BLU series battery discharger
- BLU100A-BLU200A-BLU340A-BLU110T -BLU220T -BLU360V
- BLU300C-BLU400C-BLU500CBLU600C-BLU800C
Discharger BLU series for batteries www. amperis.com
Very lightweight, stand-alone battery testing equipment, which can meet the requirements of a wide range of standardised and customised procedures. The discharge can be made at constant current, constant power, constant resistance or following a pre-selected profile.
- Application: - Power plants - Telecommunications systems - Substations - Protection and control systems
- Application: Benefits: - Power plants - Capacity measurement by means of a discharge test of - Telecommunications systems IEEE and IEC compliance. - Substations - Measurement of the internal resistance of the battery - Protection and control systems - Constant I, P or R modes of operation. - Allows to simulate the variation of the load characteristics during a discharge test. - The test configuration can be modified during the test. Software: - Parallel operation function (not included in BLU100A and - Includes updates BLU110T models) - Data export to XLS, PDF, WORD or RTF - Adjustable alarm and shutdown parameters to prevent - Customisable reports excessive discharges. - Alarms for cell voltage, bank voltage, capacity, time
BLU100A:
- Weight: 12.8 kg -Discharge power up to 14.2 kW -Discharge current up to 160 A DC -Applicable to battery voltages of 7.5-300 V DC
BLU200A:
BLU340A:
- Weight: 14.5 kg
- Weight: 20.6 kg
- Discharge power up to 19.7 kW -Discharge current up to 200 A DC -Applicable to battery voltages of 7.5-300 V DC
- Discharge power up to 28.4 kW -Discharge current up to 160 A DC -Applicable to battery voltages of 7.5-300 V DC
AMPERIS PRODUCTS, S.L. CONTACT
BLU110T:
- Weight: 12.8 kg
- Discharge power up to 6.2 kW
- Discharge current up to 110 A DC
- Applicable to battery voltages of 7.5-60 V DC
BLU220T:
BLU360V:
- Weight: 15.1 kg
- Weight: 20.6 kg
- Discharge power up to 19.2 kW
- Discharge power up to 28.4 kW
- Discharge current up to 340 A DC
- Discharge current up to 160 A DC
- Applicable to battery voltages of 7.5-60 V DC
- Applicable to battery voltages of 7.5-480 V DC
AMPERIS PRODUCTS, S.L. CONTACT
C/Barbeito María, 14 27003, Lugo, Spain
BLU300C:
BLU400C:
BLU500C:
- Weight: 17 kg
- Weight: 22 kg
- Weight: 17 kg
- Discharge power up to 20 kW
- Discharge power up to 42 kW
- Discharge power up to 20 kW
- Discharge current up to 220 A DC
- Discharge current up to 300 A DC
- Discharge current up to 220 A DC
- Applicable to battery voltages of 5.25-300 V DC
- Applicable to battery voltages of 5.25-300 V DC
- Applicable to battery voltages of 5.25-300 V DC
AMPERIS PRODUCTS, S.L. CONTACT
C/Barbeito María, 14 27003, Lugo, Spain
BLU600C:
BLU800C:
- Weight: 22 kg
- Weight: 20 kg
- Discharge power up to 42 kW
- Discharge power up to 32 kW
- Discharge current up to 300 A DC
- Discharge current up to 100 A DC
- Applicable to battery voltages of 5.25-500 V DC
- Applicable to battery voltages of 5.25-800 V DC
AMPERIS PRODUCTS, S.L.
C/Barbeito María, 14 27003, Lugo, Spain
1. Screen - 4.3" colour touch screen.
4. External input (EXT IN) and external output (EXT OUT) Used for parallel BLU-BLU operation (not available for BLU100A and BLU110T models)
- 3. Flash DriveUsed to transfer the data from the BLU memory to an external memory+SBC/firmware upgrade
- 7. Interface - Allows you to control BLU from a PC and download previously recorded results.
- 9. Current and voltage terminals - Current and voltage test cable terminals.
11. Grounding protector. Protective earth connector used to connect to the protective earth (PE).
2. Keyboard. Used to control and operate the instrument.
- 5. Current probe. Measurement of the charge current with the external current probe.
- 6. Emergency STOP button. Used when an unexpected or unwanted action occurs.
8. Alarm output. Used to activate the external alarm buzzer.
10. External load trigger. Used to trigger BXL external load units.
DV-WIN SOFTWARE SCREENSHOT
| Maximum d | discharge curren | nt (A) | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Battery v | voltage (V) | BLU 100A | BLU 200A | BLU340A | BXL-A | BLU 110T | BLU 220T | BXL-T | BLU 360V | BXL-V |
| Nominal | Min/Max | |||||||||
| 12 | 10,5 | 80 | 100 | 100 | 119 | 110 | 200 | 156 | 100 | 26 |
| 12 | 14,1 | 80 | 100 | 100 | 160 | 110 | 200 | 210 | 100 | 35 |
| 24 | 21 | 160 | 200 | 160 | 186 | 110 | 340 | 230 | 160 | 55 |
| 24 | 28,2 | 160 | 200 | 160 | 250 | 110 | 340 | 310 | 160 | 75 |
| 48 | 42 | 160 | 200 | 160 | 186 | 110 | 340 | 230 | 160 | 115 |
| 48 | 56,4 | 160 | 200 | 160 | 250 | 110 | 340 | 310 | 160 | 155 |
| 60 | 52,5 | 120 | 120 | 160 | 81 | - | - | - | 160 | 141 |
| 60 | 70,5 | 120 | 120 | 160 | 100 | - | - | - | 160 | 190 |
| 110 | 96,3 | 110 | 120 | 160 | 119 | - | - | - | 160 | 96 |
| 110 | 129,3 | 110 | 120 | 160 | 160 | - | - | - | 160 | 130 |
| 120 | 105 | 100 | 120 | 150 | 134 | - | - | - | 150 | 107 |
| 120 | 141 | 100 | 120 | 150 | 180 | - | - | - | 150 | 145 |
| 220 | 192,5 | 55 | 75 | 110 | 67 | - | - | - | 110 | 85 |
| 220 | 258,5 | 55 | 75 | 110 | 90 | - | - | - | 110 | 115 |
| 240 | 210 | 50 | 70 | 100 | 67 | - | - | - | 100 | 93 |
| 240 | 282 | 50 | 70 | 100 | 90 | - | - | - | 100 | 125 |
| 280 | 300 480 | - | - | - | - | - | - | - | 50 | 34 55 |
| Weight | t (kg/lbs) | 12,8/28 | 14,5/32 | 20,6/45,4 | 12,5/28 | 12,8/28,2 | 15,1/33 | 12,5/28 | 20,6/45,4 | 16/35 |
| Maximum | power (kW) | 14,2 | 19,7 | 28,4 | 25,4 | 6,2 | 19,2 | 17,5 | 28,4 | 35 |
| Battery vo | oltage (V) | BLU 300C | Maximum BLU 400C | m discharge cu BLU500C | urrent (A) BLU 600C | BLU 800C |
|---|---|---|---|---|---|---|
| Nominal | Min/Max | |||||
| 6 | 5,25 7,05 | 55 | 20 | 55 | 20 | 25 |
| 12 | 10,5 14,1 | 115 | 40 | 115 | 40 | 50 |
| 24 | 21 28,2 | 185 | 80 | 185 | 80 | 100 |
| 48 | 42 56,4 | 220 | 150 | 220 | 150 | 100 |
| 60 | 52,5 70,5 | 220 | 200 | 220 | 200 | 100 |
| 110 | 96,3 129,3 | 150 | 300 | 150 | 300 | 100 |
| 120 | 105 141 | 140 | 300 | 140 | 300 | 100 |
| 220 | 192,5 258,5 | 75 | 150 | 75 | 150 | 100 |
| 240 | 210 300 800 | 70 | 150 | 70 | 150 | 100 |
| Weight | (kg/lbs) | 17/37,5 | 22/48,5 | 17/37,5 | 22/48,5 | 20/44,1 |
| Maximum p | power (kW) | 20 | 42 | 20 | 42 | 32 |
AMPERIS PRODUCTS, S.L. C/Barbeito María, 14 27003, Lugo, Spain
| Maximum | m discharge cu | urrent (A) | ||||
|---|---|---|---|---|---|---|
| Battery v | voltage (V) | BLU 300C | BLU 400C | BLU500C | BLU 600C | BLU 800C |
| Nominal | Min/Max | |||||
| 480 | 300 500 | - | - | 40 | 65 | 50 |
| 640 | 564 800 | - | - | - | - | 40 |
| Weight | (kg/lbs) | 17/37,5 | 22/48,5 | 17/37,5 | 22/48,5 | 20/44,1 |
| Maximum p | power (kW) | 20 | 42 | 20 | 42 | 32 |