# Circuit breakers and switchgear: why they fail and what continuous monitoring detects

https://amperis.com/en/resources/articles/webinars-circuit-breakers-switchgear/

> Between 83 and 90 % of circuit breaker problems are mechanical. What the trip coil current, SF6 and partial discharge in switchgear reveal.

Circuit breakers are the largest single contributor to substation events: a slow or failed opening leaves everything behind them exposed to fault current. According to EPRI’s substation life extension guidelines, 83 to 90 % of reported problems are mechanical, 8 to 15 % lie in the auxiliary and control circuits and only 1 to 5 % in the main electrical circuit. This video explains what periodic maintenance misses and what a continuous monitor measures.

## Key points

- Problems develop between inspections: degrading lubrication that lengthens the interrupting time, heater failure with condensation in the control cabinet, hydraulic or pneumatic leaks, SF6 loss and failed trip or close coils.
- Every out-of-service test has a blind spot: contact resistance does not see wear on the arcing contacts, and timing and travel testing needs an outage.
- The trip coil current, captured at 128 samples per cycle with one-millisecond accuracy, portrays the mechanism. When lubrication dries out, the curve is identical up to the latch and late from there on; if a second operation comes out faster, the problem is lubrication.
- The protection relay records the fault type, distance and magnitude. The monitor adds arcing and opening time, the coil waveform, accumulated I²t per pole, the motor, stored energy and the heaters.
- An SF6 gauge or density switch only alarms once a lot of gas has gone; a density and dew-point sensor tracks the trend and forecasts the days to alarm and to lockout. In switchgear, about three quarters of failures are insulation-related, and partial discharge sensors find them: coupling capacitors and radio-frequency CTs.

## Why the breaker matters so much

A slow or failed opening exposes the whole system to fault current. Breaker mis-operation is often the root cause of a transformer failure, so a transformer is only as reliable as the breaker protecting it. And a breaker that sits closed for years gives no sign of its condition until the day it is asked to trip.

## It is almost always mechanical

The figures come from the EPRI substation life-extension guidelines:

Origin of the problem | Share of reported problems

Mechanical | 83–90 %
Auxiliary and control circuits | 8–15 %
Main electrical circuit | 1–5 %

The leading contributors are loss of lubrication, lack of maintenance and ageing, and the symptom that can actually be measured is a slowed interrupting time.

## What cyclic maintenance misses

The problems develop between the intervals: lubrication degrading and lengthening the interrupting time, heater failure and condensation in the control cabinet, hydraulic and pneumatic leaks that drive excessive motor starts, SF6 loss and moisture ingress through failing seals, trip and close coil failures, and sticking or corroded auxiliary contacts. Timing and travel testing finds these, but it needs the breaker out of service, so it is done rarely.

Each offline test also has a blind spot. Timing and travel needs an outage; contact resistance does not see arcing contact wear, because the arcing contacts are not the ones being measured; power factor is influenced by ambient conditions and contamination. The first trip test is the one that catches what the others miss.

## The coil current is the mechanism talking

Online, the central measurement is the trip coil current. Every bend in the waveform is a piece of the mechanism moving: current begins through the 52a contact, the plunger reaches speed, the latch is struck, the buffer is struck and, finally, the 52a opens and the circuit is broken. Captured at 128 samples per cycle, it is resolved to the millisecond and stored as a waveform that can be overlaid on the previous one.

That is why the diagnosis is a comparison, not a threshold. When lubrication dries out, the first half of the waveform is identical to the healthy reference and everything after the latch arrives late. Operate the breaker a second time and the interrupting time improves, which is itself the signature of a lubrication problem rather than a latch one. Left alone, it gets progressively worse.

## Relay or monitor: one describes the fault, the other the breaker

The protection relay already records the trip, so why add anything? Because from the same trip the relay gives the type of fault, the distance to the fault, the interrupting time for that one event and the breaker status, while the monitor adds what the relay cannot see: arc time and open time, the coil current waveform, the cumulative I²t per pole (the contact wear that accumulates), the motor and stored energy, and the condition of the heaters and cabinet.

From each capture come the numbers a breaker is judged on: interrupting time, open and close time per contact mechanism, arc time and restrikes.

## The gas: a gauge alarms when it has already gone

Gauges and density switches need someone to walk up and read them, and they only alarm after a significant loss. A sensor trends the loss, forecasts the days to alarm and to lockout, and turns cumulative mass loss into the emissions report that has to be filed. It should measure density and dew point together, not pressure alone: pressure moves with temperature, while density is what the equipment actually needs.

Gas is not only measured but also tested, for four reasons — acceptance, safety, fault modes, component wear — and the test ends in one decision: uncontaminated gas is stored and reused, slightly contaminated gas is filtered and retested, and severely contaminated gas is reprocessed or destroyed.

## Switchgear: here the enemy is the insulation

In switchgear the failure mode changes. Around three quarters of failures are insulation related, driven by moisture, dust, contaminants and age. The symptoms are corona, tracking on bus and insulators and, finally, flashover. Partial discharge sensors — coupling capacitors and radio-frequency CTs — detect these dielectric problems at an incipient stage. They also remove a hazard: fewer reasons to rack a breaker out for testing means less arc-flash exposure and less wear on the connectors.

## Five things to take away

- The failure is mechanical, and it develops between maintenance visits.
- The relay describes the fault; only the monitor describes the breaker.
- Diagnosis is a comparison against that breaker’s own baseline.
- Gas needs trending, not a gauge somebody has to walk up to.
- The value is scheduling repairs instead of testing during outages.

## Related equipment

The [Dynamic Ratings BPM breaker performance monitor](https://amperis.com/en/products/switch-testing/switch-testing/bpm/) captures the trip and close coil currents in service. For offline work, see our [circuit breaker analysers](https://amperis.com/en/products/switch-testing/switch-testing/), the [SF6 leak detectors](https://amperis.com/en/products/switch-testing/sf6/sf6-leak-detectors/) and the [partial discharge detection](https://amperis.com/en/products/partial-discharge-detector/) range. If you would like to discuss monitoring for your own breakers, [contact our engineers](https://amperis.com/en/contact/).