Relay test sets compared

Technical data of the 3 units of this type offered by Amperis, row by row. Tick «Compare» on two or three to see them side by side, copy the link or print the comparison.

Relay test sets compared
AK-10: three-phase relay test set AK-30: three-phase relay test set AK-6: three-phase relay test set
ChannelsUp to 13: 6×20 A (3×40 A) / 7×130 VAK-30: 10 channels; AK-31: 13 channelsNot stated on the product page
Current outputs6×420 VA at 0 – 20 A; 3×520 VA at 0 – 40 A; 1×1000 VA at 0 – 120 A3×30 to 6×30 A; 450 – 850 VA (model dependent)3×35 A (L-N); 3×450 VA at 0 – 35 A
Voltage outputs7-phase AC (L-N): 7×0 – 130 V4×300 V/120 VA or 7×300 V/90 VA; 4×310 V/124 VA (AK-31)4×300 V (L-N); 4×110 VA at 0 – 300 V; 2×600 V (L-L)
ModelsAK1030/40/63/66 and AK1030i/40i/63i/66iAK3030i / AK3063i / AK3066i; AK3130i / AK3163iNot stated on the product page
StandardsNot stated on the product pageCompatible with IEC 61850Not stated on the product page
Accuracy0.14 % rd + 0.06 % rg guaranteed at 0 – 300 V and 0 – 30 ANot stated on the product pageVoltage accuracy: 0.07 % rd + 0.03 % rg guaranteed at 0 – 130 V
Frequency: 0 – 1000 Hz; resolution 0.001 Hz
Phase: -360° to +360°; accuracy < 0.2°
DC sourceNot stated on the product pageIndependent, usable simultaneously0 – 300 V / 180 W; 0 – 20 A / 300 W (60 A, 3 L-N)
TestsNot stated on the product pageCurrent, voltage, frequency, power, impedance, harmonics, distanceDC, AC, distance, harmonic and frequency
Control and designDesign: All-in-one; Windows CE, 4-inch TFT, mouse and keyboard
Control: Amplitude, frequency and phase independent and continuous
Configurations: Eight selectable output arrangements
Not stated on the product pageAll-in-one; Windows CE, 6.4-inch TFT, keyboard and rotary encoder
Connectivity and controlSeparate Ethernet port for PCSynchronisation: GPS-triggered end-to-end testing
Connectivity: PC control over RJ45 Ethernet; RIO / XRIO import/export
RJ45 Ethernet and USB for updates and data transfer
Safety and protectionNot stated on the product pageOverload, overheating, short/open circuit, wrong wiringWrong wiring, open/short circuit, overheat and overload
View product →View product →View product →

Data from the specifications table of each product page and, for units without a product page, from their technical documentation. Missing data is flagged.

Request a quote for these units

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote