Insulation Resistance Meter
AMIC-5005
Insulation resistance measurement - 15TΩ: * 50 – 1000 V, 10 V steps * 1000 – 5000 V, 25 V steps Memory of 999 measurement results and PC transmission. Capacitance and DC/AC voltage measurement. Leakage current measurement. Digital filters function.
AMPERIS PRODUCTS S.Lagricultura, 34, Contact 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, Spain info@amperis.com | www.amperis.com
Main characteristics are the following: Insulation resistance measurement:
Insulation resistance measurement
Measurement range acc. to EN 61557-2: 50 kΩ...15,0TΩ (I ISOnom =1,2 mA ó 3 mA)
- Measurement voltage:
*50 – 1000 V, 10 V steps
| Range | Resolution | Accuracy |
|---|---|---|
| 0,0...999,9kΩ | 1kΩ | |
| 1,000...9,999MΩ | 0,01MΩ | |
| 10,0...99,99MΩ | 0,1MΩ | ±(3%.m.v.. + 10 digits) |
| 100,0...999,9MΩ | 1MΩ | ±(3%.m.v.. + 10 digits) |
| 1,000...9,999GΩ | 0,01GΩ | |
| 10,0...99,99GΩ | 0,1GΩ | |
| 100,0...999,9GΩ | 1GΩ | ±(3,5%.m.v.. + 10 digits) |
| 1,000...9,999TΩ | 0,01TΩ | ±(7,5%.m.v.. + 10 digits) |
| 10,0...15,00TΩ | 0,1TΩ | ±(10%.m.v.. + 10 digits) |
*1000 – 5000 V, 25V steps
- Continuous indication of measured insulation resistance or leakage current.
- Automatic discharge of measured object capacitance voltage.
- Acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics.
- Metered T1 , T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s.
- Adjustable measuring time to 99’59’’.
- Polarization index (PI) and dielectric absorption ratio (DAR) measurement.
- Indication of actual test voltage during measurement.
- 1.2 mA and 3 mA test current,.
- Medición de Resistencia de aislamiento con Voltage Rampa (step voltage SV).
- Dielectric Discharge calculation (DD).
Values of measured resistance depending on measurement voltage
- Protection against measuring live objects.
- Measurements with test leads up to 20 m. Digital filters function for measurements in high noise enviroment (10 s, 30 s, 60 s). Measurement of leakage current during insulation resistance testing.
| Voltage UISO | Measurement range |
|---|---|
| 250V | 500GΩ |
| 500V | 1,00TΩ |
| 1000V | 2,00TΩ |
| 2500V | 5,00TΩ |
| 5000V | 15,00TΩ |
Measurement of capacitance during the measurement of RISO. DC and AC voltage measurement in the range of 0…600 V. 990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR adapter) or through a USB cable.
Power supply from main power line or battery packs, low battery warning indicator, built-in fast charger. Keyboard and display backlit.
Measurement of leakage current
| Range | Resolution | Accuracy |
|---|---|---|
| 0…1,2 mA* | Resolution and units result from the measurement range of | Calculated basing on resistance |
| 0…3 mA* | individual insulation resistance. | measurements. |
Measurement of capacitance
| Range | Resolution | Accuracy |
|---|---|---|
| 1...999 nF 1,00...49.99 μF | 1 nF 0,01 μF | ±(5%m.v. + 5 digits) |
* - depending on the setting.
Step voltage insulation resistance measurement
Capacity measurement result is displayed after the RISO measurement.
| Target voltage | Measurement voltage sequence |
|---|---|
| 1 kV | 200, 400, 600, 800, 1000 V |
| 2.5 kV | 0.5, 1, 1.5, 2, 2.5 kV |
| 5 kV | 1, 2, 3, 4, 5 kV |
| Duration of each “step” adjustable from 30 s to 5 mins. | |
| Measurement result for each voltage step is stored in memory. |
DC and AC voltage measurement
| Range | Resolution | Accuracy |
|---|---|---|
| 0,0...29.9 V | 0,1 V | ±(2%m.v. + 20 digits) |
| 30,0...299.9 V | 0,1 V | ±(2%m.v. + 6 digits) |
| 300...600 V | 1 V | ±(2%m.v. + 2 digits) |
“m.v.” = “measured value”.
Frequency range: 45...65Hz.
AMPERIS PRODUCTS S.Lagricultura, 34, 27003 Agricultura,34 lugo [spain]27003, Lugo, Spain
Specifications AMIC-5005
Electric security:
Type of insulationDouble, acc. to EN 61010-1 and IEC 61557 Measurement categoryCAT IV 600V (III 1000V) EN 61010-1 Above sea level3000 m. Protection class acc. to EN 60529IP54 (IP67 with cover closed) Power supply90 – 265V 50/60Hz and built-in battery packs Weightaprox. 7 kg Dimensions390 x 310 x 170 mm DisplayLCD Measurement results memory990 cells of memory (11880 records) Transmission of measurement resultsUSB or wireless interface
Other technical data:
Standard accesories:
USB cable Test lead banana plug; 1,8 m; 10kv; red Test lead banana plug; 1,8 m; 10 kv; blue Test lead banana plug; 1,8 m; 10 kv; black; shielded “Crocodile” clip 5,5 kv; black “Crocodile” clip 5,5 kv; blue “Crocodile” clip 5,5 kv; red Pin probe 5,5 kv with banana connector; red Pin probe 5,5 kv with banana connector; black Carrying case L4 for accesories Power cord Battery pack (built-in) Software Calibration certificate
Optional accesories:
Test lead banana plug; 3 m; 10kv; red Test lead banana plug; 3 m; 10kv; blue Test lead banana plug; 3 m; 10kv; black; shielded Test lead banana plug; 5 m; 10kv; red Test lead banana plug; 5 m; 10kv; blue Test lead banana plug; 5 m; 10kv; black; shielded Test lead banana plug; 10 m; 10kv; red Test lead banana plug; 10 m; 10kv; blue Test lead banana plug; 10 m; 10kv; black; shielded Test lead banana plug; 20 m; 10kv; red Test lead banana plug; 20 m; 10kv; blue Test lead banana plug; 20 m; 10kv; black; shielded Carring backpack L7 OR-1 radio receiver for data transmission
OR-1 radio receptor USB para transmisión de datos.
AMPERIS PRODUCTS S.Lagricultura, 34, Contact 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, Spain info@amperis.com | www.amperis.com