AMPERIS BLU-A — Battery Load Units

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 7 pages · 263 KB) · Source page: BLU Battery Disharger

Batteries up to 500 V DC and 240 A, from 12.8 kg

Battery dischargers

Image: DV Power BLU battery load unit with touchscreen menu, emergency stop button, communication ports, high-current terminals and side cooling fans.

Battery discharge and capacity test unit

Capacity testing of stationary batteries in accordance with IEEE 450, IEEE 1188, IEEE 1106 and IEC 60896.

Product description

Image: Front of the BLU series battery load unit: touch screen menu, flash drive port, EXT IN/EXT OUT, current probe input, interface, alarm, emergency stop, high-current terminals and voltage sense inputs.

Five models up to 500 V

From the BLU100L to the BLU360V, the series discharges batteries from 3 to 500 V DC with up to 240 A and 28.4 kW, in units from 12.8 kg with built-in forced-air cooling. It works stand-alone or controlled from a PC and resumes the test after a power interruption.

Three modes and load profiles

Constant current, power or resistance, plus current, power or resistance load profiles that reproduce real load variation. The unit holds the set value throughout the test with no manual corrections, and settings can be changed while the test is running.

Key features

Full discharge down to 0 V with the ZVD module, at constant current up to 60 A.

Parallel operation of up to 10 units in master-slave mode over Ethernet and RS485 (BLU200A, BLU340A and BLU360V). Current probe mode: testing with the battery connected to its load or with external BXL load units. Discharge of single lead-acid, Li-ion and Ni-based cells. Adjustable alarm and shutdown parameters against excessive discharge. Stop by end voltage (total or per cell), capacity or time.

Internal memory with export to USB flash drive and external alarm output.

Front panel: 5.7-inch touch screen, current terminals and voltage sense inputs

Capacity testing with the battery in service and full discharge before recycling.

Applications and software

Image: Battery load unit connected with red and black cables to a string of battery cells, with earth connection.

Applications

Power plants and substations. Telecommunication systems.

Generator excitation systems.

Protection and control systems.

Full battery discharge before recycling (with ZVD).

PC software included

Included in the price, with free updates. It controls and monitors the test from a PC over USB with real-time curves and values of current, power, resistance, capacity, voltage and time, adds alarm and end-of-test conditions for cell voltage, string voltage, capacity and time, and produces reports in XLS, PDF, Word or RTF with image import.

A complete discharge system

The BVS/BVS-4 supervisor adds voltage and temperature of every cell, the BVR22 handheld recorder measures cell voltage, temperature and density (via Bluetooth), the external BXL load units increase power and the ZVD module short-circuits the remaining energy after discharging to 0 V, preventing voltage rebound.

Direct connection of the BLU-A to a stationary battery bank

BLU-A — MEASUREMENT DATA
Internal voltage0 – 300 V DC (BLU100L, BLU100A, BLU200A, BLU340A); 0 – 500 V DC (BLU360V); resolution 0.1 V or better (optional)
Voltage accuracy±0.5 % of reading ±0.1 V
Internal current0 – 300 A DC; resolution 0.1 A; ±(0.5 % of reading + 0.1 A)
Constant current±(0.5 % + 0.2 A); ripple max. 0.4 A peak; resolution 0.1 A
Constant power±1 %; ripple max. 0.2 kW; resolution 0.01 kW
Constant resistance0.1 – 300 Ω to ≤ 0.2 – 500 Ω depending on model; ±1 %; resolution down to 0.01 Ω
Current probe input0 – 1 V DC; ratio 0.3 – 100 mV/A settable; input impedance > 1 MΩ
Current clamp 30/300 A10 mV/A (30 A) and 1 mV/A (300 A); powered from the instrument; 1000 A clamps on request
Time±0.01 % of reading ±1 digit; from 00:00:00 to 23:59:59, resolution 1 s
Display ranges0 – 999.9 V; 0 – 2999.9 A; 0 – 9999.9999 Ah
Sampling10 Hz; result refresh rate 1 Hz

Stop conditions: end voltage (total battery or per cell), capacity and test time. Specifications valid at +25 °C with standard accessories.

BLU-A — TECHNICAL SPECIFICATIONS

BLU100LBLU100ABLU200ABLU340ABLU360V
Battery voltage3.0 – 300 V5.55 – 300 V5.55 – 300 V5.55 – 300 V5.55 – 500 V
Max. current160 A160 A240 A160 A160 A
Max. power14.2 kW14.2 kW19.7 kW28.4 kW28.4 kW
Constant resistance0.1 – 300 Ω0.2 – 300 Ω0.2 – 300 Ω*0.2 – 300 Ω≤ 0.2 – 500 Ω
Parallel operation——YesYesYes
Dimensions (mm)440 × 221 × 355440 × 221 × 355560 × 221 × 355730 × 221 × 355730 × 221 × 355
Weight12.8 kg12.8 kg14.5 kg20.6 kg20.6 kg
Transport case (weight)6.9 kg6.9 kg8.5 kg10.1 kg10.1 kg

With the ZVD module discharge reaches 0 V. * Up to 3000 Ω on request. On the BLU200A and BLU360V the maximum power derates above +35 °C.

Supply 90 – 264 V AC, 50/60 Hz, single-phase (IEC/EN 60320-1 C320 inlet); BLU200A, on request, from the battery under test at 110 – 240 V DC. 5.7" colour touch screen; USB communication (RS232 optional); languages: English, German, French and Spanish.

IP20 protection; operating 0 to +50 °C, storage −40 to +70 °C, humidity up to 95 % non-condensing. Test standards: IEEE 450-2010, IEEE 1188-2005, IEEE 1106-2015, IEC 60896-11/22. Safety IEC EN 61010-1 (Directive 2014/35/EU), EMC EN 61326-1 (Directive 2014/30/EU), CAN/CSA-C22.2 No. 61010-1.

Warranty: 3 years. Specifications valid at +25 °C.

BLU-A — MAXIMUM DISCHARGE CURRENT BY BATTERY VOLTAGE RANGE (A)

Battery voltage (V)BLU100LBLU100ABLU200ABLU340ABLU360V
3 – 550————
5 – 105040555050
10 – 208585110100100
20 – 30160160225160160
30 – 40160160240160160
40 – 60160160240160160
60 – 72160160240160160
72 – 90160160140160160
90 – 105120120140160160
105 – 130115115140160160
130 – 142105105140160160
142 – 2007575100150150
200 – 260555575115115
260 – 300505065100100
300 – 410————70
410 – 500————60

Current maintainable throughout the whole voltage range, with a minimum cell voltage of 1.75 V, at ambient temperature below +50 °C.

For higher currents or power: BLU-A units in parallel (BLU200A, BLU340A, BLU360V) or external BXL-A, BXL-T and BXL-V load units controlled by the instrument.

BLU-A — SCOPE OF SUPPLY AND ACCESSORIES

Image: Accessory tables: items included with the instrument (PC software, mains and ground cables, transport cases), standard accessories (current cables 35 or 50 mm², cable bag) and optional items such as ZVD module, BXL load units, BVR recorders and current clamp.

Example: 2 × BLU360V in parallel with standard accessories and BLU-BLU parallel cable CP-0003N6-00. Ask Amperis for the right configuration for your battery.

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote