Skip to content

Accessible version

FRONT CONTROL PANEL

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 11 pages · 434 KB)

BLU series battery discharger

  • BLU100A-BLU200A-BLU340A-BLU110T -BLU220T -BLU360V
Image: BLU series battery load unit: grey portable unit with display, keypad, emergency stop, current terminals and side fans.
  • BLU300C-BLU400C-BLU500CBLU600C-BLU800C

Discharger BLU series for batteries www. amperis.com

Very lightweight, stand-alone battery testing equipment, which can meet the requirements of a wide range of standardised and customised procedures. The discharge can be made at constant current, constant power, constant resistance or following a pre-selected profile.

  • Application: - Power plants - Telecommunications systems - Substations - Protection and control systems
  • Application: Benefits: - Power plants - Capacity measurement by means of a discharge test of - Telecommunications systems IEEE and IEC compliance. - Substations - Measurement of the internal resistance of the battery - Protection and control systems - Constant I, P or R modes of operation. - Allows to simulate the variation of the load characteristics during a discharge test. - The test configuration can be modified during the test. Software: - Parallel operation function (not included in BLU100A and - Includes updates BLU110T models) - Data export to XLS, PDF, WORD or RTF - Adjustable alarm and shutdown parameters to prevent - Customisable reports excessive discharges. - Alarms for cell voltage, bank voltage, capacity, time

BLU100A:

  • Weight: 12.8 kg -Discharge power up to 14.2 kW -Discharge current up to 160 A DC -Applicable to battery voltages of 7.5-300 V DC
Image: DV Power BLU series battery load unit with display, keypad, connectors, emergency stop and side fans.

BLU200A:

BLU340A:

  • Weight: 14.5 kg
  • Weight: 20.6 kg
  • Discharge power up to 19.7 kW -Discharge current up to 200 A DC -Applicable to battery voltages of 7.5-300 V DC
  • Discharge power up to 28.4 kW -Discharge current up to 160 A DC -Applicable to battery voltages of 7.5-300 V DC
Image: Two battery load units with display, control keys, emergency stop, high-current terminals and side cooling fans.

AMPERIS PRODUCTS, S.L. CONTACT

BLU110T:

  • Weight: 12.8 kg
  • Discharge power up to 6.2 kW
  • Discharge current up to 110 A DC
  • Applicable to battery voltages of 7.5-60 V DC
Image: DV Power BLU series battery load unit with display, keypad, connectors, emergency stop and side fans.

BLU220T:

BLU360V:

  • Weight: 15.1 kg
  • Weight: 20.6 kg
  • Discharge power up to 19.2 kW
  • Discharge power up to 28.4 kW
  • Discharge current up to 340 A DC
  • Discharge current up to 160 A DC
  • Applicable to battery voltages of 7.5-60 V DC
  • Applicable to battery voltages of 7.5-480 V DC
Image: Two battery load units with display, control keys, emergency stop, high-current terminals and side cooling fans.

AMPERIS PRODUCTS, S.L. CONTACT

C/Barbeito María, 14 27003, Lugo, Spain

BLU300C:

BLU400C:

BLU500C:

  • Weight: 17 kg
  • Weight: 22 kg
  • Weight: 17 kg
  • Discharge power up to 20 kW
  • Discharge power up to 42 kW
  • Discharge power up to 20 kW
  • Discharge current up to 220 A DC
  • Discharge current up to 300 A DC
  • Discharge current up to 220 A DC
  • Applicable to battery voltages of 5.25-300 V DC
  • Applicable to battery voltages of 5.25-300 V DC
  • Applicable to battery voltages of 5.25-300 V DC
Image: Three grey portable battery units side by side, each with display, control panel, connection terminals and fan grilles.

AMPERIS PRODUCTS, S.L. CONTACT

C/Barbeito María, 14 27003, Lugo, Spain

BLU600C:

BLU800C:

  • Weight: 22 kg
  • Weight: 20 kg
  • Discharge power up to 42 kW
  • Discharge power up to 32 kW
  • Discharge current up to 300 A DC
  • Discharge current up to 100 A DC
  • Applicable to battery voltages of 5.25-500 V DC
  • Applicable to battery voltages of 5.25-800 V DC
Image: Two DV Power battery load units side by side, with displays, connectors, emergency stops and side fans.

AMPERIS PRODUCTS, S.L.

C/Barbeito María, 14 27003, Lugo, Spain

1. Screen - 4.3" colour touch screen.

4. External input (EXT IN) and external output (EXT OUT) Used for parallel BLU-BLU operation (not available for BLU100A and BLU110T models)

  • 3. Flash DriveUsed to transfer the data from the BLU memory to an external memory+SBC/firmware upgrade
  • 7. Interface - Allows you to control BLU from a PC and download previously recorded results.
  • 9. Current and voltage terminals - Current and voltage test cable terminals.

11. Grounding protector. Protective earth connector used to connect to the protective earth (PE).

Image: Front panel of the BLU battery load unit with numbered callouts: display, keys, flash drive, EXT IN and EXT OUT, current probe input, emergency stop, interface, alarm, voltage sense, external load trigger and main terminals.

2. Keyboard. Used to control and operate the instrument.

  • 5. Current probe. Measurement of the charge current with the external current probe.
  • 6. Emergency STOP button. Used when an unexpected or unwanted action occurs.

8. Alarm output. Used to activate the external alarm buzzer.

10. External load trigger. Used to trigger BXL external load units.

DV-WIN SOFTWARE SCREENSHOT

Image: Battery discharge test software screen: string voltage 114.5 V, test current 50.0 A, duration 00:02:47 and capacity 2.3213 Ah, with voltage, current, power and resistance curves over time.
Image: AMPERIS PRODUCTS, S.L. C/Barbeito María, 14 27003, Lugo, Spain
Maximum ddischarge currennt (A)
Battery vvoltage (V)BLU 100ABLU 200ABLU340ABXL-ABLU 110TBLU 220TBXL-TBLU 360VBXL-V
NominalMin/Max
1210,58010010011911020015610026
1214,18010010016011020021010035
242116020016018611034023016055
2428,216020016025011034031016075
4842160200160186110340230160115
4856,4160200160250110340310160155
6052,512012016081---160141
6070,5120120160100---160190
11096,3110120160119---16096
110129,3110120160160---160130
120105100120150134---150107
120141100120150180---150145
220192,5557511067---11085
220258,5557511090---110115
240210507010067---10093
240282507010090---100125
280300 480-------5034 55
Weightt (kg/lbs)12,8/2814,5/3220,6/45,412,5/2812,8/28,215,1/3312,5/2820,6/45,416/35
Maximumpower (kW)14,219,728,425,46,219,217,528,435
Battery vooltage (V)BLU 300CMaximum BLU 400Cm discharge cu BLU500Current (A) BLU 600CBLU 800C
NominalMin/Max
65,25 7,055520552025
1210,5 14,1115401154050
2421 28,21858018580100
4842 56,4220150220150100
6052,5 70,5220200220200100
11096,3 129,3150300150300100
120105 141140300140300100
220192,5 258,57515075150100
240210 300 8007015070150100
Weight(kg/lbs)17/37,522/48,517/37,522/48,520/44,1
Maximum ppower (kW)2042204232

AMPERIS PRODUCTS, S.L. C/Barbeito María, 14 27003, Lugo, Spain

Maximumm discharge cuurrent (A)
Battery vvoltage (V)BLU 300CBLU 400CBLU500CBLU 600CBLU 800C
NominalMin/Max
480300 500--406550
640564 800----40
Weight(kg/lbs)17/37,522/48,517/37,522/48,520/44,1
Maximum ppower (kW)2042204232

AMPERIS PRODUCTS, S.L.

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote