ACCURACY AND UPGRADE SWITCHES
Basic Features Summary
- 2% Class Revenue Certifiable Energy and Demand Metering
- Meets ANSI C12.20 and IEC 62053-22 (0.2% Class)
- Multifunction Measurement
- 3 Line .56” LED display and % of Load Bar for Analog Perception
- 0.007 Hz Frequency Measurement for Generating Stations
- Standard RS485 (Modbus and DNP 3.0)
Amperis introduces a new standard in panel mounted power metering. The Shark® 200 metering system is an ultra compact power metering device providing industry leading revenue metering functionality combined with advanced data logging, power quality, communication and I/O traditionally found only in high performance and high cost systems. This product is designed to incorporate advanced features in a cost effective, small package, for large scale, low cost deployment within an electrical distribution system.
- IrDA Port Enables Laptop PC Reading and Programming
- Ultra Compact
V-SWITCH™ TECHNOLOGY
- Fits both ANSI and DIN Cutouts
Advanced Features Summary
- High Performance Waveform Recorder
The Shark® 200 meter is equipped with EIG’s exclusive V-Switch™ technology. This technology allows users to upgrade and add features to the meter without removing it rom installation. V-Switches include the following Features:
- Up to 4 Megabytes Flash for Historical Data Logging & PQ Recording
- Extremely Configurable Field Upgradable I/O
- 100BaseT Ethernet Rapid Response™ Technology
- V-Switch™ Technology
- High Precision Frequency Measurement for Frequency Control
Applications
- Utility Metering
- Commercial Metering
- Substations
- Industrial Metering
- Power Generation
- Campus Metering
- Submetering
- Analog Meter Replacement
- Power Quality Studies
- Disturbance Recording
- Load Studies
- Voltage Recording
| Feature | V1 | V2 | V3 | V4 | V5 | V6 |
|---|---|---|---|---|---|---|
| Multifunction Measurement with I/O Expansion | * | * | * | * | * | * |
| 2 Megabytes Data Loggin | * | * | * | |||
| 3 Megabytes Data Loggin | * | |||||
| 4 Megabytes Data Loggin | * | |||||
| Harmonic Analysis | * | * | * | * | ||
| TLC and CT/PT Compensation | * | * | * | * | * | * |
| Limit and Control Functions | * | * | * | |||
| 64 Samples per cycle Waveform Recorder | * | |||||
| 512 Samples per Cycle Waveform Recorder | * |
Contactoo
AMPERIS PRODUCTS S.Lagricultura, 34, Contactoo 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, España info@amperis.com | www.amperis.com
| Measured | ACCURAC | CY |
|---|---|---|
| Measured Parameters | Accuracy | Display Range |
| Voltage L-N | 0.1% | 0-9999 Scalable V or kV |
| Voltage L-N | 0.1% | 0-9999 V or Kv Scalable |
| Current | 0.1% | 0-9999 Amps or kAmps |
| +/- Watts | 0.2% | 0-9999 Watts, kWatts, MWatts |
| +/-Wh | 0.2% | 5 to 8 Digits Programmable |
| +/-VARs | 0.2% | 0-9999 VARs, kVARs,MVARs |
| +/-VARh | 0.2% | 5 to 8 Digits Programmable |
| VA | 0.2% | 0-9999 VA, Kva, MVA |
| VAh | 0.2% | 5 to 8 Digits Programmable |
| PF | 0.2% | +/- 0.5 to 1.0 |
| Frequency | +/-0.007 Hz | 45 to 65 Hz |
| % THD | +/2.0% | 1 to 99.99% |
| % Load Bar | +/- Segment | (0.005 to 6) A |
Advanced Revenue Energy Metering Capabilities
- Line Frequency Time Sync
- Traceable Watt-hour Test Pulse
- Utility Block and Rolling Average Demand
- Historical Load Profiling
- Transformer and Line Loss Compensation
- CT/PT Compensation
EXTENSIVE DATA LOGGING CAPABILITY (V2 AND HIGHER)
At V2, the Shark® 200 meter has 2 Megabytes of data logging to be used for historical trends, limit alarms, I/O changes and sequence of events (V5 and V6 offer even more memory). The unit has a real-time clock that allows for time stamping of all the data in the instrument when log events are created.
Historical Logs
- 3 Assignable Historical Logs
- Independently Programmed Trending Profiles
- Up to 64 Parameters per Log
System Events Log
To protect critical billing information, the meter records and logs the following with a time stamp:
- Demand Resets
- Password Requests
- System Startup
- Energy Resets
- Log Resets
- Log Reads
- Programmable
- Critical Data Repairs
- Settings Changes
I/O Change Log
- Provides a Time Stamped Log of Any Relay Output
- Provides a Time Stamped Log of Input Status Changes
- 2048 Events Available
Limit/Alarm Log
- Provides Magnitude and Duration of an Event
- Includes Time Stamps and Alarm Value
- 2048 Events Available
Limit Alarms and Control
- Capability (V4 Option)
- Limit Events:
- Any Measured Parameter
- Up to 16 Limits
- Voltage Imbalance
- Current Imbalance
- Based on % of Full Scale Settings
EXTENSIVE DATA LOGGING CAPABILITY (V2 AND HIGHER)
| Samples per cycle | Pre Event Cycles | Post Event Cycles | Max Waveform per Event | Number of Stored Events | |
|---|---|---|---|---|---|
| 16 | 32 | 96 | 256 | 85 | |
| V5 | 32 | 16 | 48 | 128 | 85 |
| 64 | 8 | 24 | 64 | 85 | |
| 128 | 4 | 12 | 32 | 170 | |
| V6 | 256 | 2 | 6 | 16 | 170 |
| 512 | 1 | 3 | 8 | 170 |
Waveform Scope
The unit uniquely offers a waveform scope to view the real time waveform for voltage and current. The waveform scope allows the meter to be used as a basic oscilloscope throughout a power system.
Independent CBEMA Log Plotting
The meter stores an independent CBEMA log for magnitude and duration of voltage events. This allows a user to quickly view total surges, total sags and duration, without retrieving waveform data.
Simultaneous Voltage and Current Waveform Recorder. The unit records up to 512 samples per cycle for a voltage sag or swell or a current fault event. The unit provides the preand post-event recording capability shown in the table below. Waveform records are programmable to the desired sampling rate. V5 provides up to 3 Megabytes storage and V6 provides a total of 4 Megabytes.The meter’s advanced DSP design allows Power Quality triggers to be based on a 1 cycle updated RMS. Up to 170 events can be stored until the memory fills. The meter stores waveform data in a first-in/first-out circular buffer to insure data is always recording.
Harmonic Recording to the 40th Order
The Shark® 200 meter provides advanced harmonic analysis to the 40th order for each voltage and current channel in real time. Using the stored waveforms, harmonic analysis is available to the 255th order.
STANDARD COMMUNICATION CAPABILITY
1mAOS: Four Channel Bi-directional 0-1mA Outputs
- Assignable to any parameter
The Shark® 200 meter provides two independent communication ports with advanced features.
Rear Mounted Serial Port with KYZ Pulse
- RS485 This port allows RS485 communication using Modbus or DNP 3.0 protocols. Baud rates are from 1200 to 57600
- KYZ Pulse In addition to the RS485 port, the meter also includes Pulse Outputs mapped to absolute energy.
FIELD EXPANDABLE I/O AND COMMUNICATION CAPABILITIES
- 0.1% of full scale
- 0 to 10K Ohms
- Range +/- 1.20mA
- Designed for RTUs and generating stations
20mAOS: Four Channel 4-20mA Outputs
- Assignable to any parameter
- 0.1% of full scale
- 0 to 850 Ohms at 24VDC
- Loop Powered using up to 24 Volts DC
- Ideal for any Process Control application
The Shark® 200 meter offers unequaled I/O expandability. Using the two universal option slots, the unit can be easily configured to accept new I/O cards even after installation. The unit auto-detects installed I/O option cards. Up to 2 cards of any type can be used per meter.
INP100S: 100BaseT Ethernet Capability
The meter can provide 100BaseT Ethernet functionality.
- Embedded web server, Smartphone compatible
- Network Time Protocol (NTP) support (Network Clock Sync)
- 12 simultaneous Modbus TCP/IP connections
- 5 simultaneous DNP over TCP/IP connections
- Dual Ethernet Ports available
- Supports alarm emails and periodic email notification of meterstatus/reading data
RO1S: Two Relay Outputs / Two Status Inputs
- 250VAC/30VDC - 5A Relays, Form C
- Trigger on user set alarms
- Set delays and reset delays
- Status Inputs – Wet / Dry Auto Detect (Up to 150 VDC)
- Allows for control, alarm and status (must be at V4 or higher for limit alarms and control)
PO1S: Four Pulse Outputs / Four Status Inputs
- Programmable to any energy parameter and pulse value
- Form A: Normally open contacts
- Also used for End of Interval pulse
- 120mA continuous load current
- Status Inputs - Wet / Dry Auto Detect (Up to 150 VDC)
- Provides KYZ outputs and pulse input counting
INP300S: IEC 61850 Protocol Ethernet Card
- Simultaneous Modbus and IEC 61850
- 5 Simultaneous MMS Clients
- Multiple Logical Nodes
- Polled Operation Mode (Queried Reports)
- Buffered and Unbuffered Reports
- Configurable .CID file
FOVPS or FOSTS: Fiber Optic Card
- EIG’s exclusive Fiber Optic Daisy Chain switchable built-in logic mimics RS485 half duplex bus, so you can daisy chain meters for lower installation costs. Full duplex is also assignable.
- ST Terminated Option (-FOSTS)
- Versatile Link Terminated Option (-FOVPS)
- Modbus and DNP 3.0 protocols available
- The preferred communication method for intrinsic safety and high reliability
100BASET ETHERNET (INP100S or INP300S)
Simultaneous Data Connections
INP100S - WEB SERVER, MODBUS, DNP AND EMAIL
- Web Server with Configurable HMI • Smartphone Compatible
- 12 Connections Modbus TCP HMI
- 5 Connections DNP over TCP/IP
- Smartphone Compatible
- Sends Emails on Alarm or Meter Status & Reading Data
INP300S - WEB SERVER, MODBUS, IEC 61850
- IEC 61850 Protocol
- 5 Modbus Connections
- 5 MMS Clients
- Web Server for Status and Configuration
- Dual Ethernet Port Capable
- Simultaneous Modbus, DNP over Ethernet, and IEC 61850
SHARK 200 METER ANSI AND DIN MOUNTING
The unit mounts directly in an ANSI C39.1 (4” round form) ora n IEC 92 mm DIN square form. This is perfect for new installations and for existing panels. In new installations, simply use DIN or ANSI punches. For existing panels, pullo ut old analog meters and replace them with the Shark 200 meter. The meter uses standard voltaje and current inputs so that CT and PT wiring does not need to be replaced.
SHARK 200T TRANSDUCE
Contactoo
AMPERIS PRODUCTS S.Lagricultura, 34, Contactoo 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, España info@amperis.com | www.amperis.com
TYPICAL SUBSTATION SOLUTIONS
SHARK 200 METER ANSI AND DIN MOUNTING
Traditionally, voltage recording meters were relegated to high cost metering or monitoring solutions. The Shark® 200 meter can be placed throughout an electrical distribution network. The meter provides one of the industry’s lowest cost methods of collecting voltage information within a Utility power distribution grid.
- Perform voltage reliability analysis insuring proper voltage to customers. • Compare voltage reliability throughout transmission or distribution networks.
- Monitor the output of substation transformers or line regulators.
- Initiate conservation voltage reduction, reducing system demand.
- Monitor highly accurate frequency to regulate frequency stability.
- Replace costly frequency transducers
INTERVAL LOAD PROFILING
The Shark 200 meter allows you to log substation data over time with regard to electrical usage, demand, voltage, current, PF and many other parameters. This enables a complete analysis of the power system over time.
- Provide revenue accurate load profiling.
- Determine substation usage.
- Analyze feeder capacity and utilization.
- Provide time based load profile for planning and estimation.
- Data trend PF distribution and imbalances for system efficiency analysis
LOW COST SUBSTATION TELEMETRY
The Shark® 200 meter’s advanced output capability brings back data using many different communication media such as RS485, Ethernet and analog outputs. This insures that one meter can be used for almost every substation application, no matter what communication infrastructure is needed.
- Perfect for new or retrofit applications.
- Multiple Com paths.
- One meter provides outputs for every application.
- Multiple systems and/or users accessing data simultaneously.
DIMENSIONAL DRAWINGS
WIRING DIAGRAMS
| VOLTAGE INPUTS | •20-576 Volts Line To Neutral, 0-721 Volts Line to Line •Universal Voltage Input •Input Withstand Capability – Meets IEEE C37.90.1 (Surge Withstand Capability) •Programmable Voltage Range to Any PT ratio •Supports: 3 Element WYE, SPECIFIC | CATIONS SENSING METHOD | •True RMS •Sampling at over 400 Samples / Cycle on all Channels of Measured Readings Simultaneously •Harmonics Resolution to 40th Order •Waveform up to 512 Samples/Cycle |
|---|---|---|---|
| •Supports: 3 Element WYE, •Element WYE, 2 Element Delta, 4 Wire Delta Systems •Burden: Input Impedance 1 Mega Ohm. Burden 0.014 W at 120 Volts •Input Wire Gauge: AWG#12 -26/(0.129 -3.31) mm2 | UPDATE RATE | •Watts, VAR and VA - Every 6 Cycles •All Other Parameters - Every 60 Cycles | |
| •Input Wire Gauge: AWG#12 -26/(0.129 -3.31) mm2 | Option D2: | ||
| CURRENT INPUTS | •Class 10: (0.005 to 11)A, 5 A Nominal •Class 2: (0.001 to 2)A, 1 A Nominal Secondary •Fault Current Withstand (at 23°C): 100 Amps for 10 Seconds, 300 Amps for 3 Seconds, 500 Amps for 1 Second •Continuous Current Withstand: 20 Amps for Screw Terminated or Pass Through Connections | POWER SUPPLY | •(90 to 265) Volts AC and (100 to 370) Volts DC. Universal AC/DC Supply Option D: •18-60VDC Burden: 10VA max. |
| •Programmable Current to Any CT Ratio •Burden 0.005 VA per Phase Max at 11 Amps •Pickup Current: 0.1% of Nominal Class 10: 5 mAClass 2: 1 mA •Pass Through Wire Diameter: 0.177” / 4.5 mm | STANDARD COMMUNICATION | •2 Com Ports (Back and Faceplate) •RS485 Port (Through Backplate) •IrDA (Through Faceplate) •Com Port Baud Rate: (1200 - 57600) | |
| ISOLATION | All inputs and Outputs are Galvanically Isolated to 2500 Volts | FORMAT | •Com Port Address: 1-247 •8 Bit, Parity Setting: Odd, Even, None |
| •Modbus RTU, ASCII or DNP 3.0 Protocols | |||
| •Storage: (-20 to +70) °C •Operating: (-20 to +70) °C | |||
| ENVIRONMENTAL RATING | •Operating: (-20 to +70) °C •Humidity: to 95% RH Non-Condensing •Faceplate Rating: NEMA 12 •Mounting Gasket Included | KYZ PULSE | •Type Form C Contact •On Resistance: 35 Ohms Max •Peak Voltage: 350 VDC •Continuous Load Current: 120 mA •Peak Load Current: 350 mA (10 ms) |
| •Off State Leakage Current@ 350 VDC: 1uA | |||
| DIMENSIONS & | •Weight: 2 lbs /0.91 Kg | ||
| SHIPPING | •Basic Unit: H4.85” x W4.85” x L4.25” |
AMPERIS PRODUCTS S.Lagricultura, 34, Contacto 27003 Agricultura,34 +T [+34] 982 20 99 20 | F [+34] 982 20 99 11 lugo [spain]27003, Lugo, España info@amperis.com | www.amperis.com