AMPERIS CAT Advanced Series Circuit Breaker Analyzers

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 5 pages · 213 KB)

Up to 12 contacts, DRM and 500 A built in

CAT

Circuit breaker testing

Image: CAT35, CAT36, CAT65 and CAT66 circuit breaker analysers in an open rugged case, with a quick guide in the lid, display and colour-coded terminals.

Circuit breaker analyzers with micro-ohmmeter

Comprehensive HV breaker diagnosis: timing, motion, coils and resistance.

Product overview

Image: Top panel: main contacts, auxiliaries, coils, transducers and micro-ohmmeter

Acquisition at full scale

The advanced series simultaneously times up to 12 main contacts (4 breaks per phase) and 6 auxiliaries, records 6 coil currents up to ±35 A, measures with 6 analog channels from ±1 to ±300 V and follows the motion with 3 analog or digital transducer channels, sampling at 40 kHz with 0.025 ms resolution.

A micro-ohmmeter inside the analyzer

Except for the CAT64A and CAT124A, every model integrates a 200 or 500 A micro-ohmmeter of pure DC with a regulated ramp: static resistance by Kelvin's method and dynamic resistance (DRM) during the operation, with an optional high-precision module.

Main features

  • Eight models: CAT35, CAT36, CAT65, CAT66, CAT125, CAT126, CAT64A and CAT124A.
  • Time accuracy of ±0.01% of reading ±0.1 ms.
  • First trip test with the installation in service.
  • Anti-pumping relay test.
  • Resistance of 3 coils at once (1 – 999 Ω).
  • Optional Both Sides Grounded (BSG) measurement.
  • Results via USB or PC in numerical and graphical form.

Applications and software

Image: High-voltage circuit breaker: the series' test object

Applications

  • Complete diagnosis of HV and MV breakers in substations.
  • Static and dynamic resistance (DRM) of the arcing contact.
  • Travel, rebound and velocity curves with 3 transducers.
  • First trip after long idle periods.
  • Minimum operating voltage with the associated coil power source.

PC software for control and analysis

The included PC software controls the instrument, overlays graphs of timing, currents, motion and resistance, assesses each operation against the test plans in its database and builds customisable reports with the asset data.

From timing to contact wear

The resistance-versus-travel curve obtained in DRM reveals the arcing contact's length and condition without opening the chamber; with 500 A currents the voltage drop reading is reliable even on contacts in good shape.

CAT�ADVANCED�—�MEASUREMENT�DATA

Time resolution0.025 ms (1 s, 40 kHz); 0.1 ms (2 s); 1 ms (20 s); 10 ms (200 s)
Time accuracy±0.01% of reading ±0.1 ms
Main contactsClosed ≤ 10 Ω; pre-insertion 10 Ω – 5 kΩ; open ≥ 5 kΩ; 20 V DC / 100 mA
Coil current6 channels, ±35 A AC/DC; 25 mA resolution; ±(0.5% + 0.1% FS)
Analog channels6, ±1 / ±5 / ±60 / ±300 V ranges; down to ±(0.1% + 0.05% FS)
Coil resistance3 coils at once; 1 – 999 Ω; typical ±(0.5% + 0.5% FS)
Built-in micro-ohmmeterUp to 500 A pure DC with regulated ramp; static and DRM
Transducers3 digital (2500 ppr) and 3 analog (16-bit); 5 V DC supply

Auxiliaries: 6 dry or wet channels, up to 300 V DC / 250 V AC. Specifications valid at +25 °C with standard accessories.

CAT�ADVANCED�—�TECHNICAL�SPECIFICATIONS

CAT35CAT36CAT65CAT66CAT125CAT126CAT64ACAT124A
Main contacts33661212612
Breaks per phase11224424
Built-in micro-ohmmeter200 A500 A200 A500 A200 A500 A——
High-precision moduleOpt.Opt.Opt.Opt.Opt.Opt.——

Common: 6 auxiliary inputs, 6 analog channels, 6 coil control outputs and 3 transducer channels; dimensions 480 × 197 × 395 mm; weight 10.7 to 13.2 kg depending on model and options; supply 90 – 264 V AC, 50/60 Hz; maximum input power 100 VA (without micro-ohmmeter), 1500 VA (200 A) or 3900 VA (500 A); USB and USB stick.

Standards: safety EN 61010-1; EMC EN 61326-1; installation category II; pollution degree 2. Specifications valid at +25 °C.

C/ María Barbeito, 14Contact Contact +T [+34] 982 20 99 20
27003, Lugo, Spain+T [+34] 982 20 99 20 info@amperis.com | www.amperis.com

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote