Skip to content

Accessible version

AMPERIS AGTU SF{6} Gas Transfer Unit

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 5 pages · 171 KB) · Source page: SF6 gas transfer unit AGTU

The compact solution to recover, consolidate and transfer SF6 in small-volume equipment

SF6 handling equipment

Image: Green portable unit with carrying handles, three connection valves, switches and ventilation grille.

AGTU

SF6 gas transfer unit

Designed for small volumes of SF6

The AGTU was created as a low-cost solution to recover, consolidate and transfer sulfur hexafluoride (SF6) in circuit breakers and small-volume gas equipment, up to 69 kV. It is the ideal tool for consolidating partially used cylinders into one, or for recovering left-over gas from higher-capacity carts.

Oil-less, direct-drive compressor

An oil-less, direct-drive compressor with a 1000:1 compression ratio reaches up to 34 bar of discharge pressure: enough to liquefy SF6 even at high ambient temperatures. The regulated inlet allows direct connection to high-pressure bottles, with no need to throttle the gas.

Main advantages

  • Purifies, dries and filters the gas down to 0.1 microns on every recovery and re-pressurization.
  • Colour-change moisture indicator to monitor the condition of the gas.
  • Filters can be replaced without disconnecting tubing or using special tools.
  • Automatic compressor shutoff once the maximum allowable pressure is reached.
  • Rugged steel enclosure, suited to SF6 tanks, bottles or carts.
  • Supplied with 3 m hoses and a power cable.

Applications and operation

Applications

  • Recovery of SF6 gas to an optional auxiliary storage tank.
  • Pressure-regulated recharging of SF6 gas to switchgear.
  • Consolidation of partially used storage cylinders.
  • Purification of SF6: removes particles, moisture and decomposition products.

How it works

A single unit handles the three basic operations of small-volume servicing: it recovers gas from the equipment down to a residual pressure of 100 mbar (optionally below 1 mbar with the XDS module), purifies and dries it as it passes through the filters, and transfers it again, or into another bottle, at a rate of up to 2 m³/h.

Options

  • Additional XDS vacuum module, to bring residual recovery pressure below 1 mbar.
  • Auxiliary external storage tank.
  • Longer hoses and special supply voltages on request.
AGTU — PERFORMANCE DATA
Designed forCircuit breakers and SF6 equipment up to 69 kV
SF6 transfer rateUp to 1.2 CFM (2 m³/h)
RecoveryDown to 100 mbar; optionally below 1 mbar with XDS module
SF6 compressorOil-less, direct-drive, 1000:1 ratio; up to 34 bar discharge
Filtration0.1 micron on every recovery and re-pressurization cycle

Performance data as per the manufacturer's current catalogue (2025).

AGTU — TECHNICAL SPECIFICATIONS
TypePortable SF6 gas transfer unit
EnclosureRugged steel
InletRegulated, for direct connection to high-pressure bottles
Moisture indicatorColour-change
Safety shutoffAutomatic once maximum allowable pressure is reached
Hoses3 m, supplied with power cable
Power supply120 V single-phase, 60 Hz / 220 V single-phase, 50/60 Hz
Dimensions (H × W × D)510 × 410 × 635 mm
Weight34 kg

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote