Multifunctional meter for electrical installations
Image: Sonel MPI-502 installation tester in orange housing, display showing 228.4 V and an L-N loop impedance of 0.73 Ω, with START and ESC keys and a rotary function selector.
MODELS 502, 506, 520, 525, 530-IT, 540 & 540-PV
AMPI-502
Multifunctional meter for electrical installations
Image: Sonel MPI-502 meter with orange housing; the display shows 228.4 V and 0.73 Ω. Badges: CAT III 600 V, CAT IV 300 V, Bluetooth and IP67.
Features
Measuring the short circuit loop
Type AC and A earth leakage protection test
Low voltage measurement of continuity and resistance of circuits
Management of measurement data using open
Measured parameters
- Measuring the short circuit loop
Measurement of the short-circuit impedance in 220/380 V, 230/400 V, 240/415 V networks and at a frequency of 45...65 Hz, - working voltage range: 180 ... 460 V
Indication of the short-circuit loop resistance R and the short-circuit loop reactance X
Measuring the short circuit impedance with a 15 mA current without differential tripping
Maximum measuring current: 7.6 A (at 230 V), 13.3 A (at 400 V)
- Testing of AC and A-type earth leakage protection
Testing of general and selective differential protections for differential currents of 10, 30, 100, 300, 500 mA.
Measurement of IA and triggering time tA for the currents 0.5IΔn, 1IΔn, 2IΔn, 5IΔn
ER e and UB measurement without differential tripping
Extended AUTO function with RCD measurement, with the possibility of measuring ZL-PE with a small current
IA and tA measurement with RCD triggering
Low voltage measurement of continuity and resistance of circuits s
Resistance measurement with a current of ±200 mA according to IEC 61557-4
Autocalibration of test leads - any length of test probe can be used
Low-current resistance measurement with an acoustic signal
Technical specifications
Measurement of short-circuit loop impedance ZL-PE, ZL-N, ZL-L
Measurement using according to IEC 615
the 7.6/13.3 A cu 557-3: 0.13...1999
urrent range - from of 9 Ω
Range
Resolution
Basic error
0,00...19,99 Ω
0,01 Ω
20,0...199,9 Ω
0,1 Ω
±(5% v.m. + 3 digits)
200...1999 Ω
1 Ω
ZL-PE short circuit impedance measurement in RCD mode
Measured using a 15 mA current range of in accordance with IEC 61557: 0.50...1999 Ω
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω
0,1 Ω 1 Ω
±(6% v.m. + 5 digits)
Image: Orange handheld meter held in the hand, with digital display, keypad and coiled lead; its carrying bag behind.Image: Hand holding an orange Sonel meter showing a reading of 557 during a measurement on an industrial installation.Image: Orange hand-held Sonel meter with a plug adapter inserted in a socket outlet in a distribution board, showing a reading on screen.
MEASUREMENTS OF RCD CIRCUIT BREAKER PARAMETERS (VOLTAGE RANGE 180...270 V)
RCD trip test and time measurement according to IEC 61557-3: 0.13....1999 Ω of triggering tA (for the tA function)
Switch type
Setting the multiplication factor
Measuring range
Resolution
Basic error
General type
0,5 IΔn 1 IΔn
0...300 ms
type
2 IΔn
0...150 ms
5 IΔn
0...40 ms
1 ms
±(2% v.m. + 2
Selective
0,5 IΔn 1 IΔn 2 IΔn
0...500 ms 0...200 ms
1 ms
v.m. + 2 digits)
5 IΔn
0...150 ms
Measurement of the IA differential cut-off current for the sinusoidal waveform test current
Current selected
Measuring range
Resolution
Test current
Basic error
10 mA
3,0...10,0 mA
30 mA
9,0...30,0 mA
0,1 mA
0,3 IΔn...1,0
±5% IΔn
100 mA
30...100 mA
IΔn...1,0 IΔn
±5% IΔn
300 mA
90...300 mA
1 mA
500 mA
150...500 mA
The start of the measurement of the positive or negative half-periods of the generated current.
IA trip current measurement for unidirectional pulsed residual current
Current selected
Measuring range
Resolution
Test current
Basic error
10 mA
4,0...20,0 mA
0,1 mA
0,35 IΔn ...2,0 IΔn
30 mA 100 mA 300 mA
12,0...42,0 mA 40...140 mA 120...420 mA
1 mA
0,35 IΔn ...1,4 IΔn
±10% IΔn
Measurement of positive or negative half-periods of the generated leakage current
Electrical safety
Insulation type according to PN-EN 61010-1 and IEC 61557
double
Measurement category according to PN-EN 61010-1
IV 300V
Degree of protection of the housing according to PN-EN 60529
IP67
Other technical data
Dimensions
220 x 98 x 58 mm
Weight
approx. 1 kg
Automatic shutdown time
300, 600, 900 seconds
Number of Z and differential measurements (for Ni-Cadmium batteries)
>5000 (2 per minute)
The equipment meets the requirements of the standard
EN 61326-1 EN 61326-2-2
AMPI-506
Multifunctional meter for electrical installations
Image: Sonel MPI-502 meter with orange housing; the display shows 228.4 V and 0.73 Ω. Badges: CAT III 600 V, CAT IV 300 V, Bluetooth and IP67.
Measured parameters
- Measuring the short circuit loop
Measurement of short circuit impedance in 220/380 V, 230/400 V, 240/415 V networks and at a frequency of 45...65 Hz - Operating voltage range: 180 ... 460 V
Indication of the short-circuit loop resistance R and the short-circuit loop reactance X
Measuring the short circuit impedance with a 15 mA current without differential tripping
Maximum measuring current: 7.6 A (at 230 V), 13.3 A (at 400 V)
- Type AC and A earth leakage protection test
Testing of general and selective differential protections for differential currents of 10, 15, 30, 100, 300, 500 mA.
Measurement of IA and triggering time tA for the currents 0.5 IΔn, 1 IΔn, 2 IΔn, 5 IΔn
- Low voltage measurement of continuity and resistance of circuits
Resistance measurement with a current of ±200 mA according to IEC 61557-4
Autocalibration of test leads - any length of test probe can be used
Low-current resistance measurement with an acoustic signal
- Indications of the phase sequence
ER and UB measurement without differential tripping
Extended AUTO function with RCD measurement, with the possibility of measuring ZL-PE with a small current
IA and tA measurement with RCD triggering
Additional functions
Check the correctness of the PE conductor connection using the contact electrode.
Measurement of mains voltage (0...500 V) and frequency
- Insulation resistance measurements
Measuring voltages: 100 V, 250 V, 500 V
990 result memory, wireless data transmission data to the PC
Illuminated keyboard
Technical specifications
Measurement of short-circuit loop impedance
ZL-PE, ZL-N, ZL-L
Measurement using the 7.6/13.3 A current range - from of according to IEC 61557-3: 0.13...1999 Ω
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
20,0...199,9 Ω
0,1 Ω
±(5% v.m. + 3 digits)
200...1999 Ω
1 Ω
ZL-PE short circuit impedance measurement in RCD mode
Measured using a 15 mA current range of In accordance with IEC 61557: 0.50...1999 Ω
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω
0,1 Ω 1 Ω
±(6% v.m. + 5 digits)
Insulation resistance measurement
MEASUREMENT OF RCD CIRCUIT BREAKER PARAMETERS (VOLTAGE RANGE 180...270 V)
Disconnection test of the RCDs and measurement of the tripping time tA (for the tA measurement function)
Type of RCD
Setting the multiplication factor
Masuring range
Resolution
Basic error
General type
0,5 IΔn 1 IΔn
0...300 ms
type
2 IΔn
0...150 ms
5 IΔn
0...40 ms
1 ms
±(2% v.m. + 2
Selective
0,5 IΔn 1 IΔn
0...500 ms
1 ms
+ 2 digits)
Selective
2 IΔn
0...200 ms
5 IΔn
0...150 ms
Measurement of the trigger current of the RCD IA for pulsed differential current unidirectional
Measuring range according to IEC 61557-2
UISO = 100 V: 100 kΩ...99,9 MΩ
UISO = 250 V: 250 kΩ...199,9 MΩ
UISO = 500 V: 500 kΩ...599,9 MΩ
Image: Insulation resistance tables for Uiso = 100 V and 250 V: 0–1999 kΩ at 1 kΩ resolution, 2.00–19.99 MΩ at 0.01 MΩ and up to 99.9 or 199.9 MΩ at 0.1 MΩ, accuracy ±(5% m.v. + 8 digits); start of the 500 V table.Image: Insulation resistance table for Uiso = 500 V: ranges 0–1999 kΩ, 2.00–19.99 MΩ and 20.0–599.9 MΩ, resolutions 1 kΩ, 0.01 MΩ and 0.1 MΩ, accuracy ±(5% m.v. + 8 digits).
Rated current
Measuring range
Resolution
Current measurement
Basic error
10 mA
3,0...10,0 mA
15 mA
4,5...15,0 mA
0,1 mA
30 mA 100 mA
9,0...30,0 mA 30...100 mA
0,3 IΔn...1,0 IΔn
±5% IΔn
300 mA
90...300 mA
1 mA
300 mA
150...500 mA
Start of measurement from the positive or negative half-period of the forced current
Indications of the phase sequence
Indication of phase sequence: conforming, non-conforming
Mains voltage range: 100...440 V
Display of phase-to-phase voltage values
“v.m” - valor medido
Safety and working conditions
Measurement category according to EN 61010
IV 300 V (III 600 V)
Income protection
IP67
Insulation type according to EN 61010-1 and IEC 61557
double
Dimensions
220 x 98 x 58 mm
Weight
aprox. 0,8 kg
Memory and communication
Memory of measured results
990
Data transmission
Bluetooth
Other information
Memory of measured results
EN 61326-1
Data transmission
EN 61326-2-2
AMPI-520
Multifunctional meter for electrical installations
The MPI-520 multifunction meter is dedicated to performing diagnostics according to IEC 61557.
Features
The AMPI-520 digital meter is designed to measure impedance in short circuit loops without tripping the differential protection, it also measures RCD parameters, grounding resistance, continuity and phase sequence control.
In addition, it measures voltage, current, frequency and AC power.
Measured parameters
- Measuring the short circuit loop
impedance measurement with 23 A (44 A phase to phase), short circuit resistance R =10Ω, zw
Measuring range: 95...440V, frequency 45...65 Hz,
Short circuit loop measurement with a resolution of 0.01 Ω, without triggering the ground leakage protection (I Δn ≥30mA).
Automatic short circuit calculation, phase-to-neutral and phase-to-phase voltage detection,
UNI-Schuko connector for automatic measurement, AGT adapter for measurements on three-phase networks.
Image: Sonel earth resistance meter with orange casing surrounded by its accessories: test leads, cable reels, earth spikes, clamps and crocodile clips.
- Insulation resistance measurement
with application of the test voltages: 250 V, 500 V, 1000 V,
average range up to 3GΩ,
UNI-Schuko connector for insulation measurement,
automatic discharge after measurement,
Automatic measurement of all resistances in 3, 4 or 5 wire cables using the optional AUTO-ISO adapter,
acoustic signals at 5 s intervals to obtain the insulation characteristic curve,
safety surge protection.
- Measuring the resistance of the earth
- Bi-directional continuity test on PE cables using 200 mA.
uto-calibration of test leads.
Checking the sequence of phases.
Battery charge indication.
Automatic shut-off function.
- USB interface.
Testing of differential, general and selective protections for 10, 30, 100, 300, 500 and 1000 mA differential current.
Testing of differential, general and selective protection for differential currents of 10, 30, 100, 300, 500 and 1000 mA also in IT isolated systems.
- Measurement of insulation resistance:
with application of the test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V,
Quick check of the correct connection of the PE terminals by means of the contact electrode.
Measures and records voltage, frequency, AC current, cosφ, power (active, reactive and apparent), voltage harmonics and THD calculated up to 40 harmonics.
medium range up to 10 GΩ
- Verification of the phase sequence and the motor rotation
- Bi-directional continuity test on PE cables using 200 mA.
Auto-calibration of test leads.
Dynamically managed, tree-like memory structure (max. 10,000 results of each type of measurement) with the possibility of describing measurement points, objects, client names.
Checking the sequence of phases.
Battery charge indication.
Battery powered, integrated drainer. Possibility to charge the equipment on the mains or on the car cigarette lighter (12V).
Automatic shut-off function.
- USB interface. .
Technical specifications
Measurement of short-circuit loop impedance ZL-PE, ZL-N, ZL-L
Insulation resistance measurement
Measuring range according to IEC 61557-2
Measurement using 23/40 A current Range according to IEC 61557: 0.13...1999.9Ω (for 1.2 m cables):
for UN = 50V: 50kΩ...250MΩ; for UN = 100V: 100kΩ...500MΩ; for UN = 250V: 250kΩ...1GΩ, for UN = 500V: 500kΩ...2GΩ, for UN = 1000V: 1MΩ...3GΩ
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
20,0...199,9 Ω
0,1 Ω
±(5% v.m. + 3 digits)
200...1999 Ω
1 Ω
Range *
Resolution
Accuracy
0...1999kΩ
1kΩ
2,00...19,99MΩ 20,0...199,9MΩ
0,01MΩ 0,1MΩ
±(3% v.m. + 8 digits)
200...999MΩ
1MΩ
1,00...3,00GΩ
0,01GΩ
±(4% v.m. + 6 digits)
voltage range: 95...270V (for ZL-PE and ZL-N) and 95...440V (for ZL-L)
frequency: 45...65H
ZL-PE short circuit impedance measurement in RCD mode
* limited to the measurement range. With UNI-Schuko connection, additional error ±2%. .
Measured using a 15 mA current range of in accordance with IEC 61557: 0.50...1999.9 Ω
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
±(6% v.m. + 10 digits)
20,0...199,9 Ω 200...1999 Ω
0,1 Ω 1 Ω
±(6% v.m. + 5 digits)
Sequence of phases
indication of the sequence of phases: forward, backward, reverse
Supply voltage range UL-L: 100...440V (45...65Hz) ) UL-L: 100...440V (45...65Hz)
Phase-to-phase voltage display on the screen
Voltage range: 95...270V
frequency: 45...65Hz
Earth resistance measurement RE Voltage range according to IEC 61557-5: 0.5...1999Ω.
Range
Resolution
Accuracy
0,00...9,99Ω
0,01 Ω
±(2% v.m. + 4 digits)
10,0...99,9Ω
0,1 Ω
100...999Ω
1 Ω
±(2% v.m. + 3 digits)
1,00...1,99kΩ
0,01kΩ
Measurement of active (P), reactive power (Q),apparent (S) and cosφ
ULN voltage range: 0...440V
Nominal mains frequency: 45...65Hz
Frequency measurement for voltages in the range 50...440V in the range 45.0...65.0Hz (max. accuracy ± 0.1% measured value +1 digit)
Cosφ measurement: 0.00...1.00 (resolution 0.01)
Low voltage and insulation continuity test
Test the PE cable using a current of ±200mA
Range
Resolution
Accuracy
0,00...19,99 Ω
0,01 Ω
20,0...199,9 Ω
0,1 Ω
±(2% v.m. + 3 digits)
200...400 Ω
1 Ω
Test current at R<2Ω: min. 200mA at rated voltage of nominal battery
Auto-calibration of test leads
Bi-directional measurement
Test of the differential protection trip and the tA response time (for tA mode)
Measuring ranges according to IEC 61557: 0ms ... to upper limit of the displayed value
Measurement of the current threshold of the differential protection for a unidirectional half-period sine waveform with a DC offset of 6mA
Rated current
Range
Resolution
Current measurement
Basic error
10 mA
3,5...20,0mA
0,1 mA
0,35 x IDn ...2,0 x IDn
30 mA
10,5...42,0mA
100 mA 300 mA
35...140mA 105...420mA
1 mA
0,35 x IDn ...1,4 x IDn
±10% IDn
500 mA
175...700mA
The measurement of a positive or negative leakage current is possible.
Type de RCD
Setting the multiplication factor
Measuring range
Resolution
Basic error
Ge- neral type
0,5 IΔn 1 IΔn 2 IΔn
0...300 ms 0...150 ms
5 IΔn
0...40 ms
±(2%
0,5 IΔn 1 IΔn
0...500 ms
1 ms
v.m. + 2 digits)
Sélec-
1 IΔn
tivo
2 IΔn
0...200 ms
5 IΔn
0...150 ms
Accuracy of differential current: for 0.5*I n: -8...0% for 1*I n, 2*I n, 5*I n: 0...8% for 1*I n, 2*I n, 5*I n: 0...8%.
Measurement of the current threshold of the protection differential (IA) for a test current continuous
Rated current
Range
Resolution
Current measurement
Basic error
10 mA
2,0...20,0mA
0,1 mA
30 mA
6...60mA
100 mA
20...200mA
1 mA
0,2 x IDn ...2,0 x IDn
±10% IDn
300 mA
60...600mA
500 mA
100...1000mA
The measurement of a positive or negative leakage current is possible
Measurement of the current threshold of the protection differential (IA) for a test current
Corriente nominal
Range de medición
Resolution
Corriente de medición
Basic error
10 mA
3,3...10,0mA
30 mA
9,0...30,0mA
0,1 mA
100 mA 300 mA 500 mA
33...100mA 90...300mA 150...500mA
1 mA
0,3 x IDn...1,0 x IDn
± 5% IDn
1000 mA
330...1000mA
ANALYSIS OF SINGLE-PHASE NETWORK PARAMETERS
ULN voltage measurement: 0...500 V.
Test voltage frequency range: 45.0...65.0 Hz.
Voltage frequency measurement 50...500V Range 45.0...65.0 Hz (Basic error max. +- 0.1% v.m. ± 1 digit)
Measurement of cosφ: 0,00...1,00 (Resolution 0,01)
Measurement and recording in single-phase system
Measurement can be started from the positive or negative half of the leakage current.
THD (according to the first harmonic)
Current measurement (True RMS)
Resolution
Basic error
THD-F voltage (h = 2…40)
0,0…999,9% for URMS ≥ 1% Unom
0,1%
±5%
THD-F ccu- rrent (h = 2...40)
0,0…999,9% for IRMS ≥ 1% Inom
0,1%
±5%
Pinças
Range
Resolution
Basic error*
C-3, C-6
0,0...99,9 mA 100...999 mA
0,1 mA 1 mA
±(5% v.m. + 3 digits)
C-3,C-6
1,00...9,99 A 10,0...99,9 A
0,01 A 0,1 A
±(5% v.m. + 5 digits) (C-3, C-6)
100...999 A
1 A
±(0,1% In + 2 digits)
F-1, F-2, F-3
1,00...3,00 kA
0,01 kA
(F-1, F-2, F-3)
Low voltage measurement of continuity and resistance of circuits
* It is necessary to take into account the uncertainty of current clamps
Continuity measurement of the protective conductor with a current of ±200 mA
Measurement of the active power P, the passive power Q, apparent S and cosφ
Range
Resolution
Basic error
0,00...19,99 Ω
0,01 Ω
20,0...199,9 Ω
0,1 Ω
±(2% v.m. + 3 digits)
200...400 Ω
1 Ω
Range [W], [VA], [var]
Resolution [W], [VA], [var]
Basic error
0...999
1
±(7% v.m. + 3
1,00...9,99 k
0,01 k
digits)
10,0...99,9 k
0,1 k
100...999 k
1 k
±(7% v.m. + 5 digits)
1,00...1,50 M
0,01 M
Open terminal voltage: 4..9V
Output current at R<2Ω min. 200mA
Auto-calibration of test leads
Measurement of both current polarizations
Light intensity measurement
Voltage range: 0...500V
Range
Resolution
Basic error
0,1...99,9 lx
0,1 lx
100...999 lx 1,00...9,99 klx
1 lx 0,01 klx
±(5% v.m. + 2 digits)
10,0...19,9 klx
0,1 klx
Current range: 0 ...1000 A
Nominal network frequency
Measurement of voltage harmonics
Range
Resolution
pas de harmoniques
Basic error
0,0...500 V
0,1 (1*) V
1,2,...15 16,...40
±(5% v.m. + 3 digits) ±(5% v.m. + 10 digits)
Measurement in lx or fc
m.v. means measured value
En outre, l’écran afÏche la valeur h02...h40 en pourcentage de h01 (jusqu’à 999%*) *) de 300V à 500V.
Mesure des harmoniques de courant
Range
Resolution
pas de harmoniques
Basic error
selon le
1,2,...15
±(5% v.m. + 3 digits)
0,0...1000 A*
Range de I
16,...40
±(5% v.m. + 10 digits)
In addition, the display shows the value h02...h40 as a percentage of h01 (up to 999%*) *) for the C-3 clamp for C-6 - 10 A, for F-series loops up to 3000A.
Electrical safety
Type of insulation
double, according to EN 61010-1 and IEC 61557
Measurement category
CAT IV 300 V according to EN 61010-1
Protection according to EN 60529
IP54
Other technical data
Power supply
LR14 alkaline batteries (5 pieces) or a set of Ni-MH batteries (optional)
Environmental conditions
Operating temperature range
(0...+50°C)
Image: Technician measuring illuminance with a lux meter probe connected to an orange Sonel instrument worn on a shoulder strap.
The MPI-530-IT provides automatic insulation resistance measurement of 3, 4 and 5-wire conductors with an additional AutoISO-1000C adapter.
AMPI-540 / 540-PV
Multifunctional meter for electrical installations
Image: Sonel MPI-540-PV multifunction tester with feature badges: CAT IV 300 V, CAT III 500 V, CAT II 1000 V DC, Li-ion battery, IT network testing, IP51, Bluetooth and Wi-Fi.
Largest 7-inch touch screen on the market - exceptional ergonomics and ease of use
Removable microSD card - for easy expansion of memory capacity
Fast transfer of measurements to the report - saves time
Features
Li-Ion battery - extended meter operation
MPI-540-PV: measurement of photovoltaic systems according to EN 62446
MPI-540-PV: PV system test report with Reports PLUS software
Three-phase power system parameter logger - basic power quality diagnosis
Reading of current data of network parameters - immediate evaluation of the device under study
Parameters measured in class S of EN 61000-4-30 - high measurement accuracy
Energy loss calculator - quick diagnosis of potential savings
Measurement of all lightning protection parameters - one instrument instead of several
Fast fault loop measurement with an uninterruptible RCD switch (up to several seconds) - time saving
Self-testing - possibility to perform automatic measurements in a sequence - simplification of measurements
The meter has above-average functionality. It combines the measurement capabilities of several devices, while ensuring equally good accuracy.
The MPI-540-PV can measure photovoltaic installations in accordance with EN 62446:
the continuity of the protective and equipotential connections,
resistance of the earth,
insulation resistance on the DC side,
open circuit voltage UOC,
short-circuit current ISC,
working currents and power in direct and alternating current,
the efÏciency of the inverter. .
The MPI-540 / MPI-540-PV can record 50/60 Hz power system parameters in class S of EN 61000-4-30:
voltages L1, L2, L3 - average values in the range up to 500 V,
L1, L2, L3 currents - average values, current measurement in the range up to 3 kA (depending on the current clamps used),
the continuity of the protection and equipotential connections,
measurement of illumination,
phase sequence test,
testing the direction of rotation of a motor
Automatic safety test of the installation
MPI-540 / MPI-540-PV are used for safety monitoring of residential electrical installations, commercial and industrial applications. Measurements can be easily automated with:
Image: Sonel MPI-540 installation tester with touch screen operated with a stylus, connected by a coiled lead to a wall socket.Image: Technician wearing a Sonel helmet and insulating gloves tests an electric motor with a Sonel meter connected by coloured leads.Image: Rows of solar photovoltaic panels on a building rooftop under a blue sky.Image: Gloved operator connecting the voltage leads and clamps of the MPI-540 analyser in an electrical cabinet; the screen shows a harmonics bar chart.
teste automático de dispositivos de corrente residual (RCD),
medições automáticas: sequências de medição livremente configurável,
Adaptador AutoISO-1000C para teste automático da resistência de isolamento de cabos 3, 4 e 5 condutores sem comutação
Photovoltaics under scrutiny
The MPI-540-PV is an extremely universal meter, designed in particular for testing photovoltaic installations. The device allows a complete set of tests on the DC and AC side, according to the guidelines of EN 62446.
When measuring PV system parameters, the instrument automatically converts them to STC (standard test conditions). Measurements of voltage, current and power on the AC and DC side of the inverter are used to verify its efÏciency. The Reports PLUS software allows you to create a PV system test report with the measurement results stored in the memory. .
Three-phase network parameter recorder
The instrument has a three-phase power supply parameter recorder with a current parameter reading mode and the possibility to record power system parameters, such as voltage, current, power, harmonics, THD. The meter can read the selected parameters and display them graphically on the screen in real time. These parameters are measured independently of the recording stored on the memory card. In LIVE mode, the user can view:
voltage and current versus time diagrams,
phasing diagram,
measurements of many parameters in tabular form,
current and voltage harmonic diagram.
Image: Instrument screen showing the RCD tA connection scheme for UL and RE measurement, with the meter connected to L1, L2, L3, N and PE of a three-phase installation.Image: Technician in a hard hat using a measuring instrument in a tunnel under construction.
Easy to read
The device is equipped with a 7” TFT LCD colour touch screen with a diagonal of 800x480 pixels, which allows for convenient operation and easy reading of the settings and plotted routes. This screen size allows for more information to be displayed, available at any time of use. The interface is visible in all conditions, thanks to the appropriate size of the symbols displayed. The included stylus allows you to work with dielectric gloves.
Integrated help system
Help screens with measurement diagrams are built into the unit. This allows you to quickly and easily check how to connect a particular circuit depending on the type of measurement being made.
Increased resistance to environmental conditions
The MPI-540 /MPI-540-PV works perfectly in harsh environmental conditions. Protection against dust and water ingress is provided by the IP51 waterproof housing. It is resistant to mechanical damage and its special design allows the touch screen to be easily protected by sliding the meter cover. In addition to protection against damage, it also allows the device to be easily transported and used in different positions. .
Communication and software
One of the great strengths of the instrument is the large number of communication interfaces and the compatibility with external software. Via the USB port, removable SD memory card or wireless communication (Bluetooth*, Wi-Fi), measurement data can be sent to a computer.
Image: Orange Sonel multifunction meter connected by USB cable to a laptop whose software displays a bar chart of measurement results.
In order to generate a measurement report in the field of lightning protection, it is necessary to use the Reports PLUS program.
Reader allows us to save the downloaded data in the simplest formats and to print them out. For reading and analysing the data from the recorder, we use the specific program Analysis. .
* The function will be available after the software has been updated (at no extra cost).