VIPO-85: vacuum interrupter tester 85 kV

VIPO-85: vacuum interrupter tester 85 kV

85 kV vacuum interrupter tester and DC hipot

The VIPO-85 applies a regulated DC voltage of 1 to 85 kV to a vacuum interrupter and returns a clear PASS or FAIL, following ANSI/IEEE DC test methods, with a built-in printer and IP67 transport case.

Advantages

The vacuum bottle, verified in minutes
A regulated DC voltage of 1 to 85 kV in 1 kV steps is applied to the interrupter; the leakage current is measured and shown as a clear PASS or FAIL against user-set limits of 100, 200 or 300 µA.

Also a compact DC hipot
In HiPot mode the instrument displays kV, µA and TΩ with a continuous 85 kV / 300 µA rating and a stop limit adjustable from 25 to 300 µA in 25 µA steps.

Ready in seconds
The 4.3-inch ultra-bright touch display works with gloves, the unit is ready two seconds after power-up and a built-in thermal printer documents the result on the spot.

Evidence you can keep
The instrument stores 200 tests and transfers them by USB flash drive, with a high-brightness indicator and audible alert whenever high voltage is present.

Built for the field
All cables stay connected inside the rugged case, which provides IP67 protection when closed; the unit weighs 9.4 kg and works from 0 to +50 °C.

Applications

  • Integrity testing of vacuum interrupters in medium-voltage breakers.
  • DC hipot tests on switchgear, cables and insulation up to 85 kV.
  • Commissioning and periodic maintenance in the field.
  • Workshop acceptance tests with printed evidence.

About the product

The VIPO-85 runs on 100-240 V AC, and the VIPO-85B version adds a user-replaceable 14.4 V Li-ion battery; output accuracy is 1.5 % with less than 2 % ripple, current is measured from 0 to 400 µA with 1 µA resolution and test duration is settable from 2 s to 2 min, with discharge in under 3 s.

Technical specifications

Output1.0-85.0 kV DC in 1 kV steps; 0.3 mA continuous at max V
Output accuracy1.5 %; ripple below 2 % (20-85 kV)
Current measurement0-400 µA; 1 µA resolution; 2 % at full scale
Pass/fail limit (VI test)100, 200 or 300 µA, user set
Stop limit (HiPot mode)25-300 µA in 25 µA steps
Test duration2 s to 2 min; discharge below 3 s
Display and control4.3-inch ultra-bright IPS touch, glove compatible
Results200 tests; USB transfer; built-in thermal printer
Supply100-240 V AC; battery version VIPO-85B (Li-ion)
Environment and weight0 to +50 °C; IP67 with case closed; 9.4 kg

Frequently asked questions

What does the PASS/FAIL verdict mean?
The instrument compares the measured leakage current with a user-set limit (100, 200 or 300 µA) and shows PASS or FAIL for the vacuum interrupter under test.

Up to what voltage does it test?
A regulated DC voltage adjustable from 1 to 85 kV in 1 kV steps, continuously rated at 0.3 mA.

Can it be used as a hipot tester?
Yes. HiPot mode shows kV, µA and TΩ with an 85 kV / 300 µA continuous rating and an adjustable stop limit.

How are results recorded?
The unit stores 200 tests, prints them on the built-in thermal printer and transfers them by USB flash drive.

Is there a battery version?
Yes, the VIPO-85B, with a user-replaceable 14.4 V Li-ion pack for field work without mains power.

If you want to acquire Coil testing with quality, you can also consult prices of Coil testing.

If you have any doubts or need advice from our engineers, don't hesitate to contact us and we will be pleased to help you. You can also call us at (+34) 982 20 99 20.