AMPERIS AMZC-305 Loop Impedance Meter

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 6 pages · 214 KB) · Source page: AMZC-305: loop impedance meter

Loop measurements in networks from 100 to 750 V with up to 30 A

AMZC-305

Ohmmeters and loop impedance meters

Image: Multifunction installation tester with grey and orange housing, built-in grip, display reading 0.67 Ω, keys and rotary selector.

AMZC-305

Loop impedance meter up to 400/690 V

C/ María Barbeito, 14Contact Contact T [+34] 982 20 99 20
27003, Lugo, SpainT [+34] 982 20 99 20 info@amperis.com | www.amperis.com

Loop impedance in eight rated networks — up to 400/690 V — with high-current measurement and USB.

Image: Loop measurement at a 690 V industrial socket with the AMZC-305

From the workshop to heavy industry

The AMZC-305 measures short-circuit loop impedance with 0.01 Ω resolution in networks of 110/190, 115/200, 127/220, 220/380, 230/400, 240/415, 290/500 and 400/690 V — a 100 to 750 V working range. The high-current measurement of up to 30 A yields 0.13 to 1999 Ω per IEC 61557, with the R and X components and the calculated short-circuit current.

Every circuit, also behind RCDs

The ZL-PE RCD mode measures from 0.43 Ω without tripping RCDs above 30 mA in 100…440 V networks; the device distinguishes phase from line voltage automatically, verifies the PE terminal with its contact electrode and measures with L and N swapped. The voltmeter reads up to 750 V — with 0.1 V resolution to 250 V — in every loop function, with an overvoltage alarm.

Main features

  • Memory of 990 cells (3500 records) with USB interface.
  • Test leads of 1.2, 5, 10 and 20 m or UNI-Schuko adapter.
  • Short-circuit current calculated for the rated voltage.
  • Operating frequency range 45…65 Hz.
  • Powered by four AA batteries: over 3000 measurements.
  • Auto-off after 120 seconds of inactivity.

Applications and delivery

Applications

  • Industrial networks of 290/500 and 400/690 V.
  • Short-circuit protection verification in LV installations.
  • Socket-outlet testing with the UNI-Schuko adapter.
  • RCD-protected boards measured without interruptions.

Rugged and complete

With double insulation per IEC 61010-1, CAT IV 600 V (CAT III 1000 V) and an IP54 housing of 260 × 190 × 60 mm and 2.2 kg, the AMZC-305 is delivered with three 1.2 m leads, probes and crocodile clips, USB cable, batteries, straps, case and calibration certificate; leads up to 20 m and socket adapters are optional.

990 memory cells and a USB port put every loop measurement on the computer.

Software & applications

Measurements that travel by USB

The documentation software manages reports, inspectors, test points and downloaded data

The AMZC-305 keeps 3500 records in its 990 memory cells and downloads them to the PC through the USB port. The free reader software receives loop impedances with their R and X components, calculated fault currents and voltages, organised by installation.

One archive for all networks

Whether the readings come from a 230/400 V office or from a 690 V plant, the software identifies each result by point and date, compares periodic verifications and exports or prints the documentation.

What the software provides

  • USB download of the 990 cells (3500 records).
  • Archive by clients, sites and measuring points.

Preview of a verification report of the installation, ready to print or export

  • Export to popular formats and printing.
  • History of verifications of each installation.

AMZC-305 — MEASUREMENT DATA

Fault loop impedance ZL-PE, ZL-N, ZL-L

Display rangeResolutionAccuracy
0.00…19.99 Ω0.01 Ω±(5% m.v. + 3 digits)
20.0…199.9 Ω0.1 Ω±(4% m.v. + 3 digits)
200…1999 Ω1 Ω±(4% m.v. + 3 digits)

Range per IEC 61557: 0.13…1999 Ω (1.2 m leads); 0.25…1999 Ω (UNI-Schuko adapter). Networks 110/190…400/690 V; loop voltage range 100…440 V (ZL-PE, ZL-N) and 100…750 V (ZL-L); high-current measurement up to 30 A; R and X components; Ik calculation; 45…65 Hz.

Loop impedance ZL-PE RCD (no tripping)

Display rangeResolutionAccuracy
0.00…19.99 Ω0.01 Ω±(6% m.v. + 10 digits)
20.0…199.9 Ω0.1 Ω±(6% m.v. + 5 digits)
200…1999 Ω1 Ω±(6% m.v. + 5 digits)

Range per IEC 61557: 0.43…1999 Ω (1.2 m leads); 0.50…1999 Ω (UNI-Schuko). Operating range 100…440 V; no tripping of RCDs >30 mA; contact electrode for PE checking; measurement with L-N swapped.

Voltage measurement

RangeResolutionAccuracy
0…249.9 V0.1 V±(2% m.v. + 4 digits)
250…750 V1 V±(2% m.v. + 2 digits)

Available in every loop function; 45…65 Hz; overvoltage alarm.

"m.v." = measured value

AMZC-305 — TECHNICAL SPECIFICATIONS

Type of insulationDouble, per EN 61010-1
Measurement categoryCAT IV 600 V (CAT III 1000 V)
Ingress protectionIP54, per EN 60529
Power supply4 × AA alkaline batteries or NiMH accumulators
Battery performance>3000 Z measurements (alkaline batteries)
Auto-offAfter 120 seconds
Memory of results990 cells, 3500 records
Data transmissionUSB
DisplaySegment LCD, LED backlight
Operating temperature0…+45 °C
Storage temperature-20…+60 °C
Humidity20…80 %
Dimensions260 × 190 × 60 mm
Weightapprox. 2.2 kg
StandardsIEC 61557, EN 61010-1

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote