High Current Short Circuit Loop Impedance Meter AMZC-310S

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 3 pages · 283 KB) · Source page: Hochstrom-Schleifenimpedanzmessgerät AMZC-310S

High Current Loop Impedance Meter

HIGHEST ACCURACY & LOWEST COST

Image: Sonel insulation resistance meter with the lid open showing connection diagrams, LCD display, rotary selector and coloured terminals.

AMZC-310S

Resolution 0,1mΩ.

High current measurement. Unique available meter is also able to measure touch voltage and touch shock voltage.

Memory of 999 measurement.

AMPERIS PRODUCTS S.Lagricultura, 34, Contact 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, Spain info@amperis.com | www.amperis.com

The most important features of AMZC-310S are:

Measurement of very low short circuit loop impedances (with resolution 0,1mΩ) with a current of 150A at 230V; maximum 280A at 440V or measurement with a current of 23A at 230V; maximum 42A at 440V:

  • Measurements in installations with rated voltages between: 220/380V and 230/400V and frequencies 45...65Hz.
  • Ability to perform measurements in short circuit system: phase-phase, phase-protective, phase-neutral.
  • Differentiation between the phase voltage and the inter-phase voltage while calculating the shortcircuit current.
  • Ability to change the length of test leads (measurement 23/42A).
  • Four-pole method, test leads do not require calibration (measurement 150/280A). Touch voltage and touch shock voltage measurement with resistor 1kΩ). AC voltage measurement in range 0...440V. Memory of 999 measurement results with an ability to transfer the data to a PC. Meter meets the requirements of the standard EN 61557.

Measurement of short circuit loop using standard current (2p, I =42A) Short circuit loop impedance Z measurement

Measuring range according to IEC61557: 0,13Ω...199,9Ω for 1,2m long test leads.

RangeResolutionAccuracy
0...19,99mΩ0,01mΩ±(2% m.v. + 3 digits)
20...199,9mΩ0,1mΩ±(3% m.v. + 3 digits)

Short circuit resistance R and reactance X display range

RangeResolutionAccuracy
0...19,99mΩ0,01mΩ±(2% m.v. + 3 digits)
20...199,9mΩ0,1mΩ±(3% m.v. + 3 digits)

Prospective short circuit loop current

RangeResolutionAccuracy
1,150...1,999A0 001A
2,00...19,99A0,01A
20,0...199,9A0,1Aaccuracy of the current indication compu- ted, respectively, with the use of resistance
200...1999A1Ated, respectively, with the use of resistance measurement
2,00...19,99kA0,01kA
20,0...40,0kA0,1kA

Short circuit loop parameters measurement using high current (4p, I =280A)

High-current of measurement of short circuit loop impedance Z:

Rango de medición según la IEC61557: 7,2mΩ...1999mΩ.

RangeResolutionAccuracy
0...199,9mΩ 200...1999mΩ0,1mΩ 1mΩ±(2% m.v. + 2mΩ)

Short circuit resistance R and reactance X display range

RangeResolutionAccuracy
0...199,9mΩ 200...1999mΩ0,1mΩ 1mΩ±(2% m.v. + 2mΩ)

Prospective short circuit loop current

Measuring range according to IEC 61557: for Un = 230V: 115,0A...32,0kA and for Un = 400V: 200A...55,7kA.

RangeResolutionAccuracy
115,0...199,9A0,1A
200...1999A1AAccuracy of the current indication compu-
2,00...19,99kA0,01kAted, respectively, with the use of resistance
20,0...199,9kA0,1kAmeasurement
200kA...*1kA

* 230 kA for ULN

* 440 kA for ULL

Touch voltage measurement U ST and shock voltaje U T

RangeResolutionAccuracy
ltages measurement (True RMS) 0...100V1V±(10% m.v. + 2 digits)
RangeResolutionAccuracy
0...440V1V±(2% m.v. + 2 digits)
Frequency range: DC, 45...65Hz. Input impedance of the voltmeter: > 200kΩ.

Voltages measurement (True RMS)

Frequency measurement (for voltages within the range 50...440V)

Range ResolutionAccuracy
45,0...65,0Hz 0,1Hz±(0,1% m.v. + 1 digit)
“m.v.” - measured value.

AMPERIS PRODUCTS S.Lagricultura, 34, 27003 Agricultura,34 lugo [spain]27003, Lugo, Spain

AMZC-310S Specifications Electrical safety: Type of insulationDouble, according EN 61010-1 and IEC 61557 Measurement categoryIV 300V acc. to EN 61010-1 Protection class acc. to EN 60529IP20 Other technical data: Power supplyalkaline batteries LR14 (C) (5 pcs.) Resistor limiting the currentfor measurement 4p: 1,5Ω Number of measurements (alkaline batte-for measurement 2p: 10Ω ries)min. 2000 (4/min.) Temperature coefficient±0,1% of measured value/°C Rated operational conditions: Operating temperature0...+40°C

Standard accesories:

Optional accesories:

Test lead with banana plug; 1,2m; black Test lead with banana plug; 1,2m; yellow Pin probe with banana connector - black Pin probe with banana connector - yellow High-current probe with banana connector (2 pcs.) Test lead 3m (2 pcs.) Crocodile clip K03; black (4 pcs.) Kelvin’s clamp (2 pcs.) Carrying case L1 RS-232 serial transmission cable Hanging straps Calibration certificate Operating manual Battery pack

Software for creation of documentation Software for creation drawings and diagrams Software for creation of calculation USB key for software USB1.1/RS232 adaptor AGT-16P (triple phase socket adapter) AGT-32P (triple phase socket adapter) AGT-63P (triple phase socket adapter) Test lead with banana plug; 5m; yellow Test lead with banana plug; 10m; yellow Test lead with banana plug; 20m; yellow

AMPERIS PRODUCTS S.Lagricultura, 34, 27003 Agricultura,34 lugo [spain]27003, Lugo, Spain

Image: Blue instrument on the floor connected with red and blue leads to a switchgear cabinet while an operator presses its keys.

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote