WEBVTT

00:00:00.511 --> 00:00:06.399
How the APDLT surveys cable heads, arresters,
insulators and bushings in service,

00:00:06.439 --> 00:00:10.498
from the ground, and how every
reading becomes a record.

00:00:12.734 --> 00:00:16.628
A partial discharge is a small
breakdown inside an insulation,

00:00:16.668 --> 00:00:18.976
which does not bridge the conductors.

00:00:19.016 --> 00:00:22.466
In a cable head it starts
where the field concentrates:

00:00:22.506 --> 00:00:25.829
voids under the insulation
screen, rough screen ends,

00:00:25.869 --> 00:00:28.430
or cuts made when the screen was removed.

00:00:28.470 --> 00:00:31.349
Each one sends out very
high frequency pulses.

00:00:34.844 --> 00:00:39.405
The APDLT picks up those pulses
between 30 and 47 megahertz,

00:00:39.445 --> 00:00:45.309
with 60 decibels of dynamic range and
plus or minus two decibels of accuracy.

00:00:45.349 --> 00:00:49.910
The reading travels by Bluetooth
Low Energy up to 30 metres,

00:00:49.950 --> 00:00:53.667
and the module runs 10
hours on 1 9 volt battery.

00:00:55.250 --> 00:00:59.534
The system has two parts. The
measurement module, on the hotstick,

00:00:59.574 --> 00:01:03.137
faces the device under test
with its capacitive sensor.

00:01:03.177 --> 00:01:06.871
It sends each reading by
Bluetooth to the display module.

00:01:06.911 --> 00:01:12.177
From there, the saved measurements leave
by Wi-Fi or a hotspot, as a spreadsheet.

00:01:16.184 --> 00:01:20.890
The measurement module is sealed to
IP 66 and weighs point 4 3 kilos.

00:01:20.930 --> 00:01:26.117
The capacitive sensor at its head turns
to any angle, to suit the accessory.

00:01:26.157 --> 00:01:30.794
At the other end, the universal
fitting takes any standard hotstick.

00:01:36.269 --> 00:01:38.875
On its face, the module shows its state.

00:01:38.915 --> 00:01:42.051
The on and off key, the
battery level indicator,

00:01:42.091 --> 00:01:46.352
and the Bluetooth indicator, which
shows the link to the display.

00:01:46.392 --> 00:01:51.446
At switch on, the module runs a complete
self test of its analogue front end.

00:01:55.917 --> 00:02:00.640
The display module is a rugged
5 and a half inch touch screen,

00:02:00.680 --> 00:02:04.020
readable in sunlight
and usable with gloves.

00:02:04.060 --> 00:02:08.553
It is sealed to IP 68, meets
MIL standard 8 10 G for shock,

00:02:08.593 --> 00:02:12.394
drop and vibration, and
its battery lasts all day.

00:02:15.640 --> 00:02:19.063
Everything travels in one
compact, semi rigid case:

00:02:19.103 --> 00:02:23.816
the measurement module, the display
module, the USB cable and charger,

00:02:23.856 --> 00:02:28.434
and an arm band to wear the display
while both hands hold the stick.

00:02:30.735 --> 00:02:35.304
Setting up takes a minute. Fit the 9
volt battery and switch the module on:

00:02:35.344 --> 00:02:40.343
it tests itself. Open the application on
the display and check the Bluetooth link.

00:02:40.383 --> 00:02:42.371
Mount the module on the hotstick,

00:02:42.411 --> 00:02:45.874
and turn the sensor to suit
the accessory to be measured.

00:02:52.019 --> 00:02:55.010
The operator stays on the
ground, or in a bucket,

00:02:55.050 --> 00:02:58.227
and brings the sensor to
the accessory on the stick.

00:02:58.267 --> 00:03:01.506
There is no contact with
the conductor and no outage.

00:03:01.546 --> 00:03:04.476
The reading appears on
the display in real time,

00:03:04.516 --> 00:03:08.002
so the operator never has to
approach the energised part.

00:03:12.702 --> 00:03:15.378
Observation mode measures a single device.

00:03:15.418 --> 00:03:18.353
The level is plotted in
decibels against time,

00:03:18.393 --> 00:03:21.262
so its behaviour can be
followed at a glance.

00:03:21.302 --> 00:03:26.565
An audio cue follows the signal, and noise
averaging and a timer delay can be set.

00:03:31.431 --> 00:03:35.839
Comparison mode puts several measurements
side by side in a single test,

00:03:35.879 --> 00:03:39.237
for example the same accessory
on each of the 3 phases.

00:03:39.277 --> 00:03:42.079
The difference between
them is shown directly,

00:03:42.119 --> 00:03:45.168
and the one that stands
out is the one to look at.

00:03:47.905 --> 00:03:50.686
Each recording can carry its evidence:

00:03:50.726 --> 00:03:54.620
a picture or a video of the
accessory, an audio note,

00:03:54.660 --> 00:03:58.183
text, tags, and the GPS
coordinates of the site.

00:03:58.223 --> 00:04:03.231
1000 of devices can be surveyed,
and each one is easy to find again.

00:04:06.228 --> 00:04:11.120
To export, connect the display to Wi-Fi
or a hotspot and choose a recipient.

00:04:11.160 --> 00:04:15.078
The saved measurements and their
annotations arrive by email,

00:04:15.118 --> 00:04:17.479
as a link, in a standard spreadsheet.

00:04:17.519 --> 00:04:21.178
There is no software to install
and no account to create.

00:04:25.224 --> 00:04:28.446
Four rules. The sensor
never touches the conductor.

00:04:28.486 --> 00:04:33.244
The stick is an insulated hotstick,
and the site rules for live work apply.

00:04:33.284 --> 00:04:35.611
Keep within the 30 metre radio range.

00:04:35.651 --> 00:04:39.577
And replace the 9 volt battery
when its indicator asks for it.

00:04:46.409 --> 00:04:51.548
It is used to build preventive maintenance
programmes for overhead apparatus:

00:04:51.588 --> 00:04:55.113
cable heads, line arresters,
insulators and bushings,

00:04:55.153 --> 00:04:59.350
on medium and high voltage, in
substations and along the lines.

00:05:02.959 --> 00:05:05.661
Partial discharge detection, from Amperis.