Video: Circuit breakers and switchgear: why they fail and what continuous monitoring detects

Duration: 3:11 ·

Between 83 and 90 % of circuit breaker problems are mechanical. What the trip coil current, SF6 and partial discharge in switchgear reveal.

AI-generated video. The information must be validated by an Amperis engineer.

Article this video appears in

Video transcript

Circuit breakers and switchgear: what breaks, what conventional maintenance misses, and what a continuous monitor actually adds. Start with the reason any of this matters. Circuit breakers are by far the largest single contributor to substation events, and a breaker that fails to open, or is merely slow, leaves everything behind it exposed to the fault current. And when they do fail, the cause is overwhelmingly mechanical.

According to EPRI's substation life-extension guidelines, mechanical problems account for between 83 and 90% of the reported problems, at every voltage class. Cyclic maintenance misses these problems for a simple reason. They develop between the intervals, and several of them are invisible to a test that requires taking the breaker out of service. The offline tests themselves have limits worth knowing. Contact resistance, for instance, does not tell you about contact wear at all, because the arcing contacts are not the ones being measured.

Online, the measurement at the centre of everything is the trip coil current. Every bend in it is a piece of the mechanism moving, and at a 128 samples per cycle it is resolved to the millisecond. And the diagnosis is a comparison, not a threshold. When lubrication dries out, the first half of the waveform is unchanged and everything after the latch arrives late. A detail worth remembering: operate that breaker a second time and the interrupting time improves,

which is itself the signature of a lubrication problem rather than a latch one. A question that always comes up: the protective relay already records the trip, so why add anything? Because the relay tells you about the fault, and the monitor tells you about the breaker. From each capture come the numbers a breaker is actually judged on. With SF6, the argument against the gauge is simple. A mechanical gauge or a density switch needs somebody to look at it,

and only alarms once a significant amount of gas has already gone. And when the gas is tested in the laboratory rather than merely measured, the work serves 5 purposes. Finally, switchgear, where the failure mode changes. Here it is not the mechanism but the insulation, and the measurement that finds it is partial discharge. Five things to take away. Breaker and switchgear monitoring, from Amperis.