Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 8 pages · 180 KB) · Source page: AMIC-10: insulation resistance meter

AMIC-10

Insulation resistance, continuity, capacitance and voltage measurement in a single pocket-sized meter

Up to 1000 V, 5 test voltages

Image: Orange Sonel handheld meter with display reading 322, keypad and rotary selector.

AMIC-10

Insulation resistance meter up to 1000 V

Digital insulation resistance meter for low-voltage electrical installations and equipment up to 1000 V.

Five test voltages

The AMIC-10 measures insulation resistance at 50, 100, 250, 500 or 1000 V, with continuous display of the resistance or the leakage current and automatic discharge of the capacitance of the tested object once the measurement ends.

More functions in the same meter

Besides insulation resistance, it measures the continuity of protective and equipotential conductors according to EN 61557-4, the resistance of low-voltage circuits, capacitance during the insulation test itself, and DC and AC voltage between 0 and 600 V.

Readings during the test

  • Acoustic signal every five seconds, to follow the time elapsed during the test.
  • Display of the actual test voltage throughout the measurement.
  • Protection against accidentally measuring live objects.

Three-wire measurement with compensation of the test-lead resistance.

Measurement method

Three-wire measurement

Insulation resistance is measured using three wires, with compensation of the resistance of the test leads, and the voltage on open terminals stays below 8 V in every test.

Low-voltage continuity

Continuity is measured with a short-circuit current between 5 mA and 15 mA, and an acoustic signal with a green LED warns when the detected resistance is below 30 Ω. When checking protective conductors according to EN 61557-4 the short-circuit current is above 200 mA.

Applications

  • Insulation testing of cables, motors and other low-voltage equipment.
  • Checking the protective and equipotential conductors of an installation.
  • Periodic maintenance of low-voltage electrical installations.

Pocket-sized portable meter, battery-powered, with IP67 protection for field work.

Power supply and protection

Battery power

It runs on four AA alkaline batteries or on a set of Ni-MH rechargeable batteries, with a low-battery indicator on the display.

Protection for field use

Double insulation according to EN 61010-1 and IEC 61557 and CAT IV 600 V measurement category allow it to be used at the origin of an installation, and IP67 protection guards it against dust and temporary immersion in water.

Dimensions and weight

  • 220 × 100 × 60 mm and 1 kg, with an M6 carrying case.
  • Straps and a handle to hold the meter during the measurement.
  • Calibration certificate included as standard.

Insulation resistance by test voltage (50, 100, 250, 500 and 1000 V)

Measuring ranges according to EN 61557-2, for each test voltage.

Test voltageRangeResolutionAccuracy
50 V0.0…999.9 kΩ0.1 kΩ±3% m.v. +8 digits
1.000…9.999 MΩ0.001 MΩ
10.0…99.99 MΩ0.01 MΩ
100.0…250.0 MΩ0.1 MΩ
100 V0.0…999.9 kΩ0.1 kΩ±3% m.v. +8 digits
1.000…9.999 MΩ0.001 MΩ
10.0…99.99 MΩ0.01 MΩ
100.0…500.0 MΩ0.1 MΩ
250 V0.0…999.9 kΩ0.1 kΩ±3% m.v. +8 digits
1.000…9.999 MΩ0.001 MΩ
10.0…99.99 MΩ0.01 MΩ
100.0…999.9 MΩ0.1 MΩ
1000.0…2000.0 MΩ1 MΩ
500 V0.0…999.9 kΩ0.1 kΩ±3% m.v. +8 digits
1.000…9.999 MΩ0.001 MΩ
10.0…99.99 MΩ0.01 MΩ
100.0…999.9 MΩ0.1 MΩ
1000.0…5000.0 MΩ1 MΩ±4% m.v. +6 digits
1000 V0.0…999.9 kΩ0.1 kΩ±3% m.v. +8 digits
1.000…9.999 MΩ0.001 MΩ
10.0…99.99 MΩ0.01 MΩ
100.0…999.9 MΩ0.1 MΩ
1000.0…5000.0 MΩ1 MΩ±4% m.v. +6 digits
5.0…10.0 GΩ0.01 GΩ

"m.v." = measured value.

27003, Lugo, Spain C/ María Barbeito, 14Contact Contact T [+34] 982 20 99 20
27003, Lugo, Spaininfo@amperis.com | www.amperis.com

Continuity of protective and equipotential conductors

Measuring range according to EN 61557-4: 0.10…1999 Ω, with current >200 mA.

RangeResolutionAccuracy
0.00…19.99 Ω0.01 Ω±2% m.v. +3 digits
20.0…199.9 Ω0.1 Ω
200…1999 Ω1 Ω±4% m.v. +3 digits

Low-voltage circuit continuity and resistance — current <15 mA

RangeResolutionAccuracy
00.0…199.9 Ω0.1 Ω±3% m.v. +3 digits
200…1999 Ω1 Ω

Voltage on open terminals below 8 V in both tests. Acoustic signal and green LED when the resistance detected in the low-voltage test is below 30 Ω ± 50%. "m.v." = measured value.

Capacitance measurement

Capacitance value shown during the insulation resistance (RISO) measurement.

RangeResolutionAccuracy
1…999 nF1 nF±5% m.v. +5 digits
1.00…9.99 μF0.01 μF

DC and AC voltage measurement

RangeResolutionAccuracy
0.0…299.9 V0.1 V±2% m.v. +6 digits
300…600 V1 V±2% m.v. +2 digits

For test voltages below 100 V and measured resistances below 10 MΩ, the error of the measured capacitance is not specified. Frequency range: 45…65 Hz.

"m.v." = measured value.

Electrical safety and general specifications
Type of insulationDouble, according to EN 61010-1 and IEC 61557
Measurement categoryCAT IV 600 V according to EN 61010-1
Protection classIP67 according to EN 60529
Power supply4 alkaline batteries or Ni-MH battery set
Weight1 kg
Dimensions220 × 100 × 60 mm

Standard accessories: black K01 crocodile clip; 1.2 m red test lead; 1.2 m blue test lead; black pin probe with banana connector; red pin probe with banana connector; M6 carrying case; straps; handle to suspend the meter; calibration certificate; battery set. Optional accessories: 5 m red test lead; 5 m blue test lead; 5 m shielded black test lead; 1.2 m blue test lead; red K02 crocodile clip; black K01 crocodile clip; blue K02 crocodile clip; blue pin probe with banana connector; WS-04 adapter with universal Schuko.