CAT-P

1 break per phase · Online first trip test

Image: CAT-P circuit breaker analyzer seen from the front: grey handheld unit with black corner bumpers, input terminals on top, color touch screen showing test curves, a row of soft keys and an alphanumeric keypad.

Handheld circuit breaker analyzer & timer

Overview

Image: Three-quarter view of the CAT-P: color screen with current and timing curves, soft keys, alphanumeric keypad and input terminals on top.

CAT-P: handheld circuit breaker analyzer & timer.

Offline and online testing

The CAT-P is a digital instrument for circuit breaker condition assessment. It records the timing of the main arcing contacts, the substation DC battery voltage and the Trip and Close coil currents. In online mode, the main contact operating time is calculated from the AC secondary currents of the current transformers.

Operating modes

Trip (O), Close (C), Trip-free (CO), Reclose (O-C), Close-Trip (C-O), Trip-Close-Trip (O-C-O) and First trip.

How online recording starts

Before the test, the current clamp is connected to the auxiliary circuit of the circuit breaker. Recording starts when the coil current reaches the predefined threshold; the DC clamp measures the Trip or Close coil current, depending on the operation.

What it records and analyzes

  • Trip and Close coils operation.
  • Main arcing contacts operation.
  • Auxiliary contact operation.
  • DC supply voltage.
  • Integrity of control circuit wiring.

It displays numerical and graphical results and overlays up to 4 records. The internal battery is user-replaceable.

Panel and connections

Image: CAT-P front panel and two views of its sides with the connections numbered 1 to 12: AC clamp inputs on top; DC clamp, DC voltage and main contact terminals; screen, soft keys and keypad on the front; power supply, flash drive and USB port on one side.

CAT-P front panel and side connections.

  • 1 · AC current clamp inputs: AC current recording in online mode.
  • 2 · DC current clamp input: coil current recording and measurement.
  • 3 · DC voltage channel input: voltage measurement of an analog signal.
  • 4 · Main contacts input (offline measurement): timing of the main and pre-insertion resistor contacts, and pre-insertion resistor resistance.
  • 5 · 5.7-inch color touch screen.
  • 6 · Soft keys: selection of settings and menus as an alternative to the touch screen.
  • 7 · Alphanumeric keypad: breaker data, test data and control functions.
  • 8 · Power indicator.
  • 9 · Power ON/OFF button.
  • 10 · 12 V DC, 5 A power supply, with 85-264 V AC (47-63 Hz) adapter.
  • 11 · Flash drive: direct download of test results.
  • 12 · USB port for PC communication.

First trip test (online)

Image: Online test diagram: three blue AC clamps are placed around the current transformer secondary wiring of phases A, B and C; a DC clamp is placed around the trip coil circuit and a red lead measures the substation battery voltage. Everything goes to the CAT-P at the bottom; there are no cables on the breaker interrupters.

CAT-P connection to a live tank circuit breaker for online testing.

The first trip test shows the condition of the operating mechanism and how the circuit breaker would perform in a real fault. A breaker spends most of its life conducting current without operating; if it has been idle for a long time, latch friction may increase, and the coil current waveform of the first trip reveals it.

With the breaker in service, timing cables across the interrupter cannot be used. AC clamps, DC clamps and voltage sense cables are used instead:

  • AC clamps measure the secondary current of each current transformer and indicate when the main current is interrupted, giving the main contact time.
  • The DC clamp measures the coil current in the auxiliary circuit and allows analysis of the trip coil and the mechanism.
  • Voltage sense cables measure the control voltage and show the condition of the DC battery and its wiring.

It is a fast test, of around 10 minutes, performed by a single operator with non-invasive connections while the installation is energized.

Offline testing

Image: Offline test diagram: the coil control module, on the left, operates the close and trip coils. The CAT-P measures the coil current with a clamp, the substation battery voltage and, with a timing cable with red, yellow and blue clips, the contacts of phases A, B and C, which are grounded.

CAT-P with the coil control module on a live tank circuit breaker (offline test).

In offline mode, the CAT-P measures main arcing contact timing with the circuit breaker isolated from the power grid, or at the factory or workshop. The breaker must be disconnected on both sides and grounded in accordance with safety regulations. Timing measurement fulfils the requirements of IEC 62271-100 and ANSI C37.09.

The external coil control module (optional, 0.6 kg) is used to operate the Trip and Close coils.

Applications

  • Timing of up to 3 main contacts (1 break per phase), including pre-insertion resistors and auxiliary contact.
  • Resistance of the pre-insertion resistors.
  • Main contacts bounce time and pre-trigger time.
  • Measurement and graphical display of coil currents.
  • State of the substation battery or another analog signal.

PC software

  • Download, viewing, editing, printing and exporting of records.
  • Overlay of graphs and comparison with other circuit breaker analyzers of the same range.
  • Two cursors, zoom and test sequence configuration.

CAT-P — TECHNICAL DATA

Main contact inputs3 (3 × 1), one per phase. Closed ≤ 10 Ω; pre-insertion resistor 10 Ω to 5 kΩ; open ≥ 5 kΩ. Open circuit voltage 20 V DC; short circuit current 50 mA
Time resolution0.05 ms to 10 ms depending on test duration (sampling rate up to 20 kHz)
Time accuracy0.05% of reading ± resolution
OperationsClose (C), Trip (O), Close-Trip (C-O), Trip-Close (O-C), Trip-Close-Trip (O-C-O) and First trip
DC current clampsNominal 300 A RMS or 450 A DC peak; ranges 30/300 A; DC to 20 kHz (−3 dB)
AC current clamps0.05 A to 5 A RMS; accuracy ±3% ±1 mV (0.05-0.5 A), ±1.5% ±1 mV (0.5-1 A), ±1% (1-5 A)
DC voltage measurement±300 V; typical accuracy ±0.5% of reading ±0.5% FS; guaranteed ±1% of reading ±1% FS
External power supply12 V DC, 5 A; input 90-264 V AC, 50/60 Hz
Internal batteryLi-ion 2 × 3.7 V, 2900 mAh, user-replaceable; 8 h under normal use
Display145 mm (5.7-inch) color touch screen; graphical and numerical results
Internal memoryOver 30,000 numerical and graphical test results
StandardsSafety: Directive 2014/35/EU, IEC EN 61010-1 (class I, pollution degree 2, installation category II); EMC: Directive 2014/30/EU, EN 61326-1; CAN/CSA-C22.2 No. 61010-1
Environmental conditionsOperating −10 °C to +55 °C; storage and transport −40 °C to +70 °C; humidity 0 to 95% non-condensing
DimensionsCAT-P: 310 × 170 × 58 mm; coil control module: 228 × 115 × 53 mm
WeightCAT-P: 1.4 kg; coil control module: 0.6 kg
Ingress protectionIP40
Warranty3 years

Specifications valid at +25 °C with recommended accessories. Subject to change without notice.

CAT-P — ACCESSORIES

Instrument with included accessories: CATP000-N-00 (CAT-P with PC software on USB stick, mini USB cable, touch pen, plastic transport case and mains cable with power adapter).

CMP-08-SETA1Main contacts cable set 8 m with alligator clamps (A1) · standard
MC-CG-0302A1Main contacts connection 3 × 1 m and ground cable 2 m with clamps (A1) · standard
S2-05-02BPBPVoltage sense cable set 2 × 5 m, 2.5 mm² · standard
JCR-15-2REBP / JCB-15-2REBP15 cm jumper cables with retractable-insulation banana plugs, red and black · standard
DOLPIN-CL-B0 / -R0Dolphin clips, black and red · standard
CACL-0300-09Current clamp 30/300 A powered from the instrument, with 5 m extension and adapter · standard
CACL-AC00-05AC current clamp 1 A / 1 V with 5 m cable (3 units) · standard
PLAST-CAS-00Plastic case for accessories · standard
COCON-MOD-00Coil control module · optional
CO-05-00C5B1 / CO-10-00C5B1Coil control cable 5 or 10 m with banana plugs · optional
C2-05-02BPBP / C2-10-02BPBPCoil supply cable set 2 × 5 m or 2 × 10 m, 2.5 mm² · optional
CACL-0100-00 / CACL-ACE-N10Current clamp 10/100 A with internal battery, 5 m extension and adapter; 5 m extension for the 1 A / 1 V AC clamp · optional
S2-02-02BPBP / S2-10-02BPBPVoltage sense cables 2 × 2 m or 2 × 10 m · optional
TESTPR-GJ-B0 / -R0 / TESTPR-SC-B0 / -R0Test probes with grip jaws, black and red; Test probes with split test clamps, black and red · optional
CMP-10-SETA1 / CMP-08-SETA2 / CMP-10-SETA2Contact cable sets 8 or 10 m with A1 or A2 clamps · optional
CMP-08-SETST / CMP-10-SETSTContact cable sets 8 or 10 m with SCT clamps · optional
CMPA-03-SET0 / CMPA-05-SET0Contact cable set adapter, 3 or 5 m · optional
MC-CG-0302A2 / MC-CG-0302STContacts connection 3 × 1 m and ground 2 m with A2 or SCT clamps · optional
LION-BAT-001 / FIR-RTBBAG-0Li-ion battery 7.4 V 2900 mAh in fire-retardant bag / fire-retardant bag · optional
RSTCH-PEN-00 / HARD-CASE-PP / CABLE-BAG-00Touch pen / plastic transport case for CAT-P; Cable bag · optional
PWR-ADP5A-EU / -NA / -UK / -AUMains cable with 12 V / 5 A power adapter (EU, North America, UK, Australia) · optional

Cables are available in other lengths and terminations on request.