Multifunctional meter for electrical installations

Image: Sonel MPI-502 installation tester in orange housing, display showing 228.4 V and an L-N loop impedance of 0.73 Ω, with START and ESC keys and a rotary function selector.

MODELS 502, 506, 520, 525, 530-IT, 540 & 540-PV

AMPI-502

Multifunctional meter for electrical installations

Image: Sonel MPI-502 meter with orange housing; the display shows 228.4 V and 0.73 Ω. Badges: CAT III 600 V, CAT IV 300 V, Bluetooth and IP67.

Features

  • Measuring the short circuit loop
  • Type AC and A earth leakage protection test
  • Low voltage measurement of continuity and resistance of circuits
  • Management of measurement data using open

Measured parameters

- Measuring the short circuit loop

  • Measurement of the short-circuit impedance in 220/380 V, 230/400 V, 240/415 V networks and at a frequency of 45...65 Hz, - working voltage range: 180 ... 460 V
  • Indication of the short-circuit loop resistance R and the short-circuit loop reactance X
  • Measuring the short circuit impedance with a 15 mA current without differential tripping
  • Maximum measuring current: 7.6 A (at 230 V), 13.3 A (at 400 V)

- Testing of AC and A-type earth leakage protection

  • Testing of general and selective differential protections for differential currents of 10, 30, 100, 300, 500 mA.
  • Measurement of IA and triggering time tA for the currents 0.5IΔn, 1IΔn, 2IΔn, 5IΔn
  • ER e and UB measurement without differential tripping
  • Extended AUTO function with RCD measurement, with the possibility of measuring ZL-PE with a small current
  • IA and tA measurement with RCD triggering
  • Low voltage measurement of continuity and resistance of circuits s
  • Resistance measurement with a current of ±200 mA according to IEC 61557-4
  • Autocalibration of test leads - any length of test probe can be used
  • Low-current resistance measurement with an acoustic signal

Technical specifications

Measurement of short-circuit loop impedance ZL-PE, ZL-N, ZL-L

Measurement using according to IEC 615the 7.6/13.3 A cu 557-3: 0.13...1999urrent range - from of 9 Ω
RangeResolutionBasic error
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(5% v.m. + 3 digits)
200...1999 Ω1 Ω

ZL-PE short circuit impedance measurement in RCD mode

Measured using a 15 mA current range of in accordance with IEC 61557: 0.50...1999 Ω

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω0,1 Ω 1 Ω±(6% v.m. + 5 digits)
Image: Orange handheld meter held in the hand, with digital display, keypad and coiled lead; its carrying bag behind.
Image: Hand holding an orange Sonel meter showing a reading of 557 during a measurement on an industrial installation.
Image: Orange hand-held Sonel meter with a plug adapter inserted in a socket outlet in a distribution board, showing a reading on screen.

MEASUREMENTS OF RCD CIRCUIT BREAKER PARAMETERS (VOLTAGE RANGE 180...270 V)

RCD trip test and time measurement according to IEC 61557-3: 0.13....1999 Ω of triggering tA (for the tA function)

Switch typeSetting the multiplication factorMeasuring rangeResolutionBasic error
General type0,5 IΔn 1 IΔn0...300 ms
type2 IΔn0...150 ms
5 IΔn0...40 ms1 ms±(2% v.m. + 2
Selective0,5 IΔn 1 IΔn 2 IΔn0...500 ms 0...200 ms1 msv.m. + 2 digits)
5 IΔn0...150 ms

Measurement of the IA differential cut-off current for the sinusoidal waveform test current

Current selectedMeasuring rangeResolutionTest currentBasic error
10 mA3,0...10,0 mA
30 mA9,0...30,0 mA0,1 mA0,3 IΔn...1,0±5% IΔn
100 mA30...100 mAIΔn...1,0 IΔn±5% IΔn
300 mA90...300 mA1 mA
500 mA150...500 mA
  • The start of the measurement of the positive or negative half-periods of the generated current.

IA trip current measurement for unidirectional pulsed residual current

Current selectedMeasuring rangeResolutionTest currentBasic error
10 mA4,0...20,0 mA0,1 mA0,35 IΔn ...2,0 IΔn
30 mA 100 mA 300 mA12,0...42,0 mA 40...140 mA 120...420 mA1 mA0,35 IΔn ...1,4 IΔn±10% IΔn
  • Measurement of positive or negative half-periods of the generated leakage current
Electrical safety
Insulation type according to PN-EN 61010-1 and IEC 61557double
Measurement category according to PN-EN 61010-1IV 300V
Degree of protection of the housing according to PN-EN 60529IP67
Other technical data
Dimensions220 x 98 x 58 mm
Weightapprox. 1 kg
Automatic shutdown time300, 600, 900 seconds
Number of Z and differential measurements (for Ni-Cadmium batteries)>5000 (2 per minute)
The equipment meets the requirements of the standardEN 61326-1 EN 61326-2-2

AMPI-506

Multifunctional meter for electrical installations

Image: Sonel MPI-502 meter with orange housing; the display shows 228.4 V and 0.73 Ω. Badges: CAT III 600 V, CAT IV 300 V, Bluetooth and IP67.

Measured parameters

- Measuring the short circuit loop

  • Measurement of short circuit impedance in 220/380 V, 230/400 V, 240/415 V networks and at a frequency of 45...65 Hz - Operating voltage range: 180 ... 460 V
  • Indication of the short-circuit loop resistance R and the short-circuit loop reactance X
  • Measuring the short circuit impedance with a 15 mA current without differential tripping
  • Maximum measuring current: 7.6 A (at 230 V), 13.3 A (at 400 V)

- Type AC and A earth leakage protection test

  • Testing of general and selective differential protections for differential currents of 10, 15, 30, 100, 300, 500 mA.
  • Measurement of IA and triggering time tA for the currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn

- Low voltage measurement of continuity and resistance of circuits

  • Resistance measurement with a current of ±200 mA according to IEC 61557-4
  • Autocalibration of test leads - any length of test probe can be used
  • Low-current resistance measurement with an acoustic signal

- Indications of the phase sequence

  • ER and UB measurement without differential tripping
  • Extended AUTO function with RCD measurement, with the possibility of measuring ZL-PE with a small current
  • IA and tA measurement with RCD triggering

Additional functions

  • Check the correctness of the PE conductor connection using the contact electrode.
  • Measurement of mains voltage (0...500 V) and frequency

- Insulation resistance measurements

  • Measuring voltages: 100 V, 250 V, 500 V
  • 990 result memory, wireless data transmission data to the PC
  • Illuminated keyboard

Technical specifications

Measurement of short-circuit loop impedance

ZL-PE, ZL-N, ZL-L

Measurement using the 7.6/13.3 A current range - from of according to IEC 61557-3: 0.13...1999 Ω

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(5% v.m. + 3 digits)
200...1999 Ω1 Ω

ZL-PE short circuit impedance measurement in RCD mode

Measured using a 15 mA current range of In accordance with IEC 61557: 0.50...1999 Ω

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω0,1 Ω 1 Ω±(6% v.m. + 5 digits)

Insulation resistance measurement

MEASUREMENT OF RCD CIRCUIT BREAKER PARAMETERS (VOLTAGE RANGE 180...270 V)

Disconnection test of the RCDs and measurement of the tripping time tA (for the tA measurement function)

Type of RCDSetting the multiplication factorMasuring rangeResolutionBasic error
General type0,5 IΔn 1 IΔn0...300 ms
type2 IΔn0...150 ms
5 IΔn0...40 ms1 ms±(2% v.m. + 2
Selective0,5 IΔn 1 IΔn0...500 ms1 ms+ 2 digits)
Selective2 IΔn0...200 ms
5 IΔn0...150 ms

Measurement of the trigger current of the RCD IA for pulsed differential current unidirectional

Measuring range according to IEC 61557-2

  • UISO = 100 V: 100 kΩ...99,9 MΩ
  • UISO = 250 V: 250 kΩ...199,9 MΩ
  • UISO = 500 V: 500 kΩ...599,9 MΩ
Image: Insulation resistance tables for Uiso = 100 V and 250 V: 0–1999 kΩ at 1 kΩ resolution, 2.00–19.99 MΩ at 0.01 MΩ and up to 99.9 or 199.9 MΩ at 0.1 MΩ, accuracy ±(5% m.v. + 8 digits); start of the 500 V table.
Image: Insulation resistance table for Uiso = 500 V: ranges 0–1999 kΩ, 2.00–19.99 MΩ and 20.0–599.9 MΩ, resolutions 1 kΩ, 0.01 MΩ and 0.1 MΩ, accuracy ±(5% m.v. + 8 digits).
Rated currentMeasuring rangeResolutionCurrent measurementBasic error
10 mA3,0...10,0 mA
15 mA4,5...15,0 mA0,1 mA
30 mA 100 mA9,0...30,0 mA 30...100 mA0,3 IΔn...1,0 IΔn±5% IΔn
300 mA90...300 mA1 mA
300 mA150...500 mA
  • Start of measurement from the positive or negative half-period of the forced current

Indications of the phase sequence

  • Indication of phase sequence: conforming, non-conforming
  • Mains voltage range: 100...440 V
  • Display of phase-to-phase voltage values

“v.m” - valor medido

Safety and working conditions
Measurement category according to EN 61010IV 300 V (III 600 V)
Income protectionIP67
Insulation type according to EN 61010-1 and IEC 61557double
Dimensions220 x 98 x 58 mm
Weightaprox. 0,8 kg
Memory and communication
Memory of measured results990
Data transmissionBluetooth
Other information
Memory of measured resultsEN 61326-1
Data transmissionEN 61326-2-2

AMPI-520

Multifunctional meter for electrical installations

  • The MPI-520 multifunction meter is dedicated to performing diagnostics according to IEC 61557.

Features

  • The AMPI-520 digital meter is designed to measure impedance in short circuit loops without tripping the differential protection, it also measures RCD parameters, grounding resistance, continuity and phase sequence control.
  • In addition, it measures voltage, current, frequency and AC power.

Measured parameters

- Measuring the short circuit loop

  • impedance measurement with 23 A (44 A phase to phase), short circuit resistance R =10Ω, zw
  • Measuring range: 95...440V, frequency 45...65 Hz,
  • Short circuit loop measurement with a resolution of 0.01 Ω, without triggering the ground leakage protection (I Δn ≥30mA).
  • Automatic short circuit calculation, phase-to-neutral and phase-to-phase voltage detection,
  • UNI-Schuko connector for automatic measurement, AGT adapter for measurements on three-phase networks.
Image: Sonel earth resistance meter with orange casing surrounded by its accessories: test leads, cable reels, earth spikes, clamps and crocodile clips.

- Insulation resistance measurement

  • with application of the test voltages: 250 V, 500 V, 1000 V,
  • average range up to 3GΩ,
  • UNI-Schuko connector for insulation measurement,
  • automatic discharge after measurement,
  • Automatic measurement of all resistances in 3, 4 or 5 wire cables using the optional AUTO-ISO adapter,
  • acoustic signals at 5 s intervals to obtain the insulation characteristic curve,
  • safety surge protection.

- Measuring the resistance of the earth

- Bi-directional continuity test on PE cables using 200 mA.

  • uto-calibration of test leads.
  • Checking the sequence of phases.
  • Battery charge indication.
  • Automatic shut-off function.

- USB interface.

  • Testing of differential, general and selective protections for 10, 30, 100, 300, 500 and 1000 mA differential current.

MPI-520 standard accessories

Probe SCHUKO with power button (WS-03)WAADAWS 03
Test lead with banana plug, 1.2 m yellowWAPRZ1X2YEB B
Test lead with banana plug, 1.2 m blueWAPRZ1X2BEB B
Test lead with banana plug, 1.2 m redWAPRZ1X2REB B
Test lead reel with banana plug, 30 m, red
Test lead reel with banana plug, 15 m, blueWAPRZ030REEBBSZ
USB cableWAPRZ015BUEBBSZ
Tip probe with banana plug, yellowWAPRZUS B
Tip Probe with banana plug, RedWASONYEOGB1
Tip probe with banana plug, blueWASONREOGB1
Alligator clip K02 yellowWASONBUOGB1
Alligator clip K02 blueWAKROYE0K02
Ground rod for ground contact, 0.3 mWAKROBU0K02
Carrying case L1WASONG30
StrapsWAFUTL1
Battery box and LR14 (C) batteriesWAPOZSZEKPL
BatteriesWAPOJ1
Calibration certificate

Optional accessories

Test lead with banana plug, 5 m redWAPRZ005REBB
Test Cable with banana plug, 10 m (33 ft) RedWAPRZ01REBB
Test Lead with banana plug, 20 m (65 ft) redWAPRZ002REBB
Battery charger cableWAPRZLAD230
Battery Compatible Cigarette Lighter Charger Cord (12V)WAPRZLAD212SAM
Adapter for three-phase plug AGT-16PWAADAAGT16P
Three-Phase Plug Adapter AGT-32PWAADAAGT32P
AGT-63P Three Phase Plug AdaptorWAADAAGT63P
AUTO-ISO-1000C AdaptorWAADAAISO10C
TWR-1 adapter (universal connection) for testing earth leakage circuit-breakersWAADATWR1J
Probe with UNI-SCHUKO (WS-04)WAADAWS04
Grounding Dart 0,8 mWASONG80
Carrying case L3WAFUTL
C3 Current Clamp (Ø=52 mm), round connectionWACEGC30KR
Ni-MH battery pack, 4.8 V, 4.2 AhWAAKU07
Alligator clip K02, blueWAKR0BU20K02
ClipWAZACIMA1
Test lead reelWAPOZSZP1
Z7 power socket adapterWAZASZ7
Software “SONEL PE4” for creating electrical measurement documentationWAPROSONPE4
Software for creating drawings and diagrams “SONEL Schemtaic” + “SONEL PE4”WAPROSCHEM

Technical specifications

Short circuit loop impedance measurement

ZL-PE, ZL-N, ZL-L

Measurement using the 23/40 A current range according to the standard me IEC 61557: 0.13...1999.9Ω (for 1.2 m cables)

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(5% v.m. + 3 digits)
200...1999 Ω1 Ω
  • Voltage range: 95...270V (for ZL-PE and ZL-N) and 95...440V (for ZL-L)
  • Frequency: 45...65Hz

Indications of the phase sequence

  • iindication of the sequence of phases: leading, trailing, lagging
  • Supply voltage range UL-L: 100...440V (45...65Hz) UL-L: 100...440V (45...65Hz)
  • Display of phase-to-phase voltages on the screen

Measurement of active (P), reactive power (Q), apparent (S) and cosφ

  • ULN voltage range: 0...440V
  • nominal mains frequency: 45...65Hz
  • frequency measurement for voltages in the range 50...440V in the range 45.0...65.0Hz (maximum accuracy ± 0.1% measured value +1 digit)

ZL-PE short circuit impedance measurement in RCD mode

Measurement with a range current of 15 mA according to the IEC 61557: 0.50...1999 Ω

  • cosφ measurement: 0.00...1.00 (Resolution 0.01)
RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω0,1 Ω 1 Ω±(6% v.m. + 5 digits)

Low voltage and insulation continuity test

Testing the PE cable with a current of ±200mA

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(2% v.m. + 3 digits)
200...400 Ω1 Ω
  • Voltage range: 95...270V
  • Frequency: 45...65H

Earth resistance measurement RE

  • Test current at R<2Ω: min. 200mA at rated voltage of nominal battery

Voltage range according to IEC 61557-5: 0.5...1999Ω.

  • Auto-calibration of test leads
RangeResolutionAccuracy
0,00...9,99Ω0,01 Ω±(2% v.m. + 4 digits)
10,0...99,9Ω0,1 Ω
100...999Ω1 Ω±(2% v.m. + 3 digits)
1,00...1,99kΩ0,01kΩ
  • Bidirectional measurement

Triggering and testing of the protection differential response time TA (for TA mode)

Measuring ranges according to IEC 61557: 0ms ... to upper limit of the displayed value

Type of RCDSetting the multiplication factorMeasuring rangeResolutionBasic error
Tipo gral0,5 IΔn 1 IΔn0...300 ms
Tipo gral2 IΔn0...150 ms
5 IΔn0...40 ms±(2% v.m.
0,5 IΔn 1 IΔn0...500 ms1 msv.m. + 2 digits)
Selective2 IΔn0...200 ms
5 IΔn0...150 ms

Insulation resistance measurement

Measuring range according to IEC 61557-2

for UN = 50V: 50kΩ...250MΩ; for UN = 100V: 100kΩ...500MΩ; for UN = 250V: 250kΩ...1GΩ, for UN = 500V: 500kΩ...2GΩ, for UN = 1000V: 1MΩ...3GΩ

Range *ResolutionAccuracy
0...1999kΩ1kΩ
2,00...19,99MΩ 20,0...199,9MΩ0,01MΩ 0,1MΩ±(3% v.m. + 8 digits)
200...999MΩ1MΩ
1,00...3,00GΩ0,01GΩ±(4% v.m. + 6 digits)
  • * llimited to the measuring range. With UNI-Schuko connection, additional error ±2%.

Accuracy of the differential current: for 0.5*I n: -8...0% for 1*I n, 2*I n, 5*I n: 0...8% for 1*I n, 2*I n, 5*I n: 0...8%.

Measurement of the current threshold of the differential protection (IA) for a sinusoidal test current.

Rated currentMeasuring rangeResolutionCurrent measurementBasic error
10 mA3,3...10,0mA
30 mA9,0...30,0mA0,1 mA
100 mA 300 mA 500 mA33...100mA 90...300mA 150...500mA1 mA0,3 IΔn...1,0 IΔn± 5% IDn
1000 mA330...1000mA
• It is possib half of theble to start the me e leakage currenteasurement froom the positive or neegative

Measurement of the current threshold of the differential protection (IA) for the continuous test current

Rated currentRangeResolutionCurrent measurementBasic error
10 mA4,0...20,0mA0,1 mA
30 mA12,0...60,0mA
100 mA40...200mA1 mA0,4 x IDn ...2,0 x IDn±10% IDn
300 mA120...600mA
500 mA200...1000mA
  • Positive or negative leakage current measurement is possible

“v.m.” valor medido

Measurement of the current threshold of the differential protection for a unidirectional half-period sine waveform with a DC offset of 6mA

Rated currentRangeResolutionCurrent measurementBasic error
10 mA4,0...20,0mA0,1 mA0,4 x IDn ...2,0 x IDn
30 mA12,0...42,0mA
100 mA 300 mA40...140mA 120...420mA1 mA0,4 x IDn ...1,4 x IDn±10% IDn
500 mA200...700mA
  • The measurement of a positive or negative leakage current is possible
Electrical safety
Type of insulationdouble, according to EN 61010-1 and IEC 61557
Measurement categoryCAT IV 300 V according to EN 61010-1
Protection according to EN 60529IP54
Other technical data
Power supplyLR14 alkaline batteries (5 pieces) or a set of Ni-MH batteries (optional)
Environmental conditions
Operating temperature range(0...+50°C)

AMPI-525

Multifunctional meter for electrical installations

Image: Measurement category CAT IV 300 V.

Measured parameters

- Measuring the short circuit loop

  • impedance measurement with 23 A (44 A phase to phase), short circuit resistance Rzw =10 Ω
  • Measuring range: 95...440 V, frequency 45 to 65 Hz
  • Short circuit loop measurement with a resolution of 0.01 Ω, without tripping of ground leakage protection devices (I Δn ≥30mA)
  • automatic short circuit calculation, phase and interfacial voltage detection,
  • UNI-Schuko connector for automatic measurement, AGT adapter for measurements in three-phase networks.
  • Testing of differential, general and selective protection for 10, 30, 100, 300, 500 and 1000 mA differential current (AC, type A and B).

- Measurement of insulation resistance:

Image: Orange multifunction installation tester with backlit display showing a loop impedance reading of 1.21 Ω, rotary selector and function keys.
  • Automatic measurement of all resistances in 3, 4 or 5 wire cables using the optional adapter.
  • acoustic signals at 5 s intervals to obtain the insulation characteristic curve,
  • safety surge protection.
  • Measuring the resistance of the earth connection.
  • directional continuity test of PE cables using 200 mA.
  • Self-calibration of test leads.
  • Measurement of the resistance to earth.
  • Checking the sequence of phases.
  • The memory is divided into 10 memory banks.
  • Each bank contains 99 memory cells.
  • Battery charge indication.
  • Automatic shut-off function.
  • USB interface
  • with application of the test voltages: 250V, 500V, 1000V, 2500V,
  • medium range up to G , 10 Ω
  • automatic discharge after measurement,

Technical specifications

Measurement of short-circuit loop impedance

Indications of the phase sequence

ZL-PE, ZL-N, ZL-L

  • Indication of the sequence of phases: forward, backward, reverse

Measurement using the current range 23/40 A according to to IEC 61557: 0.13...1999.9Ω (for 1.2 m cables):

  • Supply voltage range U (45...65Hz)
RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(5% v.m. + 3 digits)
200...1999 Ω1 Ω
  • Phase-to-phase voltage display on the screen

Low voltage and insulation continuity test

Testing the PE cable with a current of ±200mA

  • Voltage range: 95...270V (for ZL-PE and ZL-N) and 95...440V (for ZL-L)
RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(2% v.m. + 3 digits)
200...400 Ω1 Ω
  • Frequency: 45...65Hz

ZL-PE short circuit impedance measurement in RCD mode

Measured using a 15 mA current range of In accordance with IEC 61557: 0.50...1999 Ω

  • Voltage at open terminals: 4...9 V
  • Test current at R<2 Ω: min. 200 mA at rated voltage of the battery.
  • Auto-calibration of test leads
RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω0,1 Ω 1 Ω±(6% v.m. + 5 digits)
  • Bidirectional measurement

Differential protection trip test and response time tA (for mode tA)

Measuring ranges according to IEC 61557: 0ms ... to upper limit of the displayed value

  • Voltage range: 95...270V
  • Frequency: 45...65Hz
Type of RCDSetting the multiplication factorMeasuring rangeResolutionBasic error
General0,5 IΔn 1 IΔn0...300 ms
type2 IΔn0...150 ms
5 IΔn0...40 ms±(2%
Sélectif0,5 IΔn 1 IΔn0...500 ms1 msv.m. + 2 digits)
Sélectif2 IΔn0...200 ms
5 IΔn0...150 ms

Measuring the resistance to earth a RE

Voltage range according to IEC 61557-5: 0.5...1999Ω

RangeResolutionAccuracy
0,00...9,99Ω0,01 Ω±(2% v.m. + 4 digits)
10,0...99,9Ω0,1 Ω
100...999Ω1 Ω±(2% v.m. + 3 digits)
1,00...1,99kΩ0,01kΩ

Insulation resistance measurement

Measuring range according to IEC 61557-2

for UN = 50V: 50kΩ...250MΩ; for UN = 100V: 100kΩ...500MΩ; for UN = 250V: 250kΩ...1GΩ, for UN = 500V: 500kΩ...2GΩ, for UN = 1000V: 1MΩ...3GΩ

Accuracy of differential current: for 0.5*I n: -8...0% for 1*I n, 2*I n, 5*I n: 0...8%.

Range *ResolutionAccuracy
0...1999kΩ1kΩ
2,00...19,99MΩ 20,0...199,9MΩ0,01MΩ 0,1MΩ±(3% v.m. + 8 digits)
200...999MΩ1MΩ
1,00...3,00GΩ0,01GΩ±(4% v.m. + 6 digits)

* limited to the measuring range. With UNI-Schuko connection, additionalerror ±2%.

Measurement of the current threshold of the differential protection (IA) for a sinusoidal test current.

Rated currentMeasuring rangeResolutionCurrent measurementBasic error
10 mA3,3...10,0mA
30 mA9,0...30,0mA0,1 mA
100 mA33...100mA0,3 x IDn...1,0 x IDn± 5% IDn
300 mA 500 mA90...300mA 150...500mA1 mAx IDnIDn
1000 mA330...1000mA
  • It is possible to start the measurement from the positive or negative half of the leakage current.

Measurement of the current threshold of the differential protection (IA) for the continuous test current

Rated currentRangeResolutionCurrent measurementBasic error
10 mA4,0...20,0mA0,1 mA
30 mA12,0...60,0mA
100 mA40...200mA1 mA0,4 x IDn ...2,0 x IDn±10% IDn
300 mA120...600mA
500 mA200...1000mA
  • The measurement of a positive or negative leakage current is possible.
  • “v.m.” measured value

Measurement of the current threshold of the differential protection for a unidirectional half-period sine waveform with a DC offset of 6mA.

Rated currentRangeResolutionCurrent measurementBasic error
10 mA4,0...20,0mA0,1 mA0,4 x IDn ...2,0 x IDn
30 mA12,0...42,0mA
100 mA 300 mA40...140mA 120...420mA1 mA0,4 x IDn ...1,4 x IDn±10% IDn
500 mA200...700mA
  • Positive or negative leakage current measurement is possible
Electrical safety
Type of insulationdouble, according to EN 61010-1 and IEC 61557
Measurement categoryCAT IV 300 V according to EN 61010-1
Protection according to EN 60529IP54
Other technical data
Power supplyLR14 alkaline batteries (5 pieces) or a set of Ni-MH batteries (optional)
Condições ambientais
Operating temperature range(0...+50°C)

AMZC-530-IT

Multifunctional meter for electrical installations

Image: Sonel multifunction installation tester with display, keypad and rotary selector, alongside CAT III 600 V, CAT IV 300 V and IP54 ratings.

Measured parameters

- Measuring the short circuit loop

  • impedance measurement with 23 A (44 A phase to phase), resistencia de cortocircuito Rzw=10Ω,
  • range of measurement: 95...440V, frequency 45...65 Hz,
  • UNI-Schuko connector for insulation measurement, automatic discharge after measurement,
  • automatic measurement of all resistances in 3, 4 or 5 wire cables using the optional adapter
  • acoustic signals at 5 s intervals to obtain the insulation characteristic curve,
  • safety protection against overvoltage. .
  • Short circuit loop measurement with a resolution of 0.01Ω, without action of differential protections (I Δn ≥30mA).

- Measuring the resistance of the earth connection.

  • Measure 3 and 4p with the technical method,
  • 3p measure with the technical method + clamps,
  • automatic short circuit calculation, phase-to-neutral and phase-to-phase voltage detection,
  • UNI-Schuko connector for automatic measurement,
  • AGT adapter for measurements in three-phase networks. .
  • measure with two clamps. .
  • Measurement of soil resistivity by the Wenner method.
  • Measurement of light intensity.
  • Testing of differential, general and selective protection for differential currents of 10, 30, 100, 300, 500 and 1000 mA also in IT isolated systems.

- Measurement of insulation resistance:

  • with application of the test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V,
  • Quick check of the correct connection of the PE terminals by means of the contact electrode.
  • Measures and records voltage, frequency, AC current, cosφ, power (active, reactive and apparent), voltage harmonics and THD calculated up to 40 harmonics.
  • medium range up to 10 GΩ

- Verification of the phase sequence and the motor rotation

- Bi-directional continuity test on PE cables using 200 mA.

  • Auto-calibration of test leads.
  • Dynamically managed, tree-like memory structure (max. 10,000 results of each type of measurement) with the possibility of describing measurement points, objects, client names.
  • Checking the sequence of phases.
  • Battery charge indication.
  • Battery powered, integrated drainer. Possibility to charge the equipment on the mains or on the car cigarette lighter (12V).
  • Automatic shut-off function.

- USB interface. .

Technical specifications

Measurement of short-circuit loop impedance ZL-PE, ZL-N, ZL-L

Insulation resistance measurement

Measuring range according to IEC 61557-2

Measurement using 23/40 A current Range according to IEC 61557: 0.13...1999.9Ω (for 1.2 m cables):

for UN = 50V: 50kΩ...250MΩ; for UN = 100V: 100kΩ...500MΩ; for UN = 250V: 250kΩ...1GΩ, for UN = 500V: 500kΩ...2GΩ, for UN = 1000V: 1MΩ...3GΩ

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(5% v.m. + 3 digits)
200...1999 Ω1 Ω
Range *ResolutionAccuracy
0...1999kΩ1kΩ
2,00...19,99MΩ 20,0...199,9MΩ0,01MΩ 0,1MΩ±(3% v.m. + 8 digits)
200...999MΩ1MΩ
1,00...3,00GΩ0,01GΩ±(4% v.m. + 6 digits)
  • voltage range: 95...270V (for ZL-PE and ZL-N) and 95...440V (for ZL-L)
  • frequency: 45...65H

ZL-PE short circuit impedance measurement in RCD mode

* limited to the measurement range. With UNI-Schuko connection, additional error ±2%. .

Measured using a 15 mA current range of in accordance with IEC 61557: 0.50...1999.9 Ω

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω0,1 Ω 1 Ω±(6% v.m. + 5 digits)

Sequence of phases

  • indication of the sequence of phases: forward, backward, reverse
  • Supply voltage range UL-L: 100...440V (45...65Hz) ) UL-L: 100...440V (45...65Hz)
  • Phase-to-phase voltage display on the screen
  • Voltage range: 95...270V
  • frequency: 45...65Hz

Earth resistance measurement RE Voltage range according to IEC 61557-5: 0.5...1999Ω.

RangeResolutionAccuracy
0,00...9,99Ω0,01 Ω±(2% v.m. + 4 digits)
10,0...99,9Ω0,1 Ω
100...999Ω1 Ω±(2% v.m. + 3 digits)
1,00...1,99kΩ0,01kΩ

Measurement of active (P), reactive power (Q),apparent (S) and cosφ

  • ULN voltage range: 0...440V
  • Nominal mains frequency: 45...65Hz
  • Frequency measurement for voltages in the range 50...440V in the range 45.0...65.0Hz (max. accuracy ± 0.1% measured value +1 digit)
  • Cosφ measurement: 0.00...1.00 (resolution 0.01)

Low voltage and insulation continuity test

Test the PE cable using a current of ±200mA

RangeResolutionAccuracy
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(2% v.m. + 3 digits)
200...400 Ω1 Ω
  • Test current at R<2Ω: min. 200mA at rated voltage of nominal battery
  • Auto-calibration of test leads
  • Bi-directional measurement

Test of the differential protection trip and the tA response time (for tA mode)

Measuring ranges according to IEC 61557: 0ms ... to upper limit of the displayed value

Measurement of the current threshold of the differential protection for a unidirectional half-period sine waveform with a DC offset of 6mA

Rated currentRangeResolutionCurrent measurementBasic error
10 mA3,5...20,0mA0,1 mA0,35 x IDn ...2,0 x IDn
30 mA10,5...42,0mA
100 mA 300 mA35...140mA 105...420mA1 mA0,35 x IDn ...1,4 x IDn±10% IDn
500 mA175...700mA
  • The measurement of a positive or negative leakage current is possible.
Type de RCDSetting the multiplication factorMeasuring rangeResolutionBasic error
Ge- neral type0,5 IΔn 1 IΔn 2 IΔn0...300 ms 0...150 ms
5 IΔn0...40 ms±(2%
0,5 IΔn 1 IΔn0...500 ms1 msv.m. + 2 digits)
Sélec-1 IΔn
tivo2 IΔn0...200 ms
5 IΔn0...150 ms

Accuracy of differential current: for 0.5*I n: -8...0% for 1*I n, 2*I n, 5*I n: 0...8% for 1*I n, 2*I n, 5*I n: 0...8%.

Measurement of the current threshold of the protection differential (IA) for a test current continuous

Rated currentRangeResolutionCurrent measurementBasic error
10 mA2,0...20,0mA0,1 mA
30 mA6...60mA
100 mA20...200mA1 mA0,2 x IDn ...2,0 x IDn±10% IDn
300 mA60...600mA
500 mA100...1000mA
  • The measurement of a positive or negative leakage current is possible

Measurement of the current threshold of the protection differential (IA) for a test current

Corriente nominalRange de mediciónResolutionCorriente de mediciónBasic error
10 mA3,3...10,0mA
30 mA9,0...30,0mA0,1 mA
100 mA 300 mA 500 mA33...100mA 90...300mA 150...500mA1 mA0,3 x IDn...1,0 x IDn± 5% IDn
1000 mA330...1000mA

ANALYSIS OF SINGLE-PHASE NETWORK PARAMETERS

  • ULN voltage measurement: 0...500 V.
  • Test voltage frequency range: 45.0...65.0 Hz.
  • Voltage frequency measurement 50...500V Range 45.0...65.0 Hz (Basic error max. +- 0.1% v.m. ± 1 digit)
  • Measurement of cosφ: 0,00...1,00 (Resolution 0,01)
  • Measurement and recording in single-phase system
  • Measurement can be started from the positive or negative half of the leakage current.

THD (according to the first harmonic)

Current measurement (True RMS)

ResolutionBasic error
THD-F voltage (h = 2…40)0,0…999,9% for URMS ≥ 1% Unom0,1%±5%
THD-F ccu- rrent (h = 2...40)0,0…999,9% for IRMS ≥ 1% Inom0,1%±5%
PinçasRangeResolutionBasic error*
C-3, C-60,0...99,9 mA 100...999 mA0,1 mA 1 mA±(5% v.m. + 3 digits)
C-3,C-61,00...9,99 A 10,0...99,9 A0,01 A 0,1 A±(5% v.m. + 5 digits) (C-3, C-6)
100...999 A1 A±(0,1% In + 2 digits)
F-1, F-2, F-31,00...3,00 kA0,01 kA(F-1, F-2, F-3)

Low voltage measurement of continuity and resistance of circuits

* It is necessary to take into account the uncertainty of current clamps

Continuity measurement of the protective conductor with a current of ±200 mA

Measurement of the active power P, the passive power Q, apparent S and cosφ

RangeResolutionBasic error
0,00...19,99 Ω0,01 Ω
20,0...199,9 Ω0,1 Ω±(2% v.m. + 3 digits)
200...400 Ω1 Ω
Range [W], [VA], [var]Resolution [W], [VA], [var]Basic error
0...9991±(7% v.m. + 3
1,00...9,99 k0,01 kdigits)
10,0...99,9 k0,1 k
100...999 k1 k±(7% v.m. + 5 digits)
1,00...1,50 M0,01 M
  • Open terminal voltage: 4..9V
  • Output current at R<2Ω min. 200mA
  • Auto-calibration of test leads
  • Measurement of both current polarizations

Light intensity measurement

  • Voltage range: 0...500V
RangeResolutionBasic error
0,1...99,9 lx0,1 lx
100...999 lx 1,00...9,99 klx1 lx 0,01 klx±(5% v.m. + 2 digits)
10,0...19,9 klx0,1 klx
  • Current range: 0 ...1000 A
  • Nominal network frequency

Measurement of voltage harmonics

RangeResolutionpas de harmoniquesBasic error
0,0...500 V0,1 (1*) V1,2,...15 16,...40±(5% v.m. + 3 digits) ±(5% v.m. + 10 digits)
  • Measurement in lx or fc
  • m.v. means measured value
  • En outre, l’écran afÏche la valeur h02...h40 en pourcentage de h01 (jusqu’à 999%*) *) de 300V à 500V.

Mesure des harmoniques de courant

RangeResolutionpas de harmoniquesBasic error
selon le1,2,...15±(5% v.m. + 3 digits)
0,0...1000 A*Range de I16,...40±(5% v.m. + 10 digits)
  • In addition, the display shows the value h02...h40 as a percentage of h01 (up to 999%*) *) for the C-3 clamp for C-6 - 10 A, for F-series loops up to 3000A.
Electrical safety
Type of insulationdouble, according to EN 61010-1 and IEC 61557
Measurement categoryCAT IV 300 V according to EN 61010-1
Protection according to EN 60529IP54
Other technical data
Power supplyLR14 alkaline batteries (5 pieces) or a set of Ni-MH batteries (optional)
Environmental conditions
Operating temperature range(0...+50°C)
Image: Technician measuring illuminance with a lux meter probe connected to an orange Sonel instrument worn on a shoulder strap.

The MPI-530-IT provides automatic insulation resistance measurement of 3, 4 and 5-wire conductors with an additional AutoISO-1000C adapter.

AMPI-540 / 540-PV

Multifunctional meter for electrical installations

Image: Sonel MPI-540-PV multifunction tester with feature badges: CAT IV 300 V, CAT III 500 V, CAT II 1000 V DC, Li-ion battery, IT network testing, IP51, Bluetooth and Wi-Fi.
  • Largest 7-inch touch screen on the market - exceptional ergonomics and ease of use
  • Removable microSD card - for easy expansion of memory capacity
  • Fast transfer of measurements to the report - saves time

Features

  • Li-Ion battery - extended meter operation
  • MPI-540-PV: measurement of photovoltaic systems according to EN 62446
  • MPI-540-PV: PV system test report with Reports PLUS software
  • Three-phase power system parameter logger - basic power quality diagnosis
  • Reading of current data of network parameters - immediate evaluation of the device under study
  • Parameters measured in class S of EN 61000-4-30 - high measurement accuracy
  • Energy loss calculator - quick diagnosis of potential savings
  • Measurement of all lightning protection parameters - one instrument instead of several
  • Fast fault loop measurement with an uninterruptible RCD switch (up to several seconds) - time saving
  • Self-testing - possibility to perform automatic measurements in a sequence - simplification of measurements

The meter has above-average functionality. It combines the measurement capabilities of several devices, while ensuring equally good accuracy.

  • The MPI-540-PV can measure photovoltaic installations in accordance with EN 62446:
  • the continuity of the protective and equipotential connections,
  • resistance of the earth,
  • insulation resistance on the DC side,
  • open circuit voltage UOC,
  • short-circuit current ISC,
  • working currents and power in direct and alternating current,
  • the efÏciency of the inverter. .
  • The MPI-540 / MPI-540-PV can record 50/60 Hz power system parameters in class S of EN 61000-4-30:
  • voltages L1, L2, L3 - average values in the range up to 500 V,
  • L1, L2, L3 currents - average values, current measurement in the range up to 3 kA (depending on the current clamps used),
  • frequency in the range 40 Hz - 70 Hz,
  • active (P), reactive (Q), apparent (S) power,
  • power factor (PF), cosφ,
  • harmonics (up to 40 in voltage and current),
  • THD total harmonic distortion for current and voltage.
  • The MPI-540 / MPI-540-PV can be used for all commissioning measurements of electrical installations in accordance with the relevant regulations:
  • impedance of the fault loop (also in circuits with RCDs),
  • the parameters of the RCDs,
  • insulation resistance,
  • grounding resistance (4 measurement methods + soil resistivity measurement),
  • the continuity of the protection and equipotential connections,
  • measurement of illumination,
  • phase sequence test,
  • testing the direction of rotation of a motor

Automatic safety test of the installation

MPI-540 / MPI-540-PV are used for safety monitoring of residential electrical installations, commercial and industrial applications. Measurements can be easily automated with:

Image: Sonel MPI-540 installation tester with touch screen operated with a stylus, connected by a coiled lead to a wall socket.
Image: Technician wearing a Sonel helmet and insulating gloves tests an electric motor with a Sonel meter connected by coloured leads.
Image: Rows of solar photovoltaic panels on a building rooftop under a blue sky.
Image: Gloved operator connecting the voltage leads and clamps of the MPI-540 analyser in an electrical cabinet; the screen shows a harmonics bar chart.
  • teste automático de dispositivos de corrente residual (RCD),
  • medições automáticas: sequências de medição livremente configurável,
  • Adaptador AutoISO-1000C para teste automático da resistência de isolamento de cabos 3, 4 e 5 condutores sem comutação

Photovoltaics under scrutiny

The MPI-540-PV is an extremely universal meter, designed in particular for testing photovoltaic installations. The device allows a complete set of tests on the DC and AC side, according to the guidelines of EN 62446.

When measuring PV system parameters, the instrument automatically converts them to STC (standard test conditions). Measurements of voltage, current and power on the AC and DC side of the inverter are used to verify its efÏciency. The Reports PLUS software allows you to create a PV system test report with the measurement results stored in the memory. .

Three-phase network parameter recorder

The instrument has a three-phase power supply parameter recorder with a current parameter reading mode and the possibility to record power system parameters, such as voltage, current, power, harmonics, THD. The meter can read the selected parameters and display them graphically on the screen in real time. These parameters are measured independently of the recording stored on the memory card. In LIVE mode, the user can view:

  • voltage and current versus time diagrams,
  • phasing diagram,
  • measurements of many parameters in tabular form,
  • current and voltage harmonic diagram.
Image: Instrument screen showing the RCD tA connection scheme for UL and RE measurement, with the meter connected to L1, L2, L3, N and PE of a three-phase installation.
Image: Technician in a hard hat using a measuring instrument in a tunnel under construction.

Easy to read

The device is equipped with a 7” TFT LCD colour touch screen with a diagonal of 800x480 pixels, which allows for convenient operation and easy reading of the settings and plotted routes. This screen size allows for more information to be displayed, available at any time of use. The interface is visible in all conditions, thanks to the appropriate size of the symbols displayed. The included stylus allows you to work with dielectric gloves.

Integrated help system

Help screens with measurement diagrams are built into the unit. This allows you to quickly and easily check how to connect a particular circuit depending on the type of measurement being made.

Increased resistance to environmental conditions

The MPI-540 /MPI-540-PV works perfectly in harsh environmental conditions. Protection against dust and water ingress is provided by the IP51 waterproof housing. It is resistant to mechanical damage and its special design allows the touch screen to be easily protected by sliding the meter cover. In addition to protection against damage, it also allows the device to be easily transported and used in different positions. .

Communication and software

One of the great strengths of the instrument is the large number of communication interfaces and the compatibility with external software. Via the USB port, removable SD memory card or wireless communication (Bluetooth*, Wi-Fi), measurement data can be sent to a computer.

Image: Orange Sonel multifunction meter connected by USB cable to a laptop whose software displays a bar chart of measurement results.

In order to generate a measurement report in the field of lightning protection, it is necessary to use the Reports PLUS program.

Reader allows us to save the downloaded data in the simplest formats and to print them out. For reading and analysing the data from the recorder, we use the specific program Analysis. .