AMPERIS BLU-C Battery Load Unit Series

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 5 pages · 202 KB) · Source page: BLU Battery Disharger

Image: BLU-C catalogue cover, battery dischargers: battery load unit and capacity tester for banks up to 800 V DC with total discharge down to 0 V.

Capacity measurement of stationary batteries per IEEE 450, IEEE 1188, IEEE 1106 and IEC 60896.

Image: Front panel: 7-inch touch screen and current and sense terminals

Nine models up to 800 V

From the BLU100C to the BLU800C, the series discharges lead-acid, Li-ion, Ni-Cd or other chemistry strings with up to 300 A and 42.0 kW. The test is followed in real time on the 7-inch touch screen, with voltage and capacity graphs, and resumes by itself after a mains interruption.

Four modes plus load profiles

Constant current, power, resistance or voltage, plus programmable profiles that reproduce real duty cycles. With the current probe, the bank is tested without taking it out of service while the total current or power is kept constant.

Main features

  • Optional total discharge down to 0 V; with the ZVD module, at constant current up to 60 or 120 A.
  • Parallel operation of up to 10 identical units (from the BLU300C).
  • Cell supervision with CVM/CVM-4 modules (from the BLU300C).
  • Current adjustable with 0.1 A resolution.
  • External BXL loads to extend the capacity.
  • Adjustable alarms and shutdown against excessive discharge.
  • Internal memory with USB download; optional Ethernet and RS232.

Applications and software

Image: Capacity test on a stationary battery bank

Applications

  • Power plants and substations.
  • Telecommunication systems and data centres.
  • Generator excitation systems.
  • Protection and control systems.
  • Complete discharge of banks before recycling.

PC software for control and analysis

The included PC software controls and observes the test over USB, presents the key parameters numerically and graphically, accepts extra alarms on cell voltage or capacity and builds reports in Excel, PDF or Word with image import.

A complete discharge system

The cell modules connected to the unit show cell and intercell voltages on screen, the handheld voltage recorder complements the measurement with temperature and density via Bluetooth, and the ZVD module finishes the total discharge by short-circuiting the remaining energy.

BLU-C�—�MEASUREMENT�DATA

Internal voltage0 – 300 V DC (BLU100C-400C); 0 – 500 V (BLU500C/600C); 0 – 570/700/800 V by model; 0.1 V resolution
Voltage accuracy±0.5% of reading ±0.1 V (0 – 800 V DC)
Internal current0 – 300 or 0 – 400 A DC by model; 0.1 A resolution
Current with external probe0 – 2999.9 A DC; ±(0.5% + 0.2 A); ripple max ±0.4 A
Cell measurement (modules)±50 mV, ±1 V and ±30 V DC; down to ±(0.1% + 0.1%)
Constant resistance0.1 – 3000 Ω to 0.2 – 8000 Ω by model; ±1%
Time±0.1% of reading ±1 digit; up to 23 h 59 min
Display ranges0 – 999.9 V; 0 – 2999.9 A; 0 – 9999.9 Ah

Cell voltage sampling at 10 Hz; values are stored when the change exceeds 10 mV. Specifications valid at +25 °C with recommended accessories.

BLU-C�—�TECHNICAL�SPECIFICATIONS

BLU100CBLU200CBLU300CBLU400CBLU500CBLU570CBLU600CBLU700CBLU800C
Max. current150 A300 A270 A300 A270 A100 A300 A260 A100 A
Max. voltage300 V300 V300 V300 V500 V570 V500 V700 V800 V
Max. power20 kW42 kW20 kW42 kW20 kW32 kW42 kW42 kW32 kW
Cell supervision——YesYesYesYesYesYesYes
Parallel operation——YesYesYesYesYesYesYes
Weight18.9 kg28.5 kg18.9 kg28.5 kg18.9 kg20.8 kg28.5 kg28.0 kg20.8 kg

Dimensions: 564 × 267 × 355 mm (BLU100C, BLU300C, BLU500C); 615.5 × 287 × 566 mm (BLU200C, BLU400C, BLU600C, BLU700C); 560 × 268 × 473 mm (BLU570C, BLU800C). Supply 90 – 264 V AC, 50/60 Hz; input power 200 W (400 W with cell supervision).

The maximum current shown is the one maintainable over the whole voltage range; the maxima per voltage band appear on the measurement data page. Test standards: IEEE 450-2010, IEEE 1188-2005, IEEE 1106-2015, IEC 60896-11/21. Specifications valid at +25 °C.