The Shark 200: a revenue-grade
panel meter that also logs,

00:00:04.274 --> 00:00:07.539
records power quality and
grows with plug-in cards.

00:00:07.579 --> 00:00:12.725
What it measures, what it keeps, and how
it talks to the rest of the substation.

00:00:18.822 --> 00:00:23.244
A single main meter tells you how much
energy came in, not where it went.

00:00:23.284 --> 00:00:26.361
A meter on each feeder,
transformer or tenant does,

00:00:26.401 --> 00:00:32.046
provided its numbers are good enough to bill
with, and it keeps them when nobody is watching.

00:00:36.278 --> 00:00:42.506
It is a class 0.2 meter, to ANSI C
12 point 20 and IEC 62053 dash 22.

00:00:42.546 --> 00:00:47.502
It samples every channel at
over 400 samples per cycle,

00:00:47.542 --> 00:00:55.677
analyses harmonics to the 40th order and records
waveforms at up to 512 samples per cycle.

00:00:59.733 --> 00:01:04.781
On the front, 3 lines of bright red
digits show phases A, B and C at once.

00:01:04.821 --> 00:01:07.875
MENU, ENTER and the two
arrow keys set it up.

00:01:07.915 --> 00:01:13.376
The infrared port programs it from a
laptop, the load bar gives an analogue feel

00:01:13.416 --> 00:01:18.877
of the current, and the watt-hour pulse
lets a test standard check its accuracy.

00:01:24.340 --> 00:01:28.088
Voltage line to neutral
is measured to 0.1%,

00:01:28.128 --> 00:01:32.564
and current, power, energy
and power factor to 0.2%.

00:01:32.604 --> 00:01:35.404
Frequency, to 7000ths of a hertz.

00:01:35.444 --> 00:01:41.344
Every value can be scaled to the
primary side of any CT and PT ratio.

00:01:46.472 --> 00:01:49.462
Functions are unlocked with V Switch keys,

00:01:49.502 --> 00:01:53.502
in the field, without taking
the meter out of the panel.

00:01:53.542 --> 00:01:56.243
Each key includes everything below it:

00:01:56.283 --> 00:01:59.345
from plain multifunction
metering in V one,

00:01:59.385 --> 00:02:03.674
up to 512 samples per cycle and
4 megabytes of memory in V6.

00:02:08.256 --> 00:02:13.382
With logging enabled it keeps 3 historical
logs of more than 64 parameters each,

00:02:13.422 --> 00:02:18.741
with their own intervals, one for billing
and another for engineering, for example.

00:02:18.781 --> 00:02:23.003
Alarms, IO changes and system events
are logged with a time stamp,

00:02:23.043 --> 00:02:26.231
so any reset or change of
settings leaves a trace.

00:02:32.358 --> 00:02:38.529
From V5, a voltage sag, a swell or a
current fault triggers a waveform capture,

00:02:38.569 --> 00:02:45.291
with cycles before and after the event, kept
in a circular buffer of up to 170 events.

00:02:45.331 --> 00:02:50.952
A separate log plots each voltage
event on the CBEMA or SEMI F 47 curve,

00:02:50.992 --> 00:02:53.940
without downloading a single waveform.

00:02:57.887 --> 00:03:02.698
As standard it has an RS-485
port with Modbus or DNP3,

00:03:02.738 --> 00:03:06.382
the infrared port and a KYZ energy pulse.

00:03:06.422 --> 00:03:09.077
The option slots add Ethernet:

00:03:09.117 --> 00:03:15.455
one card with a web server, Modbus
TCP and DNP3, or one with IEC 61850.

00:03:15.495 --> 00:03:20.756
Two cards give two Ethernet
ports with their own addresses.

00:03:23.584 --> 00:03:28.989
The same two slots take IO cards, and
the meter detects which card is fitted.

00:03:29.029 --> 00:03:33.515
Analogue outputs of zero to one
or 4 to 20 milliamps for an RTU,

00:03:33.555 --> 00:03:38.040
pulse outputs, relays with status
inputs, or a fibre optic link.

00:03:38.080 --> 00:03:41.293
Cards can be ordered
later and fitted on site.

00:03:46.021 --> 00:03:50.275
In a substation one meter covers
voltage and frequency recording,

00:03:50.315 --> 00:03:54.304
the watch on transformers and
line regulators, and telemetry.

00:03:54.344 --> 00:03:58.268
RS-485, Ethernet and analogue
outputs work at the same time,

00:03:58.308 --> 00:04:04.411
so it fits whatever infrastructure is already
there, and several systems can read it at once.

00:04:10.994 --> 00:04:14.776
The same meter fits a 92
millimetre DIN cut-out or a

00:04:14.816 --> 00:04:19.113
four-inch ANSI round one, and
needs only 4 inches of depth.

00:04:19.153 --> 00:04:23.596
It replaces an old analogue
meter without enlarging the hole,

00:04:23.636 --> 00:04:27.345
and uses the CT and PT
wiring already in the panel.

00:04:27.385 --> 00:04:31.755
Without a display, the 200T
transducer mounts on a DIN rail.

00:04:36.674 --> 00:04:39.131
It is built for the switchgear:

00:04:39.171 --> 00:04:42.837
all inputs and outputs
isolated to 2500 volts,

00:04:42.877 --> 00:04:46.784
current inputs that hold
100 amps for 10 seconds,

00:04:46.824 --> 00:04:54.276
surge withstand to I triple EC 37 point 90.1,
and operation from minus 20 to plus 70 degrees.

00:04:56.888 --> 00:05:01.216
Its place is in utility, industrial,
commercial and campus metering

00:05:01.256 --> 00:05:06.170
and submetering, in substation telemetry,
in load and power quality studies,

00:05:06.210 --> 00:05:10.081
and wherever an analogue panel
meter is due for replacement.

00:05:14.316 --> 00:05:21.738
In figures: 20 to 576 volts line to
neutral, 5 amp or one amp CT secondaries,

00:05:21.778 --> 00:05:28.909
a universal supply of 90 to 265 volts
AC, and a meter of under a kilogram.

00:05:31.167 --> 00:05:33.711
Power network analysers, from Amperis.