| AE736A: SF6 gas servicing cart | AGRU-4: SF6 recovery equipment | Gas Filling Regulation Unit ARFU-2 SF6 | SF6 gas transfer unit AGTU | SF6 recovery system AGRU-8 series | |
|---|---|---|---|---|---|
| Flow rate | Not stated on the product page | Up to 2 m³/h | Not stated on the product page | Up to 1.2 CFM (2 m³/h) | Up to 51 kg/h |
| Recovery | Below 0.5 mbar; compression up to 50 bar | Down to 100 mbar; below 1 mbar with optional XDS stage | Not stated on the product page | Down to 100 mbar; optionally below 1 mbar with XDS module | Below 1 mbar |
| Vacuum | Below 0.0001 mbar | 17 m³/h; below 1 mbar | Vacuum pump: 10 CFM (17 m³/h) Sealed vacuum: Below 0.03 mbar | Not stated on the product page | 25 m³/h (below 1 mbar); optional 40 m³/h |
| Designed for | Not stated on the product page | Breakers and switchgear up to 69 kV | Not stated on the product page | Circuit breakers and SF6 equipment up to 69 kV | Circuit breakers and switchgear up to 256 kV |
| Filling | Not stated on the product page | Not stated on the product page | Valve: 3-way ball valve, evacuation/filling Filling: User-regulated through pressure regulator | Not stated on the product page | Not stated on the product page |
| Compressor | Oil-less, oil-free or oil-lubricated | Oil-less compressor, 1000:1, up to 34 bar | Not stated on the product page | Oil-less, direct-drive, 1000:1; up to 34 bar | Oil-less, direct drive, 1000:1, up to 69 bar |
| Filtration | Drying and filtering to 0.5 µm; absorption of decomposition products | 0.1 µm; removes moisture and decomposition products | Not stated on the product page | 0.1 micron on every recovery and re-pressurization cycle | Not stated on the product page |
| Storage | With or without on-board tank | On-board 22.7 kg tank; connection for external cylinders | Not stated on the product page | Not stated on the product page | Up to 160 kg in cylinders or 300 kg with optional tank |
| Control and design | Manual, PLC or optional HMI touchscreen | Not stated on the product page | Not stated on the product page | Not stated on the product page | Not stated on the product page |
| Format | Trailer, caster or skid; aluminium enclosure or tarpaulin sides | Not stated on the product page | Not stated on the product page | Not stated on the product page | Not stated on the product page |
| Power supply | All voltage and frequency combinations | 120 V, 1-phase, 60 Hz / 220 V, 1-phase, 50 – 60 Hz | 120 V AC, 60 Hz / 220 V AC, 50/60 Hz, single-phase | 120 V AC, 60 Hz / 220 V AC, 50/60 Hz, single-phase | 220 V, single-phase, 50/60 Hz |
| Dimensions and weight | Not stated on the product page | 1170 × 560 × 610 mm; 103 kg | Dimensions (H × W × D): 1500 × 600 × 400 mm Weight: 31 kg | Dimensions (H × W × D): 510 × 410 × 635 mm Weight: 34 kg | 1900 × 1140 × 1470 mm; 432 kg |
| View product → | View product → | View product → | View product → | View product → |