Skip to content

Accessible version

AMIC-10

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 3 pages · 165 KB)

Insulation Resistance Meter

HIGHEST ACCURACY & LOWEST COST

Image: Sonel insulation resistance meter in an orange housing with LCD display, keypad and rotary function selector.

AMIC-10

Insulation resistance measurement: 50, 100, 250, 500 or 1000 V. 10GΩ.

Low voltage resistance measurement. AC/DC voltage measurement 0...600V.

Capacitance measurements.

AMPERIS PRODUCTS S.Lagricultura, 34, Contact 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, Spain info@amperis.com | www.amperis.com

Main characteristics are the following:

Insulation resistance measurement:

  • Measurement voltage: 50, 100, 250, 500 or 1000 V
  • Continuous indication of insulation resistance or leakage current
  • Automatic discharge of capacitance of tested object after the insulation resistance measurement
  • Acoustic signaling of five-second periods to facilitate obtaining time characteristics
  • Indication of actual test voltage during the measurement
  • Protection against measuring live objects
  • Three-lead measurement

Continuity measurement of protective and equipotential conductors according to EN 61557-4 with the >200mA current.

Low-voltage circuit continuity and resistance measurement:

  • Circuit resistance measurement (<1999Ω) with <15mA current
  • Quick sound signal if circuit resistance is below 30. Capacitance measurement during the RISO measurement Measurement of alternating and direct voltages in the 0...600V range Power supply: 4 AA or rechargeable batteries, monitoring of power supply voltage.

Continuity measurement of protective and equipotential conductors with the 200mA current Measuring range according to EN 61557-4: 0,10...1999Ω

RangeResolutionAccuracy
0,00...19,99Ω0,01Ω±(2% m.v. + 3 digits)
20,0...199,9Ω0,1Ω±(2% m.v. + 3 digits)
200...1999Ω1Ω±(4% m.v. + 3 digits)
Voltage on open terminals: <8V Output current at R <2Ω: ISC >200mA. Compensation of test leads’ resistance. Unidirectional current flow.
Low-voltage and resistance measurement
Range ResolutionAccuracy
00,0...199,9Ω 0,1Ω±(3% m.v. + 3 digits)
200...1999Ω 1Ω±(3% m.v. + 3 digits)
Voltage on open terminals: <8V. Current for closed terminals5mA < ISC << 15mA . Sound signal and green LED on when measured resistance < 30Ω ± 50%. Compensation of test leads’ resistance.

Capacitance measurements

RangeResolution Accuracy
1...999nF 1,00...9,99μF1nF ±(5% m.v. +5 digits) 0,01μF
Capacitance value displayed during the RISSO measurement.
IS For test voltages below 100V and measureSO ed resistance below 10MΩ, unspecified capacitance measurement error. “m.v.” = “measured value”.

Insulation resistance measurement:

Measuring range according to EN 61557-2 for UN =50V: 50kΩ...250,0MΩ

Range ResolutionAccuracy
0,0...999,9kΩ 0,1kΩ
1,000...9,999MΩ 0,001MΩ±(3%.m.v. + 8 digits)
10,0...99,99MΩ 0,01MΩ±(3%.m.v. + 8 digits)
100,0...250,0MΩ 0,1MΩ
100,0...250,0MΩ 0,1MΩ Measuring range according to EN 61557-2 for UN =100V: 100kΩ...500,0MΩ
Range ResolutionAccuracy
0,0...999,9kΩ 0,1kΩ
1,000...9,999MΩ 0,001MΩ±(3%.m.v. + 8 digits)
10,0...99,99MΩ 0,01MΩ±(3%.m.v. + 8 digits)
100,0...500,0MΩ 0,1MΩ
Measuring range according to EN 61557-2 for UN =250V: 250kΩ...2000,0MΩ
Range ResolutionAccuracy
0,0...999,9kΩ 0,1kΩ
1,000...9,999MΩ 0,001MΩ
10,0...99,99MΩ 0,01MΩ±(3%.m.v. + 8 digits)
100,0..999,9MΩ 0,1MΩ
1000,0..2000,0MΩ 1MΩ
1000,0..2000,0MΩ 1MΩ Measuring range according to EN 61557-2 for UN =500V: 500kΩ...5000,0MΩ
Range ResolutionAccuracy
0,0...999,9kΩ 0,1kΩ
1,000...9,999MΩ 0,001MΩ±(3%.m.v. + 8 digits)
10,0...99,99MΩ 0,01MΩ±(3%.m.v. + 8 digits)
100,0..999,9MΩ 0,1MΩ
1000,0..5000,0MΩ 1MΩ±(4%.m.v. + 6 digits)
Measuring range according to EN 61557-2 for UN =1000V: 1000kΩ...10,0GΩ
Range ResolutionAccuracy
0,0...999,9kΩ 0,1kΩ
1,000...9,999MΩ 0,001MΩ±(3%.m.v. + 8 digits)
10,0...99,99MΩ 0,01MΩ±(3%.m.v. + 8 digits)
100,0..999,9MΩ 0,1MΩ
1000,0..5000,0MΩ 1MΩ±(4%.m.v. + 6 digits)
5,0..10,0GΩ 0,01GΩ±(4%.m.v. + 6 digits)
Measurement of AC/DC voltage
Range ResolutionAccuracy
0,0...299,9V 0,1V±(2%m.v. + 6 digits)
300...600V 1V±(2%m.v. + 2 digits)
Frequency range: 45...65Hz.

AMPERIS PRODUCTS S.Lagricultura, 34, 27003 Agricultura,34 lugo [spain]27003, Lugo, Spain

AMIC-10 Specifications Electric security: Type of insulationDouble, acc. to EN 61010-1 and IEC 61557 Measurement categoryCAT IV 600V acc. to EN 61010-1 Protection class acc. to EN 60529IP67 Other technical data: Power suply4 alkaline batteries or battery package Ni-MH Weight1kg Dimensions220 x 100 x 60 mm

Standard accesories:

“Crocodile” clip K01; black Test lead with banana plug; 1,2m; red Test lead with banana plug; 1,2m; blue Pin probe with banana connector; black Pin probe with banana connector; red Carrying case M6 Hanging straps Handle to suspend the meter Certificate calibration Battery set

Optional accesories:

Test lead with banana plug 5m; red Test lead with banana plug 5m; blue Shielded test lead with banana plug; 5m; black Test lead with banana plug 1,2m; blue “Crocodile” clip K02; red “Crocodile” clip K01; black “Crocodile” clip K02; blue Pin probe with banana connector; blue Adapter WS-04 with UNI-Schuko

AMPERIS PRODUCTS S.Lagricultura, 34, Contact 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, Spain info@amperis.com | www.amperis.com

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote