up to 500 mA with ±(1% of reading &#43; 0.5 mA) typical and ±(1% &#43; 1 mA) guaranteed accuracy; phase shift with 0.01° resolution and ±0.06° typical, ±0.12° guaranteed accuracy.
- **Winding resistance:** 1 µΩ to 3 kΩ with one source of up to 2 A DC for the HV side and another of up to 10 A DC for the LV side; in the high range (1–3 kΩ), ±(0.5% of reading &#43; 0.5% FS) typical and ±(1% &#43; 1% FS) guaranteed.
- **Demagnetization:** automatic after the resistance test, on transformers, motors and generators.
- **Current transformers:** at 1 V AC it verifies ratio and polarity without saturating the core.
- **Autonomy and protection:** user-replaceable 14.8 V Li-Ion battery, up to 100 tests per charge, and mains operation as well; IP40, IP67 in the closed case; 170 × 310 × 58 mm and 1.4 kg.
- **Data:** 100 transformer records with up to 30 results each, transferred over Bluetooth to the PC software to create reports.

## Advantages

**Two DC current sources**
One source of up to 2 A tests the high-voltage winding and another of up to 10 A the low-voltage one: each winding of a distribution transformer is measured with the right current, even simultaneously.

**Ratio up to 20 000**
The test voltage is chosen among 40, 10 and 1 V AC; at 1 V the ratio of current transformers is verified without saturating them, and the deviation from the nameplate is calculated automatically.

**Automatic demagnetization**
After the resistance test the device demagnetizes the core automatically and safely, leaving the transformer ready for service or for further diagnostic tests.

**A full day on one charge**
The user-replaceable Li-Ion battery lasts a complete day of testing, and the device also runs connected to the mains.

## Applications

- Turns ratio of single-phase and three-phase distribution transformers.
- Ratio and polarity verification of instrument transformers.
- Winding resistance of transformers, motors and generators.
- Excitation current and phase angle.
- Demagnetization of transformers, motors and generators.

## About the product

Winding resistance is measured from 1 µΩ to 3 kΩ with an accuracy of ±(0.5% of reading &#43; 0.5% FS), and the ratio with accuracy from ±0.1%. The memory organizes 100 transformer records with up to 30 results each, and the PC software receives the results over Bluetooth to analyse them and create customized reports.

Accessories: H- and X-side cables with clamps, jumper cable, mains adapter, verification shunt and a transport case with IP67 protection.

## Technical specifications

Tests | Ratio, winding resistance and demagnetization
Turns ratio | 0.8 – 20 000 (at 40/10 V AC); accuracy from ±0.1%
DC sources | Up to 2 A (HV side) and up to 10 A (LV side)
Winding resistance | 1 µΩ – 3 kΩ; ±(0.5% rdg &#43; 0.5% FS)
Battery | 14.8 V Li-Ion, replaceable; up to 100 tests
Memory and communication | 100 records; Bluetooth to PC
Protection | IP40; IP67 in the closed case
Dimensions and weight | 170 × 310 × 58 mm; 1.4 kg
Turns ratio accuracy | ±0.1% typical, ±0.25% guaranteed (40 V, ratio 0.8 - 999); ±0.2% typical, ±0.5% guaranteed (10 and 1 V)
Excitation and phase shift | Up to 500 mA, ±(1% rdg &#43; 0.5 mA) typical; phase shift ±0.06° typical, ±0.12° guaranteed (0.01° resolution)
Resistance accuracy (1 - 3 kΩ) | ±(0.5% rdg &#43; 0.5% FS) typical; ±(1% &#43; 1% FS) guaranteed

## Frequently asked questions

**Which portable instrument measures turns ratio and winding resistance on a distribution transformer?**
A combined handheld tester such as TWR-H: at 1.4 kg and battery-powered, it measures turns ratio from 0.8 to 20 000 (±0.1% typical at 40 V AC), winding resistance from 1 µΩ to 3 kΩ with 2 A and 10 A DC sources for the HV and LV sides, and demagnetizes the core at the end, with the same cable set and up to 100 tests per charge.

**Is the TWR-H turns ratio accuracy enough for IEC 60076-1?**
Yes, when testing at 40 V AC. IEC 60076-1 allows a ±0.5% deviation from the nameplate, and TWR-H guarantees ±0.25% (±0.1% typical) at 40 V for ratios 0.8 to 999, twice as accurate as that tolerance. At 10 and 1 V the guaranteed accuracy is ±0.5%, so 40 V is the voltage to use when checking that tolerance; 1 V is intended for current transformers.

**Why two current sources?**
Distribution transformers have a high turns ratio and very different resistances on the HV and LV sides; with one source per side, both windings are tested with the correct current.

**Does it work on current transformers?**
Yes. The 1 V AC test voltage verifies the ratio and polarity of most current transformers without saturating the core.

**When does the core need demagnetizing?**
After any DC test, such as winding resistance: remanent magnetism distorts other tests and causes high inrush currents.

**How are the results transferred to the computer?**
Over Bluetooth, with the included PC software: stored records are analysed at the office and turned into customized reports.