Transformer monitoring compared
Technical data of the 4 units of this type offered by Amperis, row by row. Tick «Compare» on two or three to see them side by side, copy the link or print the comparison.
| Dynamic Ratings B100 Electronic Temperature Monitor (ETM) | Dynamic Ratings C50 Bushing Monitor | Dynamic Ratings E3 Transformer Monitor | GRIDSCAN5000 hydrogen sensor | |
|---|---|---|---|---|
| Designed for | Electronic temperature monitor (ETM) for distribution, transmission and generation transformers; replaces up to 5 mechanical gauges; cooling control | Bushing and condition monitor for high-voltage transformers (bushings ≥ 69 kV): bushings, OLTC, cooling, partial discharge and dissolved gas | Continuous condition monitoring of power transformers: bushings, windings, OLTC, cooling, oil and insulation | Continuous measurement of hydrogen dissolved in the oil of power and distribution transformers; no calibration or consumables |
| Measured variables | Top-oil and tap-changer oil temperature; load current; hot spot of up to 3 windings (calculated); tap-changer Delta T | Power factor and capacitance of up to 6 bushings; top oil, ambient and load; hot spot and thermal ageing; OLTC: tap position, motor current and voltage, Delta T; cooling: fan/pump current, contactor, oil flow | Top oil, winding (fibre optic), insulation ageing Bushings: power factor and capacitance change, PD Harmonics, load profile and power factor, voltage; faults; GIC OLTC: tap counter, contact wear, motor Cooling, oil level, conservator, nitrogen pressure | H₂ 25 – 5000 ppm; accuracy ±20 % or ±25 ppm; repeatability ±10 % or ±15 ppm; response < 60 min; cross-sensitivity < 2 %; 1-year data log |
| Connectivity and control | DNP3, Modbus, IEC 61850; copper/fibre Ethernet, RS-485; USB; built-in web dashboard; optional communication over power wiring | DNP3, Modbus, IEC 61850; copper/fibre Ethernet, RS-232/RS-485; web dashboard | Multiple SCADA connections; USB; copper/fibre Ethernet; RS-232, RS-485 and serial fibre optic; e-mail notifications; built-in web pages | 2-wire RS-485; Modbus RTU and DNP3; 19,200 baud, 8N1 |
| Detected gases | Optional hydrogen and/or moisture sensor | Serial integration of external multi-gas DGA and moisture analysers | Key-gas and multi-gas DGA and moisture, via serial integration of external analysers | Dissolved hydrogen (H₂); mineral oil, silicone, natural and synthetic ester |
| Voltage and current inputs | 2 Pt100 RTDs; 3 current (CT) inputs for load; 1 digital input | Up to 6 bushing sensors (sum of currents or voltage reference); up to 15 PD channels (tap sensors, RFCT, Rogowski coils); optional winding fibre-optic probe | Up to 12 modules Digital inputs: 12 per module, 2.5 kV AC isolation Analog: 6 per module (2 AC current, 2 three-wire PT100 RTD, 2 DC 0 – 1 mA, 4 – 20 mA or 0 – 10 V) Fibre-optic hot-spot probes Multiport: OLTC motor current, dual CT, dual PT100 | Not stated on the product page |
| Outputs and alarms | 6 digital relays; 2 analog outputs; 1 system alarm relay; configurable alarm, trip and cooling | Staged cooling control; essential tap-changer voltage control | 8 form C contacts per module (NO/NC), 6 A @ 250 V AC / 6 A @ 30 V DC; 8 × 4 – 20 mA outputs (±0.2 %); common, major and minor alarms; cooling and voltage control | 4 – 20 mA with optional module |
| Standards | Not stated on the product page | Not stated on the product page | IEC 60664: overvoltage category II (power input) and I (digital inputs/outputs) | CE; FM 6520:2022 (liquid phase); RoHS 2011/65/EU; IEC 61010-1; IEC 61326; IEC 60529; IEC 60068 |
| Power supply | 48 – 240 V DC or 110 – 240 V AC, 50/60 Hz | 110 – 240 V DC or 110 – 250 V AC | 48 – 275 V DC; 60 – 265 V AC, 47 – 63 Hz; 50 W Auxiliary output 24 V DC (18 – 32 V), 0.5 A | 12 – 48 V DC; 10 W max. |
| Operating conditions | -40 – +70 °C; IP66/NEMA 4 | -40 – +70 °C | -40 – 80 °C; humidity up to 95 % non-condensing | Ambient -40 – 70 °C; oil -40 – 105 °C; IP68; C5M corrosion class; 30 g shock |
| Format | Cast-aluminium outdoor enclosure; 287 × 296 × 129 mm; M20/M25 cable entries; backlit LCD | DIN rail, panel or 19″ rack | Modular, 35 mm DIN rail; numbered pluggable terminals; modules 166.87 mm high × 50.80 or 76.20 mm wide × 105.66 mm deep | Sensor screwed into a tank valve, 3/4″-14 NPT thread; 4-wire M12 connector; 151 × 39.6 × 39.6 mm |
| View product → | View product → | View product → | View product → |
Data from the specifications table of each product page and, for units without a product page, from their technical documentation. Missing data is flagged.
Request a quote for these units