00:00:00.514 --> 00:00:04.812
What the TWA Standard Series measures,
how it is connected to each kind

00:00:04.852 --> 00:00:09.149
of transformer, and how a test is
run from the first clamp to the last.

00:00:12.006 --> 00:00:17.754
Winding resistance finds loose joints, broken
strands and worn tap changer contacts.

00:00:17.794 --> 00:00:20.027
The difficulty is the inductance:

00:00:20.067 --> 00:00:23.610
a power transformer resists
every change of current,

00:00:23.650 --> 00:00:28.709
so a reading can take minutes to settle,
on 6 windings and dozens of taps.

00:00:34.603 --> 00:00:40.248
The range runs from a 10th of a micro-ohm
to 10 kilo-ohms, selected automatically.

00:00:40.288 --> 00:00:44.270
The test current goes from 5
milliamps to 25 amps of true,

00:00:44.310 --> 00:00:50.302
ripple-free direct current, with up to 55
volts available to saturate the core quickly.

00:00:54.162 --> 00:00:59.421
There are two models. They share the range,
the current and the demagnetisation.

00:00:59.461 --> 00:01:02.800
The TWA40D adds what a full
tap changer test needs:

00:01:02.840 --> 00:01:06.377
all 3 phases at once, a
channel for the motor current,

00:01:06.417 --> 00:01:10.351
and a sampling step of a 10th
of a millisecond instead of 4.

00:01:15.625 --> 00:01:18.799
On the right, the 4 H
sockets for the high voltage

00:01:18.839 --> 00:01:23.878
side and the 4 X sockets for the low
voltage side. On the left, the earth stud,

00:01:23.918 --> 00:01:29.150
the tap changer control socket and the
motor current input. And the lamp to learn:

00:01:29.190 --> 00:01:33.136
discharge. While it is lit,
nothing comes off the transformer.

00:01:40.337 --> 00:01:43.208
With it come the mains and earth cables,

00:01:43.248 --> 00:01:48.376
a 5 metre tap changer control cable,
the USB cable and the PC software.

00:01:48.416 --> 00:01:51.651
The winding leads are
two sets of 4, H and X,

00:01:51.691 --> 00:01:58.128
10 metres as standard with TTA clamps, and
the same sets fit the TRT turns ratio testers.

00:02:02.511 --> 00:02:04.596
The order is part of the safety.

00:02:04.636 --> 00:02:10.176
The transformer is isolated from line and
load, with one end of the winding earthed.

00:02:10.216 --> 00:02:13.629
The instrument is earthed
first, with its own cable.

00:02:13.669 --> 00:02:17.083
Leads go to the instrument,
then to the transformer,

00:02:17.123 --> 00:02:19.740
and come off in reverse, the earth last.

00:02:24.762 --> 00:02:28.628
A three-phase transformer is
connected once. The earth first.

00:02:28.668 --> 00:02:31.830
Then the 4 H leads onto
the high voltage bushings,

00:02:31.870 --> 00:02:34.904
and the 4 X leads onto
the low voltage bushings.

00:02:34.944 --> 00:02:38.875
The current flows through both
windings of each limb together,

00:02:38.915 --> 00:02:43.870
so the core saturates sooner, and all 6
resistances come from this one hookup.

00:02:49.128 --> 00:02:53.628
An autotransformer takes the same
8 leads, with one difference:

00:02:53.668 --> 00:02:57.088
H0 and X0 both go to the
common neutral bushing.

00:02:57.128 --> 00:03:02.925
And when the low voltage side is tested
on its own, the H leads are disconnected.

00:03:05.474 --> 00:03:10.413
A single-phase transformer needs
only two leads from each set:

00:03:10.453 --> 00:03:17.159
H1 and H0 across the high voltage winding,
X1 and X0 across the low voltage winding.

00:03:17.199 --> 00:03:22.700
On a single-phase autotransformer,
H0 and X0 share the same terminal.

00:03:24.310 --> 00:03:26.636
The full setup for a tap changer test.

00:03:26.676 --> 00:03:30.746
The earth, the H and X leads, the
temperature probe on the tank to

00:03:30.786 --> 00:03:33.735
correct the result to the
reference temperature,

00:03:33.775 --> 00:03:37.783
the current clamp on the tap
changer motor supply, on the TWA40D,

00:03:37.823 --> 00:03:43.138
and the control cable into the motor drive,
so the instrument changes the taps itself.

00:03:49.538 --> 00:03:53.918
The control cable is simply two
dry contacts. Brown is the common.

00:03:53.958 --> 00:03:58.739
Pressing UP closes yellow to brown,
pressing DOWN closes green to brown,

00:03:58.779 --> 00:04:02.690
in parallel with the raise and
lower controls of the drive.

00:04:02.730 --> 00:04:05.971
So one operator changes
taps from the instrument,

00:04:06.011 --> 00:04:08.449
without walking to the operation box.

00:04:13.102 --> 00:04:16.373
At the instrument the test
is set in the Test menu:

00:04:16.413 --> 00:04:21.047
the current, whether there is a tap
changer, the test type and the side.

00:04:21.087 --> 00:04:24.227
Then the vector group,
because each configuration

00:04:24.267 --> 00:04:27.149
has its own algorithm
for fast stabilisation.

00:04:27.189 --> 00:04:31.238
Press START, watch the deviation
fall towards zero, and record.

00:04:31.278 --> 00:04:34.614
The instrument moves on to
the next phase by itself.

00:04:39.032 --> 00:04:43.929
In OLTC mode the current keeps flowing
while the tap changer operates,

00:04:43.969 --> 00:04:46.469
and every change leaves a short dip.

00:04:46.509 --> 00:04:51.829
Its depth, the transition ripple, and
its duration are measured at each tap.

00:04:51.869 --> 00:04:54.933
A dip out of line is
the one to investigate.

00:04:54.973 --> 00:04:59.447
The TWA40D records all 3 phases
at once, with the motor current.

00:05:05.388 --> 00:05:08.804
A direct current test
leaves the core magnetised,

00:05:08.844 --> 00:05:14.024
which means inrush at switch-on, false
readings and wrong relay operation.

00:05:14.064 --> 00:05:16.140
So demagnetisation comes last.

00:05:16.180 --> 00:05:19.314
The instrument reverses
a controlled current,

00:05:19.354 --> 00:05:23.264
each step at 60% of the one
before, down to 5 milliamps.

00:05:29.897 --> 00:05:34.623
Results stay in the instrument, 500
of them, or go out on a flash drive.

00:05:34.663 --> 00:05:39.057
The PC software, over USB, controls
the test, downloads the memory,

00:05:39.097 --> 00:05:44.022
corrects the resistance to the reference
temperature and writes the report.

00:05:44.062 --> 00:05:48.390
The dynamic resistance test and
the quick YN mode are run from it.

00:05:55.465 --> 00:05:57.833
Transformer testing, from Amperis.