Video: Transformer monitoring: hot spot, gases, moisture, bushings and tap changer
Every 6 °C above 98 °C doubles the paper ageing rate. What hot spot, dissolved gases, moisture, bushings and the tap changer tell you.
AI-generated video. The information must be validated by an Amperis engineer.
Article this video appears in
Video transcript
Transformer monitoring: temperature, gas, moisture, bushings, tap changers and through faults. What each one tells you, and what it costs to ignore. Start with a question that frames everything else. What is the most important part of a transformer? The answer is that there is no single one: it is a collection of sub-systems, and a failure in any of them can take the unit off line.
The measurement that governs the life of the unit is the winding hot spot, and it cannot be measured with a probe in the oil. It is calculated, and the old gauges can be badly wrong. And the cost of getting it wrong is not linear. Under the IEC loading guide, every 6 degrees above 98 doubles the rate at which the paper ages. Gas is the second pillar, and it works as a thermometer. Each fault temperature produces its own gas,
so the gas that appears tells you how hot the fault is. Hydrogen gets its own treatment, because its physics are awkward. It is the least soluble of the diagnostic gases, so it leaves the oil and collects in the headspace at roughly 20 to one. Moisture surprises people because of one number. In a 50 MVA transformer with one and a half percent water in the paper, almost all of the water is in the paper, not the oil. And how much appears in the oil depends entirely on temperature.
And knowing the water in the paper is not academic. Three practical limits depend on it. Bushings deserve special attention because of the severity. A bushing failure is sudden, and about half the time it starts a fire that destroys the transformer with it. The online measurement works because of the construction of the bushing itself. And what the monitor looks for is balance. Three healthy bushings produce 3 currents that cancel.
When one changes, the sum stops being zero. One warning: at 10 kilovolts an offline test may miss contamination that shows plainly at rated voltage. The tap changer is the only part of a transformer that routinely moves, and the failure statistics of a large North American transmission and distribution utility make the point. Flashover in the tap changer was the single largest category, and 14 of those 28 cases went on to destroy a winding.
Four measurements watch it, and the cleverest is the motor energy. Most mechanical problems in the drive change the power the motor draws, so the joules used per tap change become a picture of the linkage, the gears and the lubrication. Two more stresses come from outside the transformer and are worth monitoring precisely because they accumulate. Through faults, and the harmonics from a saturated core. Five things to take away.
Transformer monitoring, from Amperis.