Test voltage
50, 100, 250, 500 or 1000 V
Low voltage and resistance
0 to 1999 Ω, current <15 mA
Capacitance
1 nF to 9.99 μF
DC and AC voltage
0 to 600 V; 45…65 Hz
Safety
CAT IV 600 V; IP67
Dimensions and weight
220 × 100 × 60 mm; 1 kg

Which model do you need? Talk to an engineer

+34 982 20 99 20

ISO 9001 · ISO 14001 · ISO 45001

Pocket-sized insulation resistance meter with five test voltages up to 1000 V

Testing the insulation of low-voltage cables, motors and circuits only takes a 1000 V meter that applies the right test voltage to each circuit and, with the same instrument, verifies the continuity of protective conductors. The AMIC-10 tests at 50, 100, 250, 500 or 1000 V with ranges per EN 61557-2 reaching 10 GΩ at 1000 V and an accuracy of ±(3% m.v. + 8 digits), discharges the object automatically at the end and measures continuity with more than 200 mA per EN 61557-4, in an IP67 housing rated CAT IV 600 V.

AMIC-10 key data

  • Test voltages: the AMIC-10 applies 50, 100, 250, 500 or 1000 V, shows the actual test voltage throughout the measurement and is protected against accidentally measuring live objects.
  • Insulation ranges (EN 61557-2): 50 kΩ…250 MΩ at 50 V, 100 kΩ…500 MΩ at 100 V, 250 kΩ…2 GΩ at 250 V, 500 kΩ…5 GΩ at 500 V and 1 MΩ…10 GΩ at 1000 V.
  • Insulation accuracy: ±(3% m.v. + 8 digits) up to 999.9 MΩ and ±(4% m.v. + 6 digits) from 1 to 10 GΩ at 500 and 1000 V, with resolution from 0.1 kΩ.
  • Continuity of protective conductors: 0.10…1999 Ω per EN 61557-4 with a current >200 mA, ±(2% m.v. + 3 digits) up to 199.9 Ω and compensation of the test-lead resistance.
  • Low-current resistance: 0…1999 Ω with a current of 5 to 15 mA, ±(3% m.v. + 3 digits) and an acoustic warning with green LED below 30 Ω.
  • Capacitance and voltage: capacitance from 1 nF to 9.99 µF measured during the insulation test itself, and AC/DC voltage from 0 to 600 V (45…65 Hz) with ±(2% m.v. + 6 digits) up to 299.9 V.
  • Safety and format: double insulation per EN 61010-1, CAT IV 600 V, IP67 and 220 × 100 × 60 mm, powered by four AA alkaline batteries or Ni-MH rechargeables.

Advantages

Five test voltages

Insulation resistance at 50, 100, 250, 500 or 1000 V, with the actual test voltage shown throughout the measurement and protection against accidentally measuring live objects.

Three-wire measurement

Compensates the resistance of the test leads and keeps the voltage on open terminals below 8 V, with automatic discharge of the object's capacitance once the test ends.

More functions in the same meter

Continuity of protective conductors according to EN 61557-4, resistance of low-voltage circuits, capacitance during the insulation test and DC/AC voltage up to 600 V.

Signals during the test

Acoustic signal every five seconds to follow the elapsed time, and an acoustic warning with a green LED when the low-voltage resistance detected is below 30 Ω.

Pocket design, protected for the field

IP67, CAT IV 600 V measurement category and 1 kg weight, powered by alkaline batteries or a Ni-MH battery set.

Applications

  • Insulation testing of cables, motors and other low-voltage equipment.
  • Checking the protective and equipotential conductors of an installation.
  • Periodic maintenance of low-voltage electrical installations.
  • Continuity and resistance measurement of low-voltage circuits.

About the product

The meter runs on four AA alkaline batteries or a set of Ni-MH rechargeable batteries, with a low-battery indicator on the display, and meets double insulation according to EN 61010-1 and IEC 61557. At 220 × 100 × 60 mm and 1 kg, it is carried in an M6 case with straps and a handle, and comes as standard with a calibration certificate, test leads, probes and a crocodile clip. Optional accessories include 5 m shielded test leads, extra crocodile clips and a WS-04 adapter with a universal Schuko socket.

Technical specifications

Insulation resistance50 kΩ to 250 MΩ (50 V) up to 1 MΩ to 10.0 GΩ (1000 V), according to EN 61557-2
Test voltage50, 100, 250, 500 or 1000 V
Continuity0.10 to 1999 Ω, according to EN 61557-4, current >200 mA
Low voltage and resistance0 to 1999 Ω, current <15 mA
Capacitance1 nF to 9.99 μF
DC and AC voltage0 to 600 V; 45…65 Hz
Power supply4 AA alkaline batteries or Ni-MH battery set
SafetyCAT IV 600 V; IP67
Dimensions and weight220 × 100 × 60 mm; 1 kg
Insulation accuracy±(3% m.v. + 8 digits) up to 999.9 MΩ; ±(4% m.v. + 6 digits) from 1 to 10 GΩ (500 and 1000 V)
Continuity accuracy±(2% m.v. + 3 digits) from 0.00 to 199.9 Ω; ±(4% m.v. + 3 digits) from 200 to 1999 Ω
StandardsEN 61557-2, EN 61557-4; double insulation per EN 61010-1

Frequently asked questions

Up to what insulation resistance does the AMIC-10 measure at 500 V and at 1000 V?

At 500 V it measures from 500 kΩ to 5 GΩ and at 1000 V from 1 MΩ to 10 GΩ, per EN 61557-2. Accuracy is ±(3% m.v. + 8 digits) up to 999.9 MΩ and ±(4% m.v. + 6 digits) in the GΩ range.

Can the AMIC-10 test protective-conductor continuity per EN 61557-4?

Yes. It measures from 0.10 to 1999 Ω with a current above 200 mA, as EN 61557-4 requires, with ±(2% m.v. + 3 digits) accuracy up to 199.9 Ω and compensation of the test-lead resistance.

Which test voltages does it support?

50, 100, 250, 500 and 1000 V, each with its own insulation resistance range according to EN 61557-2.

Does it measure anything besides insulation resistance?

Yes: continuity of protective conductors, resistance of low-voltage circuits, capacitance, and DC and AC voltage up to 600 V.

What protection does it have for field work?

IP67 protection and CAT IV 600 V measurement category, weighing 1 kg, with an M6 carrying case.

What powers it?

Four AA alkaline batteries or a set of Ni-MH rechargeable batteries, with a low-battery indicator.

Videos

AMIC-10 (4:16)
AMIC-10: pocket insulation resistance meter, with five test voltages from 50 to 1000 V, up to 10 GΩ, and continuity of protective conductors at 200 mA, sealed to IP67. How it is connected for two-lead, three-lead and continuity tests, and where it fits next to the AMIC-30. Watch the video with its transcript

AI-generated video. The information must be validated by an Amperis engineer.

Downloads

PDFDownload the catalogue · AMIC-10: insulation resistance meter181 KB · EN Accessible version (HTML)
Electrical test instrument selector Tell us what you need to measure and on which installation —insulation, earth, loop, RCDs, micro-ohmmeter and other measurements— and get the instrument that covers your specification, with its standard accessories and the ones worth adding. You can send us the selection with the technical report attached. Open the selector and find my equipment Close the selector

Undecided between several models? Compare them side by side: Insulation resistance testers compared · Multifunction installation testers compared · Earth resistance testers compared · Loop impedance testers compared

More in 1 kV insulation testers for LV installations

See all →

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote