What the AGRU-4 does with the gas of
a breaker, how its circuit works,

00:00:05.361 --> 00:00:08.995
and how to recover, clean,
evacuate and fill with it.

00:00:12.484 --> 00:00:16.901
Opening a breaker for maintenance
means taking its SF6 out first.

00:00:16.941 --> 00:00:22.111
The gas cannot be vented to the atmosphere,
and it is too valuable to waste.

00:00:22.151 --> 00:00:27.048
So it is recovered, cleaned, stored,
and put back when the work is done.

00:00:32.291 --> 00:00:36.624
It is sized for breakers and
switchgear up to 69 kilovolts.

00:00:36.664 --> 00:00:42.034
It moves up to two cubic metres of
gas an hour, compresses to 34 bar with

00:00:42.074 --> 00:00:47.667
an oil-less compressor, and stores up
to 22.7 kilograms as liquid, on board.

00:00:50.948 --> 00:00:55.561
On the cart: Three gauges, for
suction, discharge and the equipment.

00:00:55.601 --> 00:01:00.283
Two alarm lights, for high pressure
and a full tank. The mode valves.

00:01:00.323 --> 00:01:04.184
The equipment and auxiliary
connections. The vacuum pump.

00:01:04.224 --> 00:01:06.100
The storage tank underneath.

00:01:06.140 --> 00:01:10.137
And two large tyres, so one
person can roll it over a kerb.

00:01:20.878 --> 00:01:23.052
Everything happens in one circuit.

00:01:23.092 --> 00:01:28.262
The compressor in the middle, a condenser
after it, and then the treatment line:

00:01:28.302 --> 00:01:32.040
drier, purifier, particle filter
and a moisture indicator.

00:01:32.080 --> 00:01:36.142
The storage tank on the right,
an auxiliary cylinder beside it,

00:01:36.182 --> 00:01:39.529
and, below, the vacuum line,
which works on its own.

00:01:47.216 --> 00:01:51.648
Recovery. The compressor draws the gas
from the equipment through the inlet

00:01:51.688 --> 00:01:55.702
regulator and compresses it, and
the condenser turns it into liquid.

00:01:55.742 --> 00:02:00.054
On its way to the tank it crosses the
drier, the purifier and the filter,

00:02:00.094 --> 00:02:02.797
so the gas is already
clean when it is stored.

00:02:07.808 --> 00:02:11.949
In practice: the hose from the
equipment connection to the breaker.

00:02:11.989 --> 00:02:15.879
On the tank, the liquid valve
open and the vapour valve closed.

00:02:15.919 --> 00:02:18.250
The mode valves to recover, and start.

00:02:18.290 --> 00:02:21.994
Open the valve on the equipment
and watch the suction gauge:

00:02:22.034 --> 00:02:25.426
when it drops into vacuum,
the breaker is nearly empty.

00:02:33.165 --> 00:02:37.577
When the tank is not enough, the
same recovery goes to an external

00:02:37.617 --> 00:02:42.096
cylinder through the auxiliary
connection, so storage has no limit.

00:02:42.136 --> 00:02:45.604
It also consolidates partly
used cylinders into one.

00:02:45.644 --> 00:02:49.044
External vessels must be
rated for at least 35 bar.

00:02:53.934 --> 00:02:57.827
The gas can also be cleaned inside
the unit, as long as needed.

00:02:57.867 --> 00:03:01.385
With both mode valves on purify
and the tank valves open,

00:03:01.425 --> 00:03:06.191
the compressor circulates the gas from
the tank through the filters and back.

00:03:06.231 --> 00:03:11.310
A hygrometer or an SF6 analyser on the
auxiliary connection shows when it is done.

00:03:17.844 --> 00:03:20.896
Before filling, the
compartment is emptied of air

00:03:20.936 --> 00:03:24.303
and moisture with the vacuum
pump, below one millibar.

00:03:24.343 --> 00:03:28.277
The hose goes to the vacuum
connection, and if the power fails,

00:03:28.317 --> 00:03:32.757
the anti-suckback valve closes, so
no pump oil can reach the equipment.

00:03:38.274 --> 00:03:43.424
Two details from the manual. A vacuum gauge
on the equipment gives the true reading.

00:03:43.464 --> 00:03:47.687
And to check for leaks, close the
pump isolation valve while it runs:

00:03:47.727 --> 00:03:52.136
if the vacuum then rises, there is a
leak, or moisture still coming out.

00:03:57.948 --> 00:04:00.153
Filling runs the circuit the other way.

00:04:00.193 --> 00:04:04.414
Vapour leaves the tank, the compressor
pushes it through the same filters,

00:04:04.454 --> 00:04:08.674
and the charging regulator sets the
pressure, read on the equipment gauge.

00:04:08.714 --> 00:04:11.668
So the gas is cleaned a
second time on its way back.

00:04:19.835 --> 00:04:23.264
Step by step: the charging
regulator backed out to zero,

00:04:23.304 --> 00:04:26.424
the hose connected, and
both mode valves to charge.

00:04:26.464 --> 00:04:30.079
Open the vapour valve of the
tank and close the liquid one.

00:04:30.119 --> 00:04:33.239
Set the regulator, start,
open the equipment valve,

00:04:33.279 --> 00:04:36.646
and let the gauge on the
equipment decide when to stop.

00:04:46.034 --> 00:04:49.300
Maintenance follows the
compressor hour counter.

00:04:49.340 --> 00:04:54.398
The drier and the filter every 50 hours,
a minor compressor kit every 200,

00:04:54.438 --> 00:04:57.979
a major one every 400, and
the pump oil once a year.

00:04:58.019 --> 00:05:02.250
The filters change one at a time,
without removing any tubing.

00:05:08.318 --> 00:05:12.114
And the safety rules. The unit
makes very high pressures,

00:05:12.154 --> 00:05:15.614
and liquid SF6 becomes cold
enough to burn the skin:

00:05:15.654 --> 00:05:18.710
gloves and eye protection
when handling hoses.

00:05:18.750 --> 00:05:22.007
Hoses are connected and
disconnected below 7 bar.

00:05:22.047 --> 00:05:25.372
The tank is for temporary
storage while servicing,

00:05:25.412 --> 00:05:29.074
and it travels empty, upright,
with every valve closed.

00:05:37.386 --> 00:05:39.736
And the specification, in one table.

00:05:42.308 --> 00:05:45.164
SF6 gas handling, from Amperis.