00:00:00.510 --> 00:00:04.626
What the ET91 measures on power
line carrier and FDM systems,

00:00:04.666 --> 00:00:10.077
how it is connected, and how it runs tests
from one end of a line, or from both.

00:00:13.201 --> 00:00:18.319
A power line carrier link, or an FDM
system, carries many channels side by side.

00:00:18.359 --> 00:00:22.510
To commission or maintain one,
you have to inject a known signal,

00:00:22.550 --> 00:00:25.799
and then measure the level
of exactly one frequency

00:00:25.839 --> 00:00:29.345
among all the others, on a
line that may be in service.

00:00:33.158 --> 00:00:37.674
The ET91 is a generator, a
selective and wideband level meter,

00:00:37.714 --> 00:00:42.010
a measuring bridge and a
high-resolution spectrum analyser,

00:00:42.050 --> 00:00:48.697
all from 100 hertz to 2400 kilohertz, in
one-hertz steps, and on battery for about 8 hours.

00:00:51.712 --> 00:00:55.519
Everything is driven from the
menus on the colour display.

00:00:55.559 --> 00:00:59.432
The 6 function keys below it
change meaning with each mode.

00:00:59.472 --> 00:01:02.616
Numbers, cursors, enter
and escape on the right,

00:01:02.656 --> 00:01:09.248
start and stop to run the measurement, and 4 LEDs
for mains, charge, measurement and remote control.

00:01:13.490 --> 00:01:17.986
On the top panel: the input
for the mains or car adapter,

00:01:18.026 --> 00:01:22.204
a USB port for the PC and
another for a memory stick.

00:01:22.244 --> 00:01:26.104
Then L2, the output, and
L1, the measuring input,

00:01:26.144 --> 00:01:31.197
each one balanced, on 4 millimetre
sockets, and coaxial, on BNC.

00:01:35.729 --> 00:01:40.772
Switch on: the battery level appears,
then a self-test, and the main menu.

00:01:40.812 --> 00:01:43.381
Before measuring, calibrate the level:

00:01:43.421 --> 00:01:47.915
connect L1 to L2 with the balanced
cable, press CAL, and continue.

00:01:47.955 --> 00:01:51.074
The calibration then
holds until the next one.

00:01:55.573 --> 00:02:00.827
FDM test instructions give the
frequency as carrier plus or minus tone.

00:02:00.867 --> 00:02:03.734
The ET91 takes it in exactly that form:

00:02:03.774 --> 00:02:07.686
type the carrier, type the
tone, and it tunes itself.

00:02:07.726 --> 00:02:11.265
Five bandwidths, from 20
hertz to 3.1 kilohertz,

00:02:11.305 --> 00:02:15.738
and a minimum and maximum limit
give a pass or fail at once.

00:02:21.523 --> 00:02:27.027
In transmitter and receiver mode it sends
on L2 and measures on L1 at the same time.

00:02:27.067 --> 00:02:31.118
In tracking mode the receiver
follows the generator by itself:

00:02:31.158 --> 00:02:34.418
change the audio test tone,
and the meter moves to

00:02:34.458 --> 00:02:37.916
carrier plus or minus that
tone, without touching it.

00:02:41.424 --> 00:02:46.442
On a working PLC line, the instrument
is connected in parallel with the line,

00:02:46.482 --> 00:02:48.938
through the 40 decibel attenuator pad:

00:02:48.978 --> 00:02:52.222
first to the instrument's
input, then to the line.

00:02:52.262 --> 00:02:54.784
It listens without disturbing the link,

00:02:54.824 --> 00:02:58.200
and the spectrum analyser
shows every carrier on it.

00:03:02.078 --> 00:03:07.973
The spectrum analyser covers ranges
from 4 kilohertz up to 2.4 megahertz,

00:03:08.013 --> 00:03:11.062
with a zoom for the narrow bandwidths.

00:03:11.102 --> 00:03:15.533
Normal, peak, average or
smoothed average, in decibels,

00:03:15.573 --> 00:03:19.923
dBm or dBm per hertz, down
to minus 140 dBm per hertz.

00:03:23.104 --> 00:03:28.249
The built-in bridge measures
longitudinal balance to ITUTO point 9,

00:03:28.289 --> 00:03:32.814
return loss and impedance, and
near-end crosstalk and loss.

00:03:32.854 --> 00:03:37.922
Noise is measured with the psophometric
filter of ITUTO point 4 1,

00:03:37.962 --> 00:03:43.648
and impulse noise from 500 nanoseconds,
over one second or up to 72 hours.

00:03:46.916 --> 00:03:51.823
For a cable or a voice channel, two
instruments work together, one at each end.

00:03:51.863 --> 00:03:54.578
One is set as master
and the other as slave,

00:03:54.618 --> 00:03:57.896
and they talk to each other
over the line under test.

00:03:57.936 --> 00:04:00.401
Connect each one to its end of the pair.

00:04:05.732 --> 00:04:08.956
At the far end, choose
slave and the connector.

00:04:08.996 --> 00:04:13.817
At the near end, choose master, the
frequency range and the impedance,

00:04:13.857 --> 00:04:16.247
and tick the measurements you want.

00:04:16.287 --> 00:04:18.886
When SLAVE READY appears, press start.

00:04:18.926 --> 00:04:21.386
Loss, noise, return loss, impedance,

00:04:21.426 --> 00:04:25.136
balance and crosstalk are
measured in both directions.

00:04:32.700 --> 00:04:34.812
The master collects everything.

00:04:34.852 --> 00:04:39.325
The list of results appears first,
and each line opens its graph,

00:04:39.365 --> 00:04:41.824
with a cursor to read any frequency.

00:04:41.864 --> 00:04:44.809
Return loss, for
instance, is shown for the

00:04:44.849 --> 00:04:47.725
master end and the slave end side by side.

00:04:53.150 --> 00:04:55.987
It keeps 100 test setups and 100 results.

00:04:56.027 --> 00:05:00.409
They move to a PC on a memory
stick, with no driver to install,

00:05:00.449 --> 00:05:05.252
or over the USB cable with the PC
software, which prints the results,

00:05:05.292 --> 00:05:09.252
exports them, and shows the
spectrogram option over time.

00:05:12.676 --> 00:05:16.283
The nickel metal hydride
battery gives about 8 hours,

00:05:16.323 --> 00:05:23.852
and recharges inside the instrument in less than 3 hours,
from the mains adapter or from a 12 volt car socket.

00:05:23.892 --> 00:05:27.223
The line inputs are
protected up to 200 volts DC,

00:05:27.263 --> 00:05:29.769
and 60 volts of longitudinal voltage.

00:05:33.023 --> 00:05:38.084
It is used to commission and maintain
power line carrier links and FDM systems,

00:05:38.124 --> 00:05:42.474
to check level, noise, carrier leak
and crosstalk in voice channels,

00:05:42.514 --> 00:05:46.994
to characterise cables, and to hunt
interference on a line in service.

00:05:51.901 --> 00:05:54.130