The AMPI-520 digital meter is designed to measure impedance in short-circuit loops without tripping the differential protection, it also measures the protection tare, earth resistance, continuity and phase sequence check.
It also measures alternating voltage, current, frequency and power.
The meter performs Short Circuit Loop Measurement, Testing of Differential, General and Selective Protections for Differential Current, Insulation Resistance Measurement, Up to 3GΩ, Voltages: 250 V, 500 V, 1000 V, Earth Resistance Measurement, Bidirectional Continuity Test on PE Cables, Phase Sequence
It has the following characteristics:
- Short circuit loop measurement:
- Impedance measurement with 23 A (44 A phase-to-phase), short circuit resistance RZW =10Ω
- Measuring range: 95...440V, frequency 45...65 Hz
- Short circuit loop measurement with resolution 0,01 Ω , without tripping the differential protections (I∆n ≥30mA)
- Automatic short-circuit calculation, phase-neutral and phase-phase voltage detection
- UNI-Schuko plug connection for automatic measurement, AGT adapter for measurements in three-phase networks
- Testing of differential, general and selective protections for 10, 30, 100, 300, 500 and 1000 mA differential current. Measurement of insulation resistance:
- With application of the test voltages: 250 V, 500 V, 1000 V
- Average range up to 3GΩ
- UNI-Schuko plug connection for insulation measurement
- Automatic download after measurement
- Automatic measurement of all resistances on 3, 4 or 5-wire cables using the optional AUTO-ISO adapter
- Acoustic signals at 5 s intervals to obtain the insulation characteristic curve
- Surge safety protection
- Measurement of the earth resistance.
- Bidirectional continuity test on PE cables using 200 mA
- Self-calibration of test cables.
- Phase sequence check
- Battery charge indication
- Auto shut-off function
- USB Interface
- Phase sequence:
- Phase sequence display: advance, delay
- Supply voltage range UL-L : 100...440V (45...65Hz)
- Display of phase-to-phase voltages
- Measurement of active (P), reactive (Q), apparent (S) power and cosφ
- UL-N voltage range : 100...440V
- Nominal mains frequency: 45...65Hz
- Frequency measurement for voltages in the range 50...440V in the range 45.0...65.0Hz (max. accuracy ± 0.1% measured value +1 digit)
- Measure cosφ: 0.00...1.00 (resolution 0.01)
Low voltage and insulation continuity test | ||
Check the PE cable using a current of ±200 | ||
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(2% v.m. + 3 digits) |
20,0...199,9Ω | 0,1Ω | |
200...400Ω | 1Ω | |
Test current at R<2Ω: minimum 200mA at nominal battery voltage | ||
Self-calibration of test cables | ||
Two-way measurement |
Differential protection trip and response time test tA (for mode tA ) | ||||
IEC61557 measurement range: 0ms ... up to the upper limit of the displayed value | ||||
Type of | Adjustment of the multiplication factor | Range | Resolution | Accuracy |
general-purpose | 0.5*I∆n | 0...300ms | 1ms | ±(2% v.m. + 2 digits) |
1* I∆n | ||||
2* I∆n | 0...150ms | |||
5*I∆n | 0...40ms | |||
Selective | 0.5*I∆n | 0...500ms | ||
1* I∆n | ||||
2* I∆n | 0...200ms | |||
5*I∆n | 0...150ms | |||
Differential current accuracy for 0.5*I∆n :-8...0%; for 1* I∆n,2* I∆n,5*I∆n : 0...8% |
Measurement of the current threshold of the differential protection (IA) for sine-wave test current | ||||
Selected switch rated current | Range | Resolution | Measuring current | Accuracy |
10mA | 3,3...10,0mA | 0.1mA | 0.3*I∆n...1*I∆n | ±5% I∆n |
30mA | 9.0...30.0mA | |||
100mA | 33...100mA | 1mA | ||
300mA | 90...300mA | |||
500mA | 150...500mA | |||
1000mA | 330...1000mA | |||
It is possible to start the measurement from the positive or negative half of the leakage current |
Measurement of the current threshold of the differential protection for a unidirectional half period of sinusoidal waveform with a DC current offset of 6mA | ||||
Selected switch rated current | Range | Resolution | Measuring current | Accuracy |
10mA | 4.0...20.0mA | 0.1mA | 0.4*I∆n...2*I∆n | ±10% I∆n |
30mA | 12.0...42.0mA | |||
100mA | 40...140mA | 1mA | 0.4*I∆n...1.4*I∆n | |
300mA | 120...420mA | |||
500mA | 200...700mA | |||
Measurement for positive or negative leakage current is possible |
Measurement of the current threshold of the differential protection (IA ) for DC continuous test | ||||
Selected switch rated current | Range | Resolution | Measuring current | Accuracy |
10mA | 4.0...20.0mA | 0.1mA | 0.4*I∆n...2*I∆n | ±10% I∆n |
30mA | 12.0...60.0mA | 1mA | ||
100mA | 40...200mA | |||
300mA | 120...600mA | |||
500mA | 200...1000mA | |||
Measurement for positive or negative leakage current is possible | ||||
"v.m." - measured value |
Measurement of short circuit impedance Z L-PE , Z L-N , Z L-L | ||
Measurement using the current range 23/40 A according to IEC | ||
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(5% v.m. + 3 digits) |
20,0...199,9Ω | 0,1Ω | |
200...1999Ω | 1Ω | |
Voltage range: 95...270V (for Z L-PE and Z L-N ) and 95...440V (for Z L-L ) | ||
Frequency: 45...65Hz |
Measurement of short circuit loop impedance Z L-PE RCD | ||
Measured using 15 mA current range according to IEC 61557: 0.50...1999,9Ω | ||
Range | Resolution | Accuracy |
0,00...19,99Ω | 0,01Ω | ±(6% v.m. + 10 digits) |
20,0...199,9Ω | 0,1Ω | ±(6% v.m. + 5 digits) |
200...1999Ω | 1Ω | |
Voltage range: 95...270V | ||
Frequency: 45...65Hz |
Earthing resistance measurement RE | ||
Voltage range according to IEC 61557-5: 0.5...1999Ω | ||
Range | Resolution | Accuracy |
0,00...9,99Ω | 0,01Ω | ±(2% v.m. + 4 digits) |
10,0...99,9Ω | 0,1Ω | ±(2% v.m. + 3 digits) |
100...999Ω | 1Ω | |
1.00...1,99kΩ | 10Ω |
Insulation resistance measurement | |||
Measured according to IEC 61557-2: | |||
-UN=50V: 50kΩ...250MΩ | -UN=500V: 500kΩ...2GΩ | ||
-UN=100V: 100kΩ...500MΩ | -UN=1000V: 3GΩ...3GΩ | ||
-UN=250V: 250kΩ...1GΩ | |||
Range | Resolution | Accuracy | |
0...1999kΩ | 1kΩ | ±(3% v.m. + 8 digits) | |
2,00...19,99MΩ | 0,01MΩ | ||
20.0...199,9MΩ | 0,1MΩ | ||
200...999MΩ | 1MΩ | ||
1,00...3,00GΩ | 0,01GΩ | ±(4% v.m. + 6 digits) | |
With UNI-Schuko connection additional error ±2%. |
AMPI-520 detailed features | |
Electrical safety: | |
Type of insulation | Double, according to EN 61010-1 and IEC 61557, EMC |
Measurement category | CAT IV 300V according to EN 61010-1 |
Protection class, according to EN 60529 | IP54 |
Other technical data: | |
Food | LR14 alkaline batteries (5 pcs.) or Ni-MH battery set ( |
Nominal conditions of use: | |
operating temperature range | 0...+50°C |
Standard accessories:
- SCHUKO probe with power button (WS-03)
- Test cable with banana plug, 1.2 m yellow
- Test cable with banana plug, 1.2 m blue
- Test cable with banana plug, 1.2 m red
- Test cable reel with banana plug, 30 m, red
- Test cable reel with banana plug, 15 m, blue
- USB cable
- Pointed probe with banana connection, yellow
- Pointed probe with banana connection, red
- Pointed probe with banana connection, blue
- Alligator clip K02 red
- Alligator clip K02 yellow
- Ground contact javelin, 0.3m
- Transport box L1
- Straps
- LR14 battery box and batteries (C)
- Batteries
- Calibration certificate
Optional accessories:
- Test cable with banana plug, 5 m red
- Test cable with banana plug, 10 m red
- Test cable with banana plug, 20 m red
- Battery charger cable
- Car lighter compatible battery charger cable (12V)
- AGT-16P three-phase plug adapter
- AGT-32P three-phase plug adapter
- AGT-63P three-phase plug adapter
- AUTO-ISO-1000C Adapter
- Adapter TWR-1 (universal connection) for testing differential switches
- Probe with UNI-SCHUKO (WS-04)
- Grounding javelin 0.8 m
- Transport box L3
- Current clamp C3 ( =52 mm), round connection
- Ni-MH battery set, 4.8 V, 4.2 Ah
- Alligator clip K02, blue
- Staple
- Test Cable Reel
- Z7 socket adapter
- Software for creating documentation of electrical measurements
- Software for the creation of drawings and diagrams
Download the catalogue of AMPI-520 Multifunction Electrical Installation Meter.