Three test-voltage levels, one shared cable set with the TWA

Standard Series TRT Three-phase turns ratio measurement with ±0.03% accuracy

TRT

Image: Transformer turns ratio tester in an open case with display, keypad, terminals and quick guide in the lid; TRT03, TRT33 and TRT63 models.
Image: TRT03, TRT33 and TRT63 turns ratio testers in an open rugged case with a quick guide in the lid.

Test technology

TRT Standard is based on the most advanced technique available for testing single-phase and three-phase transformers, with or without a tap changer, under IEC 60076-1. For a three-phase measurement the instrument is connected to all three phases of the transformer at once; once the corresponding vector diagram is selected, it runs the specific test for each connection type - star-delta, delta-delta, star-zigzag, etc. - without changing the test leads.

Deviation calculation and result interpretation

The operator enters the nameplate voltages and the instrument automatically calculates the ratio deviation, comparing the result with the nameplate value and printing the percentage error for each test. Operating-condition messages flag incorrect tests, wiring faults or possible transformer problems immediately, thanks to a very efficient filtration of the electrostatic and electromagnetic interference present in HV electric fields.

Connection to the transformer

Using two sets of four cables, all bushings on the primary and secondary sides are connected in a single step, on both three-phase transformers and three-phase autotransformers defined by the IEC, IEEE and ANSI standards. Although a three-phase device, TRT also tests single-phase transformers and autotransformers by reusing part of the same cable set, as well as current transformers, connecting the “X” leads to the primary side of the CT or sliding them through its window when no primary terminals exist.

Front view of the TRT Standard Series, with keypad and LCD display.

Applications and software

Image: Connection panel of the TRT Standard Series (top view).

Applications

  • Commissioning and periodic maintenance of power and distribution transformers, with or without an on-load tap changer.
  • Ratio and polarity verification of current transformers, with test voltages from 1 V AC.
  • Testing of special transformers: phase-shifting, rectifier and arc-furnace units.
  • Automatic vector group detection and magnetic balance test on three-phase units.

Cables shared with the winding analyzer

TRT Standard uses the same H and X cable set as the TWA Three-Phase Winding Analyzer, so a single connection to the bushings chains the turns ratio test with winding resistance, on-load tap changer DVtest and demagnetization, without rewiring the transformer.

PC software

A Windows-based PC software, included in the purchase price with free updates, controls every TRT function from the computer: creating and recording test plans, downloading results from the internal memory, and displaying every measurement numerically and graphically. Customised reports export to spreadsheet, text document or PDF. Accessories: H and X test lead sets in several lengths, cable cases, TRTC verification calibrator, cable bag, Bluetooth module and, as an option, a built-in 58 mm thermal printer.

TRT — MEASUREMENT DATA
Turns ratio range0.8 - 50,000 (5-digit resolution)
Accuracy at maximum voltage (250 V AC)±0.03% (0.8-999); ±0.05% (1,000-19,999); ±0.1% (20,000-50,000)
Accuracy at minimum voltage (1 V AC)±0.05% (0.8-999); ±0.1% (1,000-4,000)
Excitation current range0 - 2 A; resolution from 0.1 µA to 100 µA depending on range
Excitation current accuracy±(0.25% of reading + 0.5 mA)
Phase angle range0 - 360°; resolution 0.01°; accuracy ±0.05°

Accuracy depends on the selected test voltage; the highestand lowest-voltage cases available are shown (see per-model specifications). Data valid at +25 °C with standard accessories (manufacturer's current datasheet).

TRT — TECHNICAL SPECIFICATIONS

TRT63TRT33TRT03
Voltage sourceSingle-phase and true three-phaseSingle-phase and true three-phaseSingle-phase
Test voltage1-250 V AC1-100 V AC8-100 V AC
Input power250 VA200 VA200 VA
DisplayBacklit LCD, 20×4 charactersBacklit LCD, 20×4 charactersBacklit LCD, 20×4 characters
Internal memory10,000 test records10,000 test records10,000 test records
InterfaceUSB; RS-232 optionalUSB; RS-232 optionalUSB; RS-232 optional
Dimensions (W×H×D)478 × 194 × 390 mm478 × 194 × 390 mm478 × 194 × 390 mm
Weight9 kg8 kg8 kg

A/B/C mains variants depending on the test voltage available in each country (manufacturer's datasheet). Common environmental conditions: operation from -20 to +60 °C, storage from -40 to +70 °C, relative humidity up to 95% non-condensing. Standards: safety EN 61010-1; electromagnetic compatibility EN 61326-1; IEEE C57.12.90. Specifications valid at +25 °C.