Skip to content

Accessible version

AMPERIS VIPO-85 Vacuum Interrupter Tester

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 4 pages · 179 KB) · Source page: VIPO-85: vacuum interrupter tester 85 kV

PASS/FAIL verdict on vacuum interrupters up to 85 kV DC

Switch testing equipment

Image: Portable test instrument in its open rugged case with cables, clamps and accessories.

VIPO-85

85 kV vacuum interrupter tester and DC hipot

Quick, safe integrity testing of vacuum interrupters following ANSI/IEEE DC methods.

Product overview

Image: Instrument and leads inside the transport case

The vacuum bottle, verified in minutes

The VIPO-85 applies a regulated DC voltage of 1 to 85 kV, in 1 kV steps, to the vacuum interrupter and measures the leakage current, showing a clear PASS or FAIL against user-set limits of 100, 200 or 300 µA. It follows the ANSI/IEEE standardised DC test methods, and all cables remain connected inside the rugged IP67 case between jobs.

Also a compact DC hipot

In HiPot mode the instrument displays kV, µA and TΩ with a continuous 85 kV / 300 µA rating and a stop limit adjustable from 25 to 300 µA in 25 µA steps. The 4.3-inch ultra-bright touch display works with gloves, the unit is ready 2 seconds after power-up, and a built-in thermal printer documents the result on the spot.

Main features

  • Output accuracy of 1.5 % with less than 2 % ripple (20-85 kV).
  • Current measurement 0-400 µA with 1 µA resolution.
  • Test duration settable from 2 s to 2 min; discharge in under 3 s.
  • High-brightness visual indicator and audible alert while HV is present.
  • Storage for 200 tests, transferred by USB flash drive.
  • Battery version VIPO-85B with user-replaceable Li-ion pack.

Applications and delivery

Applications

  • Integrity testing of vacuum interrupters in medium-voltage breakers.
  • DC hipot tests on switchgear, cables and insulation up to 85 kV.
  • Commissioning and periodic maintenance in the field.
  • Workshop acceptance tests with printed evidence.

Ready for the field

The instrument travels in its transport and operation case with IP67 protection when closed, weighs 9.4 kg and works from 0 to +50 °C; firmware updates and test transfers use a standard USB flash drive.

VIPO-85 — TECHNICAL SPECIFICATIONS
Output1.0-85.0 kV DC in 1 kV steps; 0.3 mA continuous at max voltage
Output accuracy1.5 %; ripple below 2 % (20-85 kV)
Current measurement0-400 µA; 1 µA resolution; 2 % accuracy at full scale
Pass/fail limit (VI test)100, 200 or 300 µA, user set
Stop limit (HiPot mode)25-300 µA in 25 µA steps; kV/µA/TΩ display
Test duration2 s to 2 min, user set; discharge below 3 s
Display and control4.3-inch ultra-bright IPS touch screen, glove compatible
ResultsStorage for 200 tests; USB transfer; built-in thermal printer
Supply100-240 V AC, 47-63 Hz; battery version VIPO-85B (Li-ion 14.4 V)
Environment0 to +50 °C; 5-95 % RH non-condensing; IP67 with case closed
Dimensions and weight410 × 310 × 150 mm; 9.4 kg

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote