Transformer monitoring compared

Technical data of the 4 units of this type offered by Amperis, row by row. Tick «Compare» on two or three to see them side by side, copy the link or print the comparison.

Transformer monitoring compared
Dynamic Ratings B100 Electronic Temperature Monitor (ETM) Dynamic Ratings C50 Bushing Monitor Dynamic Ratings E3 Transformer Monitor GRIDSCAN5000 hydrogen sensor
Designed forElectronic temperature monitor (ETM) for distribution, transmission and generation transformers; replaces up to 5 mechanical gauges; cooling controlBushing and condition monitor for high-voltage transformers (bushings ≥ 69 kV): bushings, OLTC, cooling, partial discharge and dissolved gasContinuous condition monitoring of power transformers: bushings, windings, OLTC, cooling, oil and insulationContinuous measurement of hydrogen dissolved in the oil of power and distribution transformers; no calibration or consumables
Measured variablesTop-oil and tap-changer oil temperature; load current; hot spot of up to 3 windings (calculated); tap-changer Delta TPower factor and capacitance of up to 6 bushings; top oil, ambient and load; hot spot and thermal ageing; OLTC: tap position, motor current and voltage, Delta T; cooling: fan/pump current, contactor, oil flowTop oil, winding (fibre optic), insulation ageing
Bushings: power factor and capacitance change, PD
Harmonics, load profile and power factor, voltage; faults; GIC
OLTC: tap counter, contact wear, motor
Cooling, oil level, conservator, nitrogen pressure
H₂ 25 – 5000 ppm; accuracy ±20 % or ±25 ppm; repeatability ±10 % or ±15 ppm; response < 60 min; cross-sensitivity < 2 %; 1-year data log
Connectivity and controlDNP3, Modbus, IEC 61850; copper/fibre Ethernet, RS-485; USB; built-in web dashboard; optional communication over power wiringDNP3, Modbus, IEC 61850; copper/fibre Ethernet, RS-232/RS-485; web dashboardMultiple SCADA connections; USB; copper/fibre Ethernet; RS-232, RS-485 and serial fibre optic; e-mail notifications; built-in web pages2-wire RS-485; Modbus RTU and DNP3; 19,200 baud, 8N1
Detected gasesOptional hydrogen and/or moisture sensorSerial integration of external multi-gas DGA and moisture analysersKey-gas and multi-gas DGA and moisture, via serial integration of external analysersDissolved hydrogen (H₂); mineral oil, silicone, natural and synthetic ester
Voltage and current inputs2 Pt100 RTDs; 3 current (CT) inputs for load; 1 digital inputUp to 6 bushing sensors (sum of currents or voltage reference); up to 15 PD channels (tap sensors, RFCT, Rogowski coils); optional winding fibre-optic probeUp to 12 modules
Digital inputs: 12 per module, 2.5 kV AC isolation
Analog: 6 per module (2 AC current, 2 three-wire PT100 RTD, 2 DC 0 – 1 mA, 4 – 20 mA or 0 – 10 V)
Fibre-optic hot-spot probes
Multiport: OLTC motor current, dual CT, dual PT100
Not stated on the product page
Outputs and alarms6 digital relays; 2 analog outputs; 1 system alarm relay; configurable alarm, trip and coolingStaged cooling control; essential tap-changer voltage control8 form C contacts per module (NO/NC), 6 A @ 250 V AC / 6 A @ 30 V DC; 8 × 4 – 20 mA outputs (±0.2 %); common, major and minor alarms; cooling and voltage control4 – 20 mA with optional module
StandardsNot stated on the product pageNot stated on the product pageIEC 60664: overvoltage category II (power input) and I (digital inputs/outputs)CE; FM 6520:2022 (liquid phase); RoHS 2011/65/EU; IEC 61010-1; IEC 61326; IEC 60529; IEC 60068
Power supply48 – 240 V DC or 110 – 240 V AC, 50/60 Hz110 – 240 V DC or 110 – 250 V AC48 – 275 V DC; 60 – 265 V AC, 47 – 63 Hz; 50 W
Auxiliary output 24 V DC (18 – 32 V), 0.5 A
12 – 48 V DC; 10 W max.
Operating conditions-40 – +70 °C; IP66/NEMA 4-40 – +70 °C-40 – 80 °C; humidity up to 95 % non-condensingAmbient -40 – 70 °C; oil -40 – 105 °C; IP68; C5M corrosion class; 30 g shock
FormatCast-aluminium outdoor enclosure; 287 × 296 × 129 mm; M20/M25 cable entries; backlit LCDDIN rail, panel or 19″ rackModular, 35 mm DIN rail; numbered pluggable terminals; modules 166.87 mm high × 50.80 or 76.20 mm wide × 105.66 mm deepSensor screwed into a tank valve, 3/4″-14 NPT thread; 4-wire M12 connector; 151 × 39.6 × 39.6 mm
View product →View product →View product →View product →

Data from the specifications table of each product page and, for units without a product page, from their technical documentation. Missing data is flagged.

Request a quote for these units

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote