AMPERIS AMRU-10 Earth Resistance Meter

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 5 pages · 190 KB)

Earth resistance up to 9999 Ω with 3-pole and 2-pole methods

AMRU-10

Earth resistance meters

Image: Orange Sonel MRU-10 earth resistance meter with measurement display and control buttons.

AMRU-10

Earth resistance meter

Earth resistance by the technical 3-pole and the 2-pole methods, up to 9999 Ω, in an IP67 housing.

Image: The AMRU-10 with its large segment display

Grounding, kept simple

The AMRU-10 measures earth resistance by the technical three-pole method per EN 61557-5 — from 0.53 Ω to 9999 Ω at 50 V — and by the two-pole method, along with the resistance of the auxiliary electrodes RH and RS up to 19.9 kΩ and interference voltages up to 100 V. Its ergonomic, rugged housing and large, legible display make it a natural choice for field work.

Stable readings under disturbance

A measurement current above 20 mA at 125 or 150 Hz and a selectable test voltage of 25 or 50 V keep the readings accurate even with disturbance voltages up to 24 V present. Resolution starts at 0.01 Ω with an intrinsic uncertainty of ±(3 % of reading + 3 digits), and battery indication with automatic power-off looks after the four AA cells.

Main features

  • Technical 3-pole method per EN 61557-5 and 2-pole method.
  • Auxiliary electrode resistances RH and RS up to 19.9 kΩ.
  • Interference voltage measurement up to 100 V.
  • Selectable measuring voltage of 25 V or 50 V.
  • Battery state indication and auto-off function.
  • CAT III 300 V safety with an IP67 housing.

Applications and delivery

Applications

  • Verification of earthing systems in electrical installations.
  • Earth electrodes of buildings, substations and lightning protection.
  • Quality checks of the earthing circuit from the measured result.
  • Work by installation contractors and maintenance technicians.

Everything included

The set includes 30 m and 15 m leads on reels, a 2.2 m lead, a crocodile clip, two 25 cm ground probes, AA batteries, carrying case, straps and a calibration certificate; 80 cm probes and leads up to 200 m on spools are optional. At about 660 g with batteries and only 221 × 102 × 62 mm, the AMRU-10 travels to wherever the earthing is.

AMRU-10 — TECHNICAL SPECIFICATIONS

Measuring methodsTechnical 3-pole per EN 61557-5; 2-pole
Earth resistance range0.53…9999 Ω (UN = 50 V); display from 0.01 Ω
Accuracy±(3 % m.v. + 3 digits) to 199.9 Ω; ±5 % to 1999 Ω; ±8 % to 9999 Ω
Auxiliary electrodesRH and RS: 0…19.9 kΩ; ±(5 % m.v. + 8 digits)
Interference voltage0…100 V; ±(10 % m.v. + 1 digit)
Measuring current> 20 mA (short circuit); 125 Hz or 150 Hz
Measuring voltageSelectable: 25 V or 50 V
Permitted disturbanceRE measured with interference up to 24 V
Power supply4 × AA alkaline batteries or NiMH accumulators
DisplayBacklit segment LCD
SafetyCAT III 300 V; double insulation per EN 61010-1
Protection classIP67, per EN 60529
Operating conditions-10…+50 °C; humidity 20-90 %
Dimensions and weight221 × 102 × 62 mm; approx. 660 g with batteries
StandardsEN 61557-5, EN 61010-1, EN 61326-1, EN 61326-2-2

AMRU-10 — MEASUREMENT DATA

Earth resistance RE — 3-pole method

Measuring range acc. to EN 61557-5: 0.53 Ω…9999 Ω for test voltage UN = 50 V.

Range ResolutionAccuracy
0.00…19.99 Ω 0.01 Ω±(3% m.v. + 3 digits)
20.0…199.9 Ω 0.1 Ω±(3% m.v. + 3 digits)
200…1999 Ω 1 Ω±5%
2000…9999 Ω 1 Ω±8%
Earth resistance RE — 2-pole method
Range ResolutionAccuracy
0.01…19.99 Ω 0.01 Ω±(3% m.v. + 3 digits)
20.0…199.9 Ω 0.1 Ω±(3% m.v. + 3 digits)
200…1999 Ω 1 Ω±5%
2000…9999 Ω 1 Ω±8%
Interference voltage meaasurement UN
RangeResolutionAccuracy
0…100 V Measurement for 45…65 Hz; at le1 V east 2 measurements per second.±(10% m.v. + 1 digit)
Measurement for 45…65 Hz; at leeast 2 measurements per second.
Resistance of auxiliary ellectrodes RH, RS
RangeResolutionAccuracy
0…999 Ω1 Ω±(5% + 8 digits)
1.00…9.99 kΩ0.01 kΩ±(5% + 8 digits)
10.0…19.9 kΩ0.1 kΩ±(5% + 8 digits)

Test current at short circuit > 20 mA; measuring frequency 125 Hz (50 Hz networks) or 150 Hz (60 Hz networks); test voltage selectable 25 V or 50 V; maximum interference voltage during the RE measurement: 24 V.

"m.v." – measured value.