Loop impedance testers compared

Technical data of the 4 units of this type offered by Amperis, row by row. Tick «Compare» on two or three to see them side by side, copy the link or print the comparison.

Loop impedance testers compared
AMZC-304: loop impedance meter AMZC-305: loop impedance meter AMZC-306: loop impedance meter High Current Short Circuit Loop Impedance Meter AMZC-310S
Test currentMax. 13.3 A at 400 V; 7.6 A at 230 V (3 × 10 ms)High current, up to 30 AHigh current, up to 30 A4p: 150 A at 230 V, max. 280 A at 440 V; 2p: 23 A at 230 V, max. 42 A at 440 V
Measuring range0.13 – 1999 Ω (EN 61557); no-trip RCD mode: from 0.5 ΩZL-PE, ZL-N, ZL-L: 0.13 – 1999 Ω (IEC 61557); no-trip RCD mode: 0.43 – 1999 ΩZL-PE, ZL-N, ZL-L: 0.13 – 1999 Ω (IEC 61557); no-trip RCD mode: 0.43 – 1999 Ω4p: 7.2 – 1999 mΩ (IEC 61557); 2p: 0.13 – 199.9 Ω (1.2 m leads)
Resolution0.01 Ω0.01 Ω0.01 Ω0.1 mΩ (4p measurement)
Accuracy±(5 % rdg + 3 digits)±(5 % rdg + 3 digits) up to 19.99 Ω; ±(4 % rdg + 3 digits) above±(5 % rdg + 3 digits) up to 19.99 Ω; ±(4 % rdg + 3 digits) above4p: ±(2 % rdg + 2 mΩ); 2p: ±(2 % rdg + 3 digits) / ±(3 % rdg + 3 digits)
Voltage measurement0 – 500 V; networks 180 – 460 V; 45 – 65 Hz0 – 750 V (0.1 V resolution up to 250 V); networks from 110/190 V to 400/690 V (100 – 750 V); 45 – 65 Hz0 – 750 V (0.1 V resolution up to 250 V); networks from 110/190 V to 400/690 V (100 – 750 V); 45 – 65 Hz0 – 440 V True RMS, ±(2 % rdg + 2 digits); DC and 45 – 65 Hz; 220/380 V and 230/400 V networks
Other measurementsProspective short-circuit current 0.110 – 9999 A; R and X components; continuity ±200 mA (0.12 – 400 Ω); frequencyProspective short-circuit current; R and X components; PE touch electrode; overvoltage alarmProspective short-circuit current; R and X components; PE touch electrode; overvoltage alarmProspective short-circuit current (4p: 115 A – 32 kA at 230 V; 200 A – 55.7 kA at 400 V); R and X components; prospective touch voltage and shock voltage 0 – 100 V; frequency 45 – 65 Hz
Memory and communications990 results; Bluetooth990 cells (3500 records); USB990 cells (3500 records); USB990 results; RS-232 (USB with optional adapter)
Power supply4 AA batteries or NiMH rechargeables4 AA batteries or rechargeables; > 3000 measurements4 LR14 alkaline or NiMH cells; > 5000 measurements5 LR14 (C) alkaline batteries; ≥ 2000 measurements
Safety and protectionCAT IV 300 V (CAT III 600 V); IP67; double insulation; EN 61557CAT IV 600 V (CAT III 1000 V); IP54; double insulation (IEC 61010-1); IEC 61557CAT IV 600 V (CAT III 1000 V); IP54; double insulation (IEC 61010-1); IEC 61557CAT IV 300 V; IP20; double insulation (EN 61010-1); EN 61557
Dimensions and weight220 × 102 × 61 mm; 0.8 kg260 × 190 × 60 mm; 2.2 kg288 × 223 × 75 mm; 2 kgNot stated on the product page
View product →View product →View product →View product →

Data from the specifications table of each product page and, for units without a product page, from their technical documentation. Missing data is flagged.

Request a quote for these units

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote