Shark 100

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 8 pages · 255 KB) · Source page: Shark 100 panel power meter, class 0.2S

Over 400 samples per cycle and a 24-bit converter in a meter that fits ANSI and DIN cut-outs

Revenue-grade panel meter, 0.2 % accuracy class

Image: Shark 100 multifunction meter front with three red LED rows reading 120.0 for phases A, B and C, Menu and Enter buttons and indicator LEDs.

Shark 100

Multifunction power and energy meter

A revenue-grade panel meter that measures voltage, current, power, energy, frequency and maximum demand.

Image: Meter with the terminal base and pass-through current inputs

Accuracy first

Sampling runs at over 400 samples per cycle with a 24-bit converter, which places the readings in the ANSI C12.20 0.2 accuracy class and the IEC 62053-22 0.2S class. A bright red LED display shows three lines of readings with intuitive navigation, an auto-scroll mode and a percentage of load bar that keeps the feel of an analogue meter.

What it measures

  • Voltage line to neutral and line to line, current, and frequency.
  • Active, reactive and apparent power, power factor and maximum demand.
  • Active, reactive and apparent energy, with 5 to 8 programmable digits.
  • Total harmonic distortion and limit-exceeded alarms with the V4 key.

Where it is used

  • Utility, commercial, industrial and campus metering, and submetering.
Image: Front, side and rear views with the main controls
  • Substations and power generation plants.
  • Direct replacement of analogue panel meters, reusing the existing CT and PT wiring.

Inputs designed for harsh electrical systems, simple installation and optional serial or Ethernet communication.

Installation, inputs and communication

High isolation voltage inputs

Image: Dimension drawings for ANSI mounting (3.38 in square, 4 x 0.2 in holes, 4.0 in diameter), DIN mounting (9.20 x 9.20 cm) and the Shark 100T DIN-rail transducer.
  • Up to 416 V line to neutral and 721 V line to line, universal input.
  • One unit works to specification on 69, 120, 230, 277 and 347 V systems.
  • Programmable to any PT ratio; withstand to IEEE C37.90.1.

Short-circuit safe current inputs

  • CT lead pass-through: the lead crosses the meter with no termination, so the meter cannot become a point of failure on the CT circuit and adds no burden to the secondary.
  • Current gills: rugged stud-based pass-through bars allow the CT leads to be terminated on the meter without the risk of an open CT under fault.

ANSI and DIN mounting, and the transducer version on DIN rail

Easy to install and use

  • Faceplate programming or set-up from a PC.
  • Phasor diagram on the display shows the wiring status.
Image: Wiring diagrams: three-phase four-wire wye direct and with PTs, and three-phase three-wire delta direct and with PTs.
  • Colour-coordinated voltage and current inputs to reduce wiring errors.

Communication and pulse output

  • Optional RS485 serial port with Modbus and DNP3, standard on the transducer version.
  • Optional 10/100BaseT Ethernet port with Modbus TCP/IP.
  • Fixed energy pulse mapped to positive energy, supplied with the communication options.
  • Standard IrDA optical port on the faceplate.

Wiring diagrams for the supported connections

Accuracy chart

ParameterAccuracyDisplay range
Voltage L-N0.1 %0-9999 V or kV, scalable
Voltage L-L0.1 %0-9999 V or kV, scalable
Current0.1 %0-9999 A or kA
Watts (+/-)0.2 %0-9999 W, kW, MW
Watt-hours (+/-)0.2 %5 to 8 programmable digits
VAR (+/-)0.2 %0-9999 VAR, kVAR, MVAR
VAR-hours (+/-)0.2 %5 to 8 programmable digits
VA0.2 %0-9999 VA, kVA, MVA
VA-hours0.2 %5 to 8 programmable digits
Power factor0.2 %+/- 0.5 to 1.0
Frequency0.01 Hz(45 to 65) Hz
THD5.0 %0 to 100 %
% load bar1-120 %10-digit scalable resolution

Accuracy is given as a percentage of reading; typical results are better. Applies to 3-element WYE and 2-element Delta connections. For 2.5-element connections add 0.1 % of full scale plus one digit to the figures above.

V-Switch key technology - features by key

Each key includes the functions of the previous ones and is activated in the field without removing the meter from service.

FeatureV1V2V3V4
Voltage and current measurement••••
Power, power factor and frequency•••
Energy counters and DNP3 protocol••
THD monitoring and limit-exceeded alarms•
Technical specifications
Voltage inputsUniversal input, (20-416) V line to neutral and (0-721) V line to line; programmable to any PT ratio; supports 3-element WYE, 2.5-element WYE, 2-element Delta and 4-wire Delta; burden 0.36 VA per phase at 600 V and 0.014 VA at 120 V; wire gauge AWG 12 / 2.5 mm² maximum
Current inputsClass 10: (0.005 to 10) A with 5 A nominal CT secondary; Class 2: (0.001 to 2) A with 1 A nominal CT secondary; programmable to any CT ratio; pick-up current 5 mA; burden 0.005 VA per phase at 11 A; pass-through wire diameter 0.177" / 4.5 mm
Current withstand100 A for 10 s, 300 A for 3 s and 500 A for 1 s at 23 °C; 20 A continuous on screw or pass-through connections
IsolationAll inputs and outputs galvanically isolated to 2500 V
Sensing methodRMS, over 400 samples per cycle on all channels simultaneously, with total harmonic distortion measurement
Update rateWatts, VAR and VA every 6 cycles; all other parameters once per second
Power supplyOption D2: universal (90-265) V AC at 50/60 Hz or (100-370) V DC, 5 VA maximum. Option D: (18-60) V DC
CommunicationStandard IrDA optical port; optional RS485 with Modbus RTU/ASCII and DNP3 (485P) or 10/100BaseT Ethernet with Modbus TCP/IP (INP10); both options include the KYZ energy pulse
Environmental ratingOperating and storage (-20 to +70) °C; humidity to 95 % RH non-condensing; faceplate NEMA 12 water resistant; mounting gasket included
ProtectionIP30 front and back; optional DIN rail mounting
Mounting, dimensions and compliance
Panel cut-outANSI C39.1 4-inch round (3.38" square punch) or 92 mm DIN square; one meter fits both standards
Meter dimensionsFront 4.85" x 4.85" (12.32 x 12.32) cm; depth 3.56" (9.04) cm; rear projection 4.10" (10.41) cm
Transducer versionShark 100T transducer without display, DIN rail mounted, with the RS485 port fitted as standard
DisplayThree lines of bright red LED digits, auto-scroll, percentage of load bar and phasor diagram
ComplianceANSI C12.20 0.2 accuracy class; IEC 62053-22 0.2S; IEEE C37.90.1 surge withstand; NEMA 12 faceplate; CE marking

Ordering information

Every field must be filled in to form a valid part number, in the order shown.

1. ModelShark100 (meter with display) or Shark100T (transducer without display)
2. Frequency range60 = 60 Hz system; 50 = 50 Hz system
3. Current input10 = 5 A nominal CT secondary; 2 = 1 A nominal CT secondary
4. V-Switch packV1 voltage and current; V2 adds power, power factor and frequency; V3 adds energy counters and DNP3; V4 adds THD and limits
5. Power supplyD2 = (90-265) V AC at 50/60 Hz or (100-370) V DC; D = (18-60) V DC
6. CommunicationX = none; 485P = RS485 with KYZ pulse, standard on the transducer; INP10 = 10/100BaseT Ethernet with KYZ pulse
7. Mounting Accessories, software and convertersX = ANSI mounting; DIN = DIN mounting brackets
COMPQA6P1YConfiguration and monitoring software for Windows, single-computer licence
EnergyPQA-1YearEnergy management system with analytics, one year
9PINCRS232 cable
CAB6490USB to IrDA adapter
Unicom 2500RS485 to RS232 converter
Unicom 2500-FRS485 or RS232 to fibre optic converter
CCalCertificate of calibration with NIST traceable test data

Accessories, software and converters

Example of a valid part number: Shark100-60-10-V1-D2-X-X.