CAB — Handheld circuit breaker analyzer and timer

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 5 pages · 1296 KB) · Source page: CAB: handheld breaker and timer analyser

Breaker diagnosis in the palm of the hand

CAB

Image: CAT-H handheld circuit breaker analyzer with colour screen showing timing graphs, numeric keypad and rubber bumpers.

Circuit breaker testing

CAB

Handheld circuit breaker analyzer and timer

Timing, synchronism and coil currents on breakers with one break per phase.

Product overview

Two complementary handheld devices

The handheld series comprises the CAT-P (1.4 kg) and the CAT-H (1.6 kg). Both time the main contacts with one break per phase, record the opening and closing coil currents, the substation battery voltage and the auxiliary contacts, and measure the resistance of the pre-insertion resistors.

Each with its own speciality

The CAT-H integrates coil control to operate the breaker from the device itself; the CAT-P offers it through an external module and adds the online first trip test based on the CTs' secondary currents.

Main features

  • Internal Li-ion battery for 8 hours of testing (user replaceable on the CAT-P).
  • 5.7-inch colour touch screen readable in full sunlight.
  • Overlay of up to 4 graphical records to compare operations.
  • Internal memory for over 30,000 results.
  • O, C, CO, O-C, C-O and O-C-O operations with delay or contact-position sensing.
  • Direct download to USB memory and PC communication.
  • IP40 protection rating in 310 × 170 × 58 mm.
Image: CAT-P: 5.7-inch touch screen and alphanumeric keypad. CAT-P handheld circuit breaker analyzer, front view with colour screen and keypad.

Applications and software

Applications

  • LV, MV and HV breakers with one break per phase.
  • First trip test with the installation in service (CAT-P).
  • Verification of control circuit wiring.
  • Pole synchronisation and bounce times.
  • Maintenance contractors and industrial environments.

PC software for control and analysis

The included PC software downloads the tests over Bluetooth or USB, presents the curves with cursors and zoom, overlays several records for comparison, converts units automatically and exports the results for reports.

Measurement triggers for every case

Recording can start from the coil control channel, from the DC current clamp or from the DC voltage channel, depending on whether the operation is initiated from the control room, a local switch or the test device itself.

Image: Measurement on a breaker: main contact cables and current clamp. Technician in a hard hat and work clothes connecting test leads to the mechanism of a medium-voltage circuit breaker.

CAB — MEASUREMENT DATA

Main contact inputs3 (1 per phase); closed ≤ 10 Ω; pre-insertion 10 Ω – 5 kΩ; open ≥ 5 kΩ
Time resolution0.05 to 10 ms depending on test duration (sampling up to 20 kHz)
Time accuracy0.05% of reading ± resolution
Coil current±35 A DC to 5 kHz; 30/300 A clamps (300 A RMS / 450 A peak)
DC voltage±300 V; typical ±0.5% ±0.5% FS; guaranteed ±1% ±1% FS
AC clamps for first trip (CAT-P)0.05 – 5 A RMS; ±3% to ±1% by range
Coil control (CAT-H)2 channels; ±300 V DC/AC peak; ±35 A
MemoryOver 30,000 numerical and graphical results

The contact circuit works with 20 V DC and 50 mA open-circuit values. Specifications valid at +25 °C with standard accessories.

CAB — TECHNICAL SPECIFICATIONS

CAT-PCAT-H
Weight1.4 kg1.6 kg
Coil controlVia external module (optional; 0.6 kg)Built-in (2 channels, ±300 V, ±35 A)
Online first trip testYes (AC clamps 0.05 – 5 A)—
Internal battery2 × 3.7 V, 2900 mAh; user replaceable2 × 3.7 V, 2900 mAh
Display5.7-inch colour touch screen5.7-inch colour touch screen
Dimensions310 × 170 × 58 mm310 × 170 × 58 mm

Common: 8-hour autonomy; 12 V DC / 5 A adapter with 90 – 264 V AC input; memory for over 30,000 results; IP40; operation -10 to +55 °C; storage -40 to +70 °C; humidity 0 – 95% non-condensing. Standards: safety EN 61010-1 (Directive 2014/35/EU); EMC EN 61326-1 (Directive 2014/30/EU); installation category II; pollution degree 2. Specifications valid at +25 °C.

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote