Advanced Performance Smart Power Meter
Accu-Measure™ Technology and Substation Data Acquisition Node
- 0.06% Billing Grade Power Metering • Billing Grade Revenue Meter
- RTU with I/O & Control
- Power Quality Recorder
Performance Power Quality Monitoring XML Web Server with Email Alarms
- Onboard Ethernet Connectivity
- DNP 3.0 Level 2 Plus
- Extensive Communication Capabilities
- Smart Grid and Automation Solutions
MV90 COMPATIBLE
Smart Grid and automated data collection solutions are the backbone of a modern power distribution system. From the residential metering point to the sophisticated transmission substation automation solutions, accurate and reliable data collection is critical to success. The advanced monitoring features of the Nexus® 1252 provide the total picture of power usage and power quality for any metered point within a power distribution network, allowing power related decisions to be made quickly and effectively. With EIG’s exclusive Total Web Solutions, you can monitor your Nexus® 1252 anytime and from anywhere via the Internet and receive critical alarms via email when action is required.
Technology Designed For Utilities, Industrial Users and Critical Power Applications
FOR ENERGY PROVIDERS
(Utilities, Municipals, ESPs, Independents, etc.)
- Improve Substation Automation Solutions
- Increase Power Distribution Reliability
- Record Faults/Time Protective Equipment
- Monitor Reliability of Breakers and Relays
- Shed or Shift Loads Quickly
Obtain High-End Power Quality and Accurate Billing Measurements
High-performance energy usage and power quality data is always available at your fingertips with the Nexus® 1252. The meter provides you with the necessary power system assessment information in real time. The Nexus® 1252 provides advanced power disturbance recording including EN50160/EN61000-4-15 Flicker Analysis and AI-based PQ reporting. Use Nexus®’ precision accuracy for primary metering or submetering for checking on an installed utility meter.
Expandable I/O and Trending Customize Nexus® For Every Application
- Identify and Manage Peak Demand
- Heighten Response Time to PQ Events
- Enhance Levels of Communication and Data Transmission
- Provide Real Time Data on the Web
FOR ENERGY CONSUMERS
(Industrial, Commercial, Government, Etc.)
- Real Time PQ Monitoring and Analysis
- Efficiently Control/Manage Energy Consumption
Nexus® offers virtually unlimited I/O capability in conjunction with all metering functions. Expandable I/Os enable the meter to be used for all metering and data-gathering applications. Nexus®’ modular plug-in design allows you to add analog and digital I/Os to specifically meet your application. With this advanced I/O capability, you can use Nexus® to replace RTUs and PLCs for energy management and substation automation solutions. With Nexus®, you can monitor system apparatus reliability such as transformers, circuit breakers, or other critical equipment.
- Reduce Costs/Conserve Energy
- Improve Operational Efficiencies
- Increase Productivity/Reduce Downtime
- Optimize Loads/Extend Equipment Life
- Identify and Respond to PQ Events Quickly
- Avoid High Utility Penalties for Exceeding Usage
- View Energy Usage and Power Quality through the Web
Auto-Calibrating Revenue Metering Technology
Accu-Measure™Technology
Multi-Part Approach To Precision In Accuracy
- Multipoint Phase Angle Compensation
- Better than 0.01% Resolution
The Nexus® 1252 is the first meter of its kind to utilize EIG’s patented Accu-measure™ Technology. Accu-measure™ is a technique based on a multi-part approach that allows a fieldmounted metering device to achieve laboratory grade accuracy.
TIME OF USE CAPABILITY
Nexus® offers comprehensive time of use capability. Standard features include:
- Bidirectional Consumption
- and Demand Quantities
- 20 Year Calendar
DUAL HIGH POWERED 16 BIT A/D CONVERTERS
- 4 Seasons/Yr
- 12 Holidays/Yr
Dual 16 Bit A/D converters provide supreme sampling accuracy and resolution.
- 4 TOU Schedules/Season
- Prior Month, Prior Season Storage
- Present Month, Present Season Storage
DUAL INTERNAL REFERENCES STABLE TO 5 PPM/CELSIUS
MAX/MIN INTEGRATION AND RECORDING
The unit auto-adjusts to dual internal references stable to 5 parts per million. These references insure that the monitoring equipment maintains its calibration.
The unit offers time stamped max and min values for almost all measured readings. A time stamp is associated with each max and min. KW readings are integrated using:
AUTO-CALIBRATION WITH TEMPERATURE COMPENSATION
- Block (Fixed) Window
- Thermal Window
- Rolling (Sliding) Window
The Nexus® uses an auto-calibration technique that re-calibrates the unit on the fly when the temperature changes more than 5 degrees Celsius, monitoring for accuracy over temperature.
- Predictive Window. Any integration period is allowed. The default period is 15 minutes.
COINCIDENTAL READINGS
PRECISION ACCURACY SPECIFICATIONS
When logging max Watt readings, the coincidental VARs at the time of the max are also recorded. You can determine the number of capacitors needed, identify peak inefficiencies and resolve many other issues.
With Accu-measure™, this unit meets ANSI C-12 0.2% accuracy specifications watt-hour accuracy.
Revenue Metering Features
TRANSFORMER LOSS AND LINE LOSS COMPENSATION
PASSWORD PROTECTION PREVENTS UNAUTHORIZED
TAMPERING
The unit compensates for transformer and line losses. Power reading compensation is conducted for both iron and copper losses.
Two 10-character, alphanumeric passwords protect the unit from unauthorized tampering. The first level password is a general password allowing a user to view readings, but not change them. The second level password allows the user to change and re-program the unit.
CT AND PT COMPENSATION
The Nexus® unit compensates for errors in current transformers and potential transformers.
LOAD AGGREGATION/UNIVERSAL METERING
Using the status inputs, Nexus® has the ability to count pulses and aggregate different loads providing a total picture of the load and its component parts. The pulse inputs can be used to accumulate and aggregate all other utility values such as water and gas.
- 8 pulse inputs standard
- 4 aggregators
- 32 additional external pulse inputs
- Voltage Compensation
- Multipoint Current Compensation
Detailed Power Quality Recording
16 BIT WAVEFORM EVENT AND FAULT RECORDER
The unit records up to 512 samples per cycle for a Power Qualtiy event. Voltages and currents are recorded with preand post-event analysis. Fault recording offers 8x full scale capture capability on current. All voltage and current readings are recorded using a 16 bit A/D converter providing precise waveform resolution. Both hardware and software triggers are available to activate a waveform recording, which can be used for power quality surveys, fault analysis, breaker timing, etc.
MEASURE AND RECORD HARMONIC
MAGNITUDES TO THE 255TH ORDER
The unit measures harmonic magnitudes up to the 255th order for each voltage and current channel. Real Time Harmonics are resolved to the 128th order. Percent THD and K-Factor are also calculated. This high performance harmonic analysis allows users to conduct power quality analysis at the high end of the harmonic spectrum.
SUBCYCLE TRANSIENT RECORDER
The unit records subcycle transients on voltage and current readings. It monitors switching noise from capacitors, static transfer switches, SCRs and many other “power quality harmful” devices. Transients are often the cause of intermittent and expensive periods of downtime. Without Nexus, solving these problems is often impossible.
STATUS INPUT TRIGGERS
The unit records the waveform at the time of the status change. The input change and waveform recording are time stamped to a 1msec resolution. Up to 8 inputs can be plotted on the waveform. This enables a user to time the reliability of relays and circuit breakers.
ADDITIONAL INPUTS
Nexus® offers inputs for Neutral to Ground Voltage measurements. This allows you to analyze rising ground potential which often damages electrical equipment. The unit also calculates and measures the neutral current.
16 Bit Waveform Resolution
INDEPENDENT ITIC/CBEMA LOG PLOTTING
The Nexus® stores an independent ITIC/ CBEMA Log for magnitude and duration of voltage events. With this log, the user can quickly view total surges, total sags and average duration without having to retrieve waveform information.
PHASOR ANALYSIS
The monitor reads a phase angle analysis between the voltage and current channels, allowing for efficiency and system-integrity analysis.
ITIC/CBEMA Plotting showing damaging Power Quality events.
Advanced Reporting and Analysis
EN50160/EN61000-4-15 FLICKER AND COMPLIANCE MONITORING (V-2 ONLY)
It is important to maintain a source of high quality power to insure efficient operations. One particular source of disturbance that can have very negative effects is Flicker. This consists of low frequency to intermittent line disturbances on the power line. Aside from effects on equipment, disturbances of this type can have negative effects on people.
One particular example of this is the flickering of light sources that can affect humans in different ways, depending on the severity.
The Nexus® 1252 with V-Switch 2 complies fully with the Flicker requirements of EN50160 /EN61000-4-15 and includes:
- Flicker Evaluation-Instantaneous readings suitable for on line monitoring; Short Term Readings (PST - 10 Min) - logging and monitoring; Long Term Readings (PLT - 4 hour) - logging and monitoring
- Polling Pinst, Pst, Pst Max, Pst Min, Plt, Plt Max, Plt Min values
- Log Viewer (View graphed values Pst and Plt for Va, Vb and Vc or displayed values including Max and Min.)
INTERHARMONIC ANALYSIS
The Nexus® 1252 provides users with the ability to view Interharmonics, the discrete frequencies that lie between the harmonics of the power frequency voltage and current. Frequencies can now be observed which are not an integer multiple of the fundamental and can appear as discrete frequencies or as a wide-band spectrum.
The user can set a starting point anywhere in the waveform, assuming that there are enough sample points available after the starting point. If there are not enough points in this waveform capture, the software will check the next waveform record(s) stored in the database. If it is contiguous, additional points up to 200ms will be retrieved for analysis.
AIREPORTS EXT – PQ ANALYSIS
events.
- Uses Artificial Intelligence
- Evaluates All Data from Nexus® Meters
- Rates Events for Severity
- Identifies Probable Causes
- Identifies Possible Impact
- Recommends Corrective Actions or Solutions
- Prepares & Formats Reports of All Power Quality Events
- PQDIF File Format Converter allows Nexus® data to be read by standard EPRI Power Quality viewing software.
- COMTRADE File Converter changes fault records to standard fault analysis file formats.
Measure amplitudes and timing with millisecond resolution. See system reliability events that lasted for several seconds.
Total Web Solutions
Total Web Solutions— Providing Advanced Metering Data Integration With the Web
Total Web Solutions is an advanced Ethernet communication architecture allowing you to custom design web pages, display metering data and host your meter power information web site directly on a Nexus® meter. The Nexus® meter directly hosts the web data without any need for dedicated server software, ActiveX Controls or Java Applets. The meter does the data collection, the formatting and the page hosting. Additionally, this solution is very Information Technology Department friendly because it creates almost no network traffic and provides all formatted data through an HTTP interface without resident client software.
ADVANCED FEATURES INCLUDE:
- Fully Customizable Web Page Development
- Direct Web Page Hosting With Live Readings
- Multiple Meter Hosting On One Page
- Read Direct From Meters (No Server Software Needed)
- No Active Controls Or Java Downloads
- IT Dept Friendly. Works Through Firewalls; Low-Cost/High Functionality
- Instant Alarm Emails – Direct from the Meter
WEBEXPLORER
(Directly Host Metering Data)
EIG’s WebExplorer provides you with direct access to all power data through Internet Explorer without needing to download ActiveX Controls or Java Applets. Because it is a standard HTML web page to an IT department, it works directly through corporate firewalls. WebExplorer is fully programmable so you can customize your own SCADA quality web pages, graphics and configurations.
- Easily Incorporated Into Any Existing Web Applications
- Fully Programmable Web Page Generator
- Brings in Direct XML Links, customizing many meters onto one page
- Quick Page Upload Time
- Easily Passes Through Firewalls
- No ActiveX Controls or Java Applets Downloaded to Client
WEBXML
Creates Real Time Data in XML Format. WebXML allows the Nexus® meter to gather data from the Nexus® Host or through other meters and put the data directly into an XML format. This allows you to share data through the web to multiple applications and
EIG’s WebAlarm sends real time email alerts via the Internet to up to 9 recipients simultaneously for any combination of event notifications. With WebAlarm, you can easily program the type of email format for the alert:
either short format for cell phones with text messaging service or long format that will provide detailed alarm conditions for any devices with full email support (computers, PDAs, cell phones).
create custom web pages, using Web Explorer. WebXML technology is easy to configure and extremely flexible. With WebXML, your data is instantly available to a host of software applications including Internet Explorer, Excel, Power Point and Word.
- Real Time Alerts
- Simultaneous
Emails to Multiple Recipients
- Update Users on Virtually Any Abnormality
- XML Support
- Uses Standard SMTP – Just Assign Email Addresses
- Shows the Last 10 Emails on Web Site for Later Investigation
- Automatically Process and Present Data In Readable Format
- Add Scale Factors, Multipliers or Any Other Desired HTML
- Capability
WEBMOD
(Open Architecture 3rd Party Integration)
- Display Data from Host Meter and/or Any Other Meter Using Modbus RTU or TCP/IP (WebReacher)
The 10/100BaseT design allows the unit to speak with 12 simultaneous sockets of Modbus TCP. Once the card is placed inside the Nexus®, Port 2 becomes a gateway enabling other Modbus based IED equipment to be interfaced to the network LAN, thus allowing multiple requests to receive data simultaneously.
- Customized Programming for Data Collection
- Easily Viewed by Different Applications
- Modbus Data Concentrator
WEBREACHER
With EIG’s exclusive WebReacher technology, you can now access remote meters around the world, retrieve data and consolidate it onto one web page or web site without any separate software SCADA package or client-side ActiveX Controls or Java Applets.
EIG’s WebMod features Modbus TCP open protocol that can be easily integrated with most other software or hardware. And, with the built-in Modbus data concentrator, you can poll up to 8 devices or 512 unique polling items from any device that can speak Modbus RTU and/or Modbus TCP protocols.
WEBDNP
- No Additional Application Software Costs
Using this feature, you can gain access to the meter speaking native DNP over Ethernet. This allows the unit to open an exclusive network socket for DNP 3.0. Using this unique technology, all other meter web features are available simultaneously. Even with DNP 3.0 over the Ethernet, you still have access to multiple Modbus socket, email alarms and many other communication features.
- No Server System Required
- No Complex Integration
- No ActiveX Controls or Java Applets on Client
- No Costly Point Charges (Up to 32 Devices)
WebAlarm
Extensive Onboard Mass Memory Securely Records All Data
| Log Storage Options | Standard RAM | Typical Log Size | Advanced RAM | Typical Log Size |
|---|---|---|---|---|
| Historical Log 1 | 256K | 85 Days | 1664K | 555 Days |
| Historical Log 2 | 400K | 133 Days | 400K | 133 Days |
| Out of Limit | 96K | 1024 Events | 96K | 1024 Events |
| ITIC/CBEMA/PQ Log | 64K | 512 Events | 64K | 512 Events |
| Relay Output Log | 48K | 256 Events | 48K | 256 Events |
| Input Status Log | 48K | 1024 Events | 48K | 1024 Events |
| # of Waveform Events | 1040K | 63 Events | 1568K | 95 Events |
| Flicker Log | 48K | 1536 Events | 160K | 5120 Days |
| System Event Log | 16K | 1024 Events | 16K | 1024 Events |
| TOU Recording | 128K | 20 Years | 128K | 20 Years |
Multiple Programmable Memory Logs
Nexus® utilizes two separate logs of historical information. In addition to all power parameters, the historical logs allow users to trend data from Electro Industries’ remote I/O devices. Furthermore, circuit breaker pressure, transformer temperature or any other analog or digital parameter can be monitored. You can conduct preventative maintenance on critical equipment as well as power analysis.
PRIMARY HISTORICAL TRENDING LOG FILE — LOG 1
Log any measured parameter from either the main unit or any of the option modules. Either 8, 16, 32 or 64 values can be logged per programmable interval.
EVENT-TRIGGERED WAVEFORM RECORDING LOG
Nexus® stores a separate ITIC/CBEMA log that records magnitude and duration of voltage clock resolution, the logs can be combined with different metered points through a distribution system to provide an accurate system-wide depiction of a power disturbance.
SECONDARY HISTORICAL
Nexus® records waveforms with a resolution of up to 512 samples per cycle. The amount of waveform recording is based on the amount of memory installed.
TRENDING LOG FILE — LOG 2
This log can be set up as an additional historical interval log or as an exclusive energy log. Either 8, 16, 32 or 64 values can be logged per interval.
The unit records the waveform when a value goes out of limit and when the value returns to normal. All information is time stamped to the nearest 1msec. The 8 onboard high-speed inputs can be tied to the waveform recording. You can record when the breaker tripped as compared to when the relay activated. This is very useful for fault and breaker integrity analysis.
RELAY OUTPUT LOG
The unit records when a relay output from the external I/O is activated, timestamps the event and provides a reason why the relay changed status.
OUT OF LIMIT LOG
The unit offers an independent out of limit log. This allows a user to download out of limit information to obtain a sequence of events for any occurrence. Utilizing the 1msec clock resolution, the logs can be combined with different metered points through a distribution system to provide an accurate system-wide depiction of a power disturbance.
INPUT STATUS LOG
This log is similar to the Relay Output Log in that it allows the user to record when inputs change status.
The unit can be programmed to take more than one recording every time an event occurs. Thousands of cycles can be recorded per event.
UPLOADABLE FLASH MEMORY
Nexus® utilizes uploadable flash memory technology on all processors and DSPs located in the unit. This insures that the unit can be upgraded without removing it from service.
| Samples | Number of Cycles | Max. Number of Cycles † | Number of |
|---|---|---|---|
| Per Cycle | Recorded Per Screen* | Recorded Per Event† | Channels |
| 16 | 8 Pre / 56 Post Event Screen | 6080 | 7 |
| 32 | 4 Pre / 28 Post Event Screen | 3040 | 7 |
| 64 | 4 Pre / 12 Post Event Screen | 1520 | 7 |
| 128 | 1 Pre / 7 Post Event Screen | 760 | 7 |
| 256 | 1 Pre / 3 Post Event Screen | 760 | 3 |
| 512 | 1 Pre / 3 Post Event Screen | 760 | 1 |
* Calculations at 60Hz
† Maximum using Advanced Memory
ITIC/CBEMA LOG
Expandable External I/O • RTU Capability • ElectroLogic™ Control
Use Nexus® As an RTU
Electro Industries offers multiple Analog and Digital I/O modules that mount externally to the Nexus®. The unit supports up to 4 I/O modules using internal power. An additional power supply extends I/O capability.
The master port of the Nexus® eliminates the need for RTUs in many substation applications. The Nexus® can poll different I/O devices, log data and send data to a master station via Modbus or DNP 3.0 protocol. This I/O functionality is available in the Nexus® at much lower costs than traditional substation RTUs.
ELECTROLOGIC™ — PROGRAMMABLE LOGICAL PROTECTION AND CONTROL
The Nexus® power monitor provides advanced logic and control on programmable limit settings. The 7000 values that the monitor measures can have limits and logic set to trigger operations. This feature allows a user to configure the Nexus® to be used as a control device for many applications such as:
Using the graphical array, each tier configures to the desired logical scheme enabling the Nexus® to address complex control requirements. The Nexus® ElectroLogic™ control can be extended for a virtually unlimited number of relay outputs. Simply extend additional I/O modules. Response time is typically less than 200 msec per I/O module, extendible to multiple seconds.
- Capacitor Control
- Load Shedding
- Automatic Transfer Schemes
- Transformer Monitoring & Control
- Redundant Protection (Not designed for Primary Over-Current Protection)
- Many Other Control Functions
GRAPHICAL PROGRAMMING INTERFACE FOR RELAYING AND CONTROL
EIG’s unique ElectroLogic™ structure allows users to develop up to 3 tiers of logic control based on limits and status conditions. All data is displayed in a graphical tree structure. The user can set logical descriptors, such as:
- AND/NAND/XAND Gates
Graphical 3 Tier Programming Interface
- OR/ NOR/XOR Gates
- Hysteresis/NHysteresis Control
Superior Construction and Isolation
This unit is a rugged, durable device. It provides considerable protection and isolation from damaging outside forces.
CASE CONSTRUCTION
The unit is mounted in a shielded metal case. It is resistant to contamination from harmful dust, sand or other matter. All screws and hardware are stainless steel.
POWER SUPPLY
The power supply offers both MOV protection and active line filtering to reduce any damaging occurrences to the supply.
VOLTAGE INPUTS
The voltage inputs are optically isolated. Issues such as noisy grounds, switching noise, SWC or any other such problems pose no threat to Nexus®.
CURRENT INPUTS
COMMUNICATION PORTS
All communication ports are isolated from the main unit and additionally isolated from each other. This avoids dangerous ground loops. I/O MODULES
The current inputs are direct shorts. They offer a stud input U-Bolt design with an internal toroidal sensor. Since this is a 0.15" thick solid brass U-Bolt without solder or weld joints, the unit’s current input and surge withstand capability is significant.
Each I/O module is isolated from the main unit and from other I/O modules. No signal entering an I/O module can damage any other part of the Nexus®.
Onboard Communication for Every Application
Robust Communication For Every Option
4 ISOLATED HIGH-SPEED COMMUNICATION PORTS
HIGH-SPEED TRANSDUCER OUTPUTS FOR CONTROL PURPOSES
INDUSTRY LEADING DNP 3.0 LEVEL 2 PLUS
The Nexus® 1252 provides the industry’s most advanced DNP 3.0 protocol implementations. EIG’s Nexus® 1252 complies with all DNP Level 1 and Level 2 certification requirements PLUS a host of additional features including:
Nexus® offers 4 built-in identical communication ports. Each port speaks any desired protocol. Standard protocols include Modbus RTU/ASCII and DNP 3.0 Level 2. Logs and Waveform events are available in Modbus format. Port 3 and Port 4 can be used as a Modbus master for I/O modules.
Nexus® offers 200 msec updates for all instantaneous readings. The unit can be a highspeed control transducer for power generation, transmission line synchronization and any other synchronizing and control scheme.
- Up to 136 measurements (64 Binary Inputs, 8 Binary Counters, 64 Analog Inputs) can be mapped to DNP Static points in the customizable DNP Point map.
Additional Capabilities 8 BUILT-IN DIGITAL HIGH-SPEED STATUS INPUTS
SYNC. CHECK-AUX. VOLT INPUT
The unit has a high-speed Vaux input. This input can be used for multiple purposes
- Neutral to Ground
- Up to 16 relays and 8 resets can be controlled through DNP.
These inputs automatically sense whether the circuit is externally wetted. If externally wetted, the input will accept up to 300VDC. If internally wetted, the unit supplies the needed voltage for the desired control application.
- Voltage Readings
- Synchronizing Schemes
- Report-by-exception processing (DNP Events) deadbands can be set on a per-point basis.
The Vaux channel can be used to get the frequency, magnitude and phase angle on both sides of a switch or between generator and bus voltage.
- 250 events of combinations of four events (Binary Input Change, Frozen Counter, Counter Change, Analog Change).
- Freeze Commands: Freeze, Freeze/ No-Ack, Freeze with Time, Freeze with Time/No-Ack.
MULTIPLE COMMUNICATION PATHS
(ONE EXAMPLE SHOWN BELOW)
- Freeze with Time command enables the Nexus® meter to have internal time driven Frozen Counter and Frozen Counter Event data. When the Nexus® meter receives the Time and Interval, the data will be created.
- Third party certification is available.
Optional On-board Modem with Dial-Out
DIAL-OUT ON ALARM
With the built-in optional INP2 modem, the meter has dial-out capabilities that detect when an alarm occurs and dials out to provide notification. The Nexus® 1252 dials to EIG Dial-In Server EXT, which allows users to be paged or e-mailed with notifications of events.
DIAL-OUT FOR OTHER EVENTS
The meter will dial out for the following circumstances:
- Limits Status Change
- High Speed Input Change
- Waveform Record Capture
- CBEMA Power Quality Event
- Control Output Change
- Filling of Meter Memory
- Cycling of Control Power
- Password Failure on a Call coming into the Modem
- Meter Communication Failure
DIAL-IN SERVER EXT* CAPABILITIES
The EIG Dial-In Server EXT* will record all notifications, accept downloads from the meter and allows users to be notified by email and paging automatically. Features of Dial-In Server EXT include:
Dial-In Settings
- Unlimited Meters
EMAIL/PAGING FEATURE
- Scalable Multi-Server Architecture
Once the software detects a call, Communicator EXT launches the Dial-Out feature, immediately alerting those designated users via:
- Email Notification
- Paging Notification
- Audible System Alarm
- Email (PC, PDA, Cell)
- * Dial-In Server EXT is an add-on software component to Communicator EXT.
- Pager
- Many Users Can Be Contacted Simultaneously
Improve Reliability with Substation System Equipment Monitoring
Nexus® allows you to monitor the health and status of critical substation equipment such as transformer and circuit breakers. This insures the user that the electrical distribution infrastructure is sound and reliable.
TRANSFORMER MONITORING
- Measure Voltage, Current,
- Power and PF
- Limit on VA Ratings
- Data trend and /or alarm transformer temperature
- Log ambient temperature
- Monitor TAP position
CIRCUIT BREAKER MONITORING
- Record Faults
- Monitor Operations of Delays and Breakers
- Record Fault events with millisecond timing
- Count operations
- Calculate accumulated 12T on Contacts
Display & External I/O Options
P60N Graphical LCD Display
P60N Touch-Screen LCD for a graphical data presentation. 320 x 240 pixels, CCFL Backlight. See P60N Datasheet for details. Up to 8 Meters per display.
P40N+ Series Multifunction LEDDisplays
P41N+ Amp Display Slave
P43N+ Watt/VAR/PF Display Slave
Multifunction/Master
Amps Slave
Watt/VAR/PF Slave
Analog Transducer Signal Inputs
- 8AI1
- 8 Analog Inputs, 0-1mA, bidirectional
- 8AI2
- 8 Analog Inputs, 0-20mA, bidirectional
8AI3 8 Analog Inputs, 0-5V DC, bidirectional 8AI4 8 Analog Inputs, 0-10V DC, bidirectional WIRING: Common Mode ACCURACY: 0.25% of Full Scale SCALING: Programmable
ORDERING SPECIFICS: Up to 4 modules can be used
Digital Dry Contact Relay Outputs
4RO1 4 Relay Outputs, 5 Amps, 125V AC/DC, Form C
ORDERING SPECIFICS: Up to 4 modules can be used
Digital Solid State Pulse Outputs
4PO1
4 Solid State Pulse Outputs, Form A or C KYZ Pulses
MAXIMUM 20 pulses per second PULSE SPEED:
ORDERING SPECIFICS: Up to 4 modules can be used
Digital Inputs
8DI18 Digital Status Inputs Wet/Dry
Auto-Detect Up to 300 Volts DC
Analog Transducer Signal Outputs
1MAON4 4 Analog Outputs, 0–1mA, self-powered, scalable, bidirectional
1MAON8 8 Analog Outputs, 0–1mA, self-powered, scalable, bidirectional 20MAON4 4 Analog Outputs, 4–20mA, self-powered, scalable
20MAON8 8 Analog Outputs, 4–20mA, self-powered, scalable WIRING: Common Mode ACCURACY: 0.1% of Full Scale CALIBRATION: Self-Calibrating SCALING: Programmable ORDERING SPECIFICS: Up to 4 Analog Output modules can be used with each Nexus®.
Stackable I/O Module Design
Additional I/O Accessories
PSIO
Additional power supply for up to 4 additional I/O modules. This additional accessory may be needed when using 3 or more displays and/or modules.
MBIO Mounting bracket for I/O modules
The Nexus® meter supports every wiring and configuration. It configures easily for 2, 21/2 or 3 element. All wiring and hookup configurations are software configured.
Nexus® P60N Touch-Screen Display
Specifications
INPUT VOLTAGE RANGE
- 150 Volt PH-N, 300V PH-PH (Suffix-120) (Used with PTs for Extended Range)
- 300 Volt PH-N, 600 Volt PH-PH (Suffix-G) Voltage Input Withstand Capability
- VOLTAGE INPUT WITHSTAND CAPABILITY
- Voltage Inputs optically isolated to 2500V DC. Meets ANSI C37.90.1 (Surge Withstand Capability)
INPUT CURRENT RANGE
- 5 Amp Inputs 2x continuous programmable to any CT range
- Fault Current recording to 60 Amps peak secondary based on 5 Amp full scale. Note: 1 Amp and 0.25 amp current inputs available as special order.
- CURRENT INPUT WITHSTAND CAPABILITY (AT 23°C)
- 100 Amps for 10 Seconds
- 300 Amps for 3 Seconds
- 500 Amps for 1 Second
- Continuous Withstand Rating: 20 Amps
BURDEN
- Voltage Inputs: 0.05VA@120V rms
- Current Inputs: 0.002VA@5A rms
ISOLATION
All inputs and outputs are isolated to 2500 Volts. All Com Ports are additionally isolated from each other.
TEMPERATURE RATING
- Operating Temperature: (-40 to +70)°C
- P60N Display 0-50 °C
- Humidity: Up to 95% Non-condensing
- SENSING METHOD
- Up to 512 Samples per Cycle
- (Programmable)
- 16 Bit A/D Resolution – Dual Converters
- Accu-measure™ Auto-Calibration Technology
- True RMS
- ACCURACY RATING
- This unit complies with ANSI C12.20 and IEC687 accuracy requirements.
- UPDATE TIME
- 200 msec — High Speed Readings
- 1 Second — Revenue Accurate Reading
- CONTROL POWER REQUIREMENTS
- 120V AC/DC (-20%) - 230V AC (+20%) (Suffix -D2)
- 24V DC (-20%) - 48V DC (+20%) (Suffix -D)
- Burden: 20 VA Max
- FREQUENCY RANGE
- Fundamental 20– 65 Hz
- COMMUNICATION FORMAT
- Programmable parity and stop bits
- Communication Protocols: Modbus TCP/IP ASCII/RTU and DNP 3.0 Level 2 Plus
- 4 Communication ports, 2 slave ports,
2 selectable master/slave ports
- All ports use 2-wire RS485 communication; Port 1 is RS232 or RS485 Selectable
- INP2 - 56k Modem with Dial-Out Capability
- INP200 - Total Web Solutions - 10/100BaseT CONSTRUCTION
Constructed in a metal case. All screws are stainless steel.
SHIPPING
Total shipping weight: approx. 5 lbs (2.2 kgs) Shipping container dimensions: 14" x10" x6" (35.6cm x 25.4cm x 15.2cm)
Displays and I/O modules ship in separate containers.
COMPLIANCE
- ANSI C12.20 Class 0.2 and IEC687 (Accuracy)
- ANSI C37.90.1 (Surge Withstand)
- ANSI C62.41 (Surge)
- ANSI/IEEE C37.90.1 – Surge Withstand
- IEC 1000-4-2 – ESD
- IEC 1000-4-3 – Radiated Immunity
- IEC 1000-4-4 – Fast Transient
- IEC 1000-4-5 – Surge Immunity
- IEC 61000-4-15 – Flicker Meter
- IEC 61000-4-30 – Power Quality
- Contact factory on specifics of compliance
- MEASUREMENT METHODS
- CE Marked
- UL and cUL Listed
Measurement Accuracy (% of Reading)
| PARAMETER | 200 MILLISECOND * | 1 SECOND* | DISPLAY RESOLUTION |
|---|---|---|---|
| Voltage (L-N) | 0.1% | 0.05% | 5 Digit |
| Voltage (L-L) | 0.1% | 0.05% | 5 Digit |
| Current | 0.1% | 0.025% | 5 Digit |
| Frequency | 0.03 Hz | 0.01 Hz | 00.001 Hz |
| KW @ Unity PF | 0.1% | 0.06% | 5 Digit |
| KW @ .5 PF | 0.1% | 0.1% | 5 Digit |
| KVA | 0.1% | 0.08% | 5 Digit |
| VAR | 0.1% | 0.08% | 5 Digit |
| PF | 0.1% | 0.08% | 3 Digit |
| Harmonics | N/A | 0.2% | 3 Digit |
| KW/Hours | N/A | 0.04% | 16 Digit |
| KVA/Hours | N/A | 0.08% | 16 Digit |
| KVAR/Hours | N/A | 0.08 | 16 Digit |
To order a Nexus® 1252:
Example:
- 1. Fill out the options desired on the order chart below. List accessories separately.
OPTIONS:
ACCESSORIES:
Nexus®1252-A-120-D2-60Hz-INP200-P40N+ - 1mAON4-8AI1-MBIO-COMEXT3.1C
- 2. Specify display type and number.
- 3. Specify desired I/O modules and mounting bracket(s).
- 4. Specify Communicator EXT 3.0.
- 5. If you provide CT and PT ratios and wiring, EIG will program the units at the factory.
This equates to a Nexus® 1252 Monitor with advanced memory, an operating voltage of 120, a 90-276 Volts AC/DC power supply, a 60Hz frequency, an internal 10/100BaseT Ethernet port, a multifunction LED display, a 0-1mA output module with an analog input module, mounting bracket and one site license for Communicator EXT 3.0 software.
Ordering Specifications
Accessory Options
DISPLAYS
P60NGraphical LCD Touch-Screen Display P40N+Multi-Function LED Display/Master P41N+Amp Display Slave P43N+Watt/VAR/PF Display Slave
PSIOPower Supply for Additional IO modules MBIO I/O Mounting Bracket (must be ordered with purchase of I/O module)
SOFTWARE
I/O MODULES
1mAON44 Analog Outputs, 0–1mA 1mAON88 Analog Outputs, 0–1mA 20mAON44 Analog Outputs, 4–20mA 20mAON88 Analog Outputs, 4–20mA 8AI18 Analog Inputs, 0–1mA 8AI28 Analog Inputs, 0–20mA 8AI3 8 Analog Inputs, 0–5V DC 8AI4 8 Analog Inputs, 0–10V DC 4RO14 Relay Outputs 4PO14 Solid State Pulse Outputs 8DI18 Digital Status Inputs
COMEXT3.1CCommunicator EXT 3.0 for Windows® Single-Computer License (One Site) COMEXT3.MC Communicator EXT 3.0 for Windows® Multiple-Computer License (One Site) AIEXT.1C AiReports EXT Power Analysis Software for Windows®Single-Computer License (One Site) AIEXT.MC Multiple-Computer License (One Site) DISEXT.1C Dial-In Server EXT For Modems Single-Computer License (One Site) DISEXT.MC Dial-In Server EXT For Modems Multi-Computer License (One Site)