WEBVTT

00:00:00.501 --> 00:00:02.963
How the CAT is wired to a circuit breaker,

00:00:03.003 --> 00:00:06.836
what every cable is for, and the
order the job has to be done in.

00:00:10.611 --> 00:00:13.118
Four things before a single clamp goes on.

00:00:13.158 --> 00:00:17.485
The breaker is disconnected or separated
from its circuit on both sides.

00:00:17.525 --> 00:00:20.093
The breaker is earthed
to protective earth.

00:00:20.133 --> 00:00:24.277
The CAT is earthed too, with the
cable supplied with it and no other.

00:00:24.317 --> 00:00:28.280
And the CAT is switched off while
cables are connected or removed.

00:00:35.767 --> 00:00:38.722
And the order is not a
preference, it is a rule.

00:00:38.762 --> 00:00:42.030
Cables go to the CAT first
and to the breaker second.

00:00:42.070 --> 00:00:45.774
Coming off, they leave the
breaker first and the CAT second.

00:00:45.814 --> 00:00:48.457
The earth wire is
disconnected last of all.

00:00:53.953 --> 00:00:57.945
If the instrument does not have the
both sides grounded timing feature,

00:00:57.985 --> 00:01:02.148
the earthing is handled the conventional
way, and it has its own sequence.

00:01:06.523 --> 00:01:11.866
This is the front panel, and these are
the 6 connectors you will actually wire.

00:01:11.906 --> 00:01:15.750
Main contacts by phase,
auxiliary contacts, coil control,

00:01:15.790 --> 00:01:19.021
coil supply, analog channels
and the transducer.

00:01:23.411 --> 00:01:24.824
And the 6 you operate.

00:01:24.864 --> 00:01:28.917
Mains in, the on off button, the
earth stud, the touch screen,

00:01:28.957 --> 00:01:33.275
the START button, and the flash
drive that takes the results away.

00:01:38.081 --> 00:01:41.292
The main contact cables
come as one set per phase,

00:01:41.332 --> 00:01:46.625
and the whole colour code exists so that
nothing has to be worked out on a ladder.

00:01:46.665 --> 00:01:49.616
Phase A carries a red
ring over the connector,

00:01:49.656 --> 00:01:52.412
phase B a yellow ring,
phase C a blue ring.

00:01:52.452 --> 00:01:56.574
Inside a set, the red clamp with
a red label is the first break,

00:01:56.614 --> 00:02:01.841
the red clamp with a blue label is the
second, and the black clamp is the common.

00:02:07.008 --> 00:02:09.784
This is a live tank
breaker with 4 breaking

00:02:09.824 --> 00:02:12.862
elements per phase, wired
the conventional way.

00:02:12.902 --> 00:02:15.677
The instrument goes on
the ground, earthed,

00:02:15.717 --> 00:02:18.559
and then the hookup is
built phase by phase:

00:02:18.599 --> 00:02:21.178
A one and A two on the first two breaks,

00:02:21.218 --> 00:02:25.500
A 3 and A 4 on the next, and the
black N clamp on the common side.

00:02:30.998 --> 00:02:35.707
And this is the same job on a dead tank
breaker, with both sides grounded timing.

00:02:35.747 --> 00:02:40.397
The earths stay on. A current cable with
branch connectors feeds the whole line,

00:02:40.437 --> 00:02:45.556
and an AC clamp on each tank picks up the
current that flows through the closed contact.

00:02:52.512 --> 00:02:54.209
In the yard it looks like this.

00:02:54.249 --> 00:02:58.805
The clamp goes on the terminal itself, and
nothing about the connection is clever:

00:02:58.845 --> 00:03:03.289
what matters is that it is on the right
terminal, tight, and on the right phase.

00:03:07.970 --> 00:03:12.738
The coil control wiring, on a breaker
with 3 independently operated poles.

00:03:12.778 --> 00:03:16.116
Each coil control cable
carries a close and an open,

00:03:16.156 --> 00:03:21.184
and the coil supply input cables come
from whatever feeds the control circuit.

00:03:25.438 --> 00:03:29.241
When the station battery is not
available, or should not be used,

00:03:29.281 --> 00:03:33.617
an external source powers the coils
and the spring charging motor instead.

00:03:33.657 --> 00:03:36.159
The CAT drives the
close and open switches,

00:03:36.199 --> 00:03:38.820
and the supply comes
from the unit beside it.

00:03:43.557 --> 00:03:46.585
This is the measurement
everything else rests on:

00:03:46.625 --> 00:03:49.716
the current in the trip
coil during one operation.

00:03:49.756 --> 00:03:54.286
Six things happen in it, and each one
is a piece of the mechanism moving.

00:03:54.326 --> 00:03:57.918
Learn these 6 and you can read
a breaker from one capture.

00:04:03.161 --> 00:04:06.125
And with a transducer
fitted, the travel curve.

00:04:06.165 --> 00:04:10.344
This is the contact actually moving,
and it is where contact wipe,

00:04:10.384 --> 00:04:13.668
over-travel, rebound and
average velocity come from.

00:04:13.708 --> 00:04:16.480
None of these can be
measured any other way.

00:04:21.181 --> 00:04:25.112
The same instrument measures the
resistance of the main contacts.

00:04:25.152 --> 00:04:28.533
Current cables on the outside,
sense cables inside them,

00:04:28.573 --> 00:04:32.992
so the drop is measured across the
contact and not across the test leads.

00:04:35.886 --> 00:04:39.968
And gas insulated switchgear, where
there is nothing to clamp onto.

00:04:40.008 --> 00:04:44.889
A test module sits next to the CAT, connects
to it with one communication cable,

00:04:44.929 --> 00:04:49.072
and takes the current cables and
the AC clamps out to the enclosure.

00:04:52.335 --> 00:04:56.638
Auxiliary contacts have 4
timing channels of their own,

00:04:56.678 --> 00:05:00.506
on inputs labelled one a,
one b, two a and two b.

00:05:00.546 --> 00:05:04.612
They are what you put on
the 52 a and 52 b contacts.

00:05:07.863 --> 00:05:12.746
Four analog channels take anything else
worth recording alongside the operation:

00:05:12.786 --> 00:05:17.791
the station battery voltage, the motor
current through a clamp, the motor voltage.

00:05:17.831 --> 00:05:21.299
They are isolated from everything
else in the instrument,

00:05:21.339 --> 00:05:24.129
and the panel supplies
24 volts for the clamp.

00:05:29.462 --> 00:05:31.681
Running the test itself is 5 steps,

00:05:31.721 --> 00:05:34.909
and 4 of them happen before
anybody presses START.

00:05:37.698 --> 00:05:42.688
Two checks worth knowing, because they
separate a wiring fault from a breaker fault.

00:05:42.728 --> 00:05:47.358
If the main contacts read wrongly, short
the clamps together and run the test:

00:05:47.398 --> 00:05:50.771
what you should see is a closed
contact on every channel.

00:05:50.811 --> 00:05:55.382
If a coil does not operate, check the
coil supply before suspecting the coil.

00:06:02.840 --> 00:06:05.183
Circuit breaker testing, from Amperis.