00:00:00.140 --> 00:00:06.200
How the APQM-700 records a network for
weeks without a screen, how it is connected,

00:00:06.240 --> 00:00:09.500
and how its five lights tell you
that the connection is right.

00:00:11.770 --> 00:00:13.990
Load studies, supply audits,

00:00:14.030 --> 00:00:17.330
and the search for a disturbance
all need the same thing.

00:00:17.370 --> 00:00:20.910
Data from the real network,
over days or weeks,

00:00:20.950 --> 00:00:24.690
often on a pole or in a cabinet
where nobody stays to watch.

00:00:24.730 --> 00:00:28.630
A compact, sealed recorder
does exactly that job.

00:00:31.340 --> 00:00:38.600
Every parameter is measured to
class S of IEC 60143-0. For voltage

00:00:38.640 --> 00:00:44.380
inputs up to 760 volts, for current
inputs with clamps up to 6 kiloamps,

00:00:44.420 --> 00:00:48.600
and up to 1100 recorded
parameters, harmonics included.

00:00:53.240 --> 00:00:55.420
Three cable glands underneath.

00:00:55.460 --> 00:00:59.040
The current inputs, the
four voltage leads L1,

00:00:59.080 --> 00:01:03.100
L2, L3 and N, and the red power leads.

00:01:03.140 --> 00:01:05.820
There is no display, five
lights and two lights.

00:01:05.860 --> 00:01:10.800
Two buttons, on and start stop are
the whole user interface on site.

00:01:13.900 --> 00:01:15.880
The lights replace the screen.

00:01:15.920 --> 00:01:18.980
On is green. Log flashes while recording.

00:01:19.020 --> 00:01:22.780
Error flashes when the connection
does not match the configuration.

00:01:22.980 --> 00:01:26.760
MEM warns about the memory card
and bad about a low battery.

00:01:34.890 --> 00:01:37.990
there is no screen, the work
starts on the computer.

00:01:38.150 --> 00:01:42.810
Configure the network type, nominal
voltage, clamps, and what to record.

00:01:42.850 --> 00:01:46.370
Mount the analyzer on
a DIN rail or a pole.

00:01:46.410 --> 00:01:50.010
Connect it. Check that error
stays off, and press start.

00:01:56.250 --> 00:02:01.730
a single phase supply, the blue end lead
goes to the neutral, and L1 to the phase.

00:02:01.770 --> 00:02:06.670
The clamp goes round L1, with its
arrow pointing towards the load.

00:02:06.710 --> 00:02:09.650
A second clamp on the neutral is optional.

00:02:12.080 --> 00:02:17.120
a four-wire three-phase network,
the clips go to N, L1, L2,

00:02:17.160 --> 00:02:21.740
and L3. Then one clamp per phase,
and a fourth on the neutral.

00:02:21.780 --> 00:02:26.520
The neutral clamp is needed for the
total apparent power and power factor.

00:02:29.730 --> 00:02:34.490
Without a neutral, the voltage channels
are referenced to the N input.

00:02:34.530 --> 00:02:39.250
So N goes to L3. L1 and
L2 go to their phases.

00:02:39.290 --> 00:02:41.730
The L3 input is then optional.

00:02:41.770 --> 00:02:46.430
With the Aron method, two
clamps on L1 and L3 are enough.

00:02:46.470 --> 00:02:48.650
The third current is calculated.

00:02:52.450 --> 00:02:56.610
it measures, the analyzer compares
the network with its configuration.

00:02:56.650 --> 00:03:02.150
Error starts flashing if a voltage is
15% off nominal, if an angle is wrong,

00:03:02.190 --> 00:03:06.770
if the frequency is off, or if the
clamp currents do not add up to zero.

00:03:06.810 --> 00:03:08.730
Fix it before leaving the site.

00:03:14.330 --> 00:03:19.090
Parameter groups are switched on or off,
so the card holds only what is needed.

00:03:19.130 --> 00:03:21.730
Averages from 1 second to 30 minutes,

00:03:21.770 --> 00:03:24.930
with minimum, maximum,
and instantaneous values.

00:03:24.970 --> 00:03:29.770
Dips, swells, and interruptions are
logged as events with their waveform,

00:03:29.810 --> 00:03:34.350
and a half-cycle mode records inrush
currents for up to 60 seconds.

00:03:40.320 --> 00:03:46.740
The data stays on a 2 GB microSD
card, expandable to 32. It is read

00:03:46.780 --> 00:03:51.560
over USB or with a card reader, and
the PC software draws the graphs

00:03:51.600 --> 00:03:57.120
and writes the EN 50160 report, or
a report against your own limits.

00:04:00.890 --> 00:04:05.830
housing is sealed to IP65, so it
can hang on a pole in rain or snow.

00:04:05.870 --> 00:04:11.190
Below zero, a heater keeps the electronics
warm, down to minus 20 degrees.

00:04:11.290 --> 00:04:15.770
If the supply fails, the battery
keeps recording for at least 6 hours,

00:04:15.810 --> 00:04:19.270
and recording resumes by
itself when the power returns.

00:04:23.510 --> 00:04:30.150
Measuring Category 4 at
300 volts, 3 at 600, IP65,

00:04:30.210 --> 00:04:35.950
200 by 180 by 77 millimeters,
and about 1.6 kilos.

00:04:39.210 --> 00:04:42.150
Load recording in
industry and maintenance,

00:04:42.270 --> 00:04:47.630
4-quadrant power in wind and solar
plants, supply audits to EN 50160,

00:04:47.670 --> 00:04:51.850
and tracing disturbances in
substations and low-voltage boards.

00:04:56.720 --> 00:04:59.800
Power Quality Analysis, from Amperis.