Timing, coil currents and substation battery in a 1.6 kg handheld instrument
CAT-H
1 break per phase · Built-in coil control
Handheld circuit breaker analyzer & timer
Overview
CAT-H: handheld circuit breaker analyzer & timer.
Circuit breaker diagnostics in a handheld instrument
The CAT-H is a digital instrument for circuit breaker condition assessment. It records the Trip and Close coil current waveforms, the timing of the main arcing contacts and the substation DC battery voltage. The timing channels record the closing and opening of the main contacts and also measure the resistance of the pre-insertion resistors, if present in the circuit breaker.
Operating modes
Trip (O), Close (C), Trip-free (CO), Reclose (O-C), Close-Trip (C-O) and Trip-Close-Trip (O-C-O). Multiple operations are initiated using a predefined delay time or by sensing the position of the breaker contacts.
Measurement triggering
The operation can be initiated from the control room, by a local switch or externally by a testing device. The measurement is triggered by the coil control channel, the DC current clamp channel or the DC voltage channel.
What it records and analyzes
- Main arcing contacts operation.
- Trip and Close coils operation.
- Auxiliary contact operation.
- DC supply voltage.
- Integrity of control circuit wiring.
It displays numerical and graphical results and overlays up to 4 records, so operations can be compared and defects located on site in the substation.
Panel and connections
CAT-H front panel and side connections.
- 1 · Coil supply input: voltage supply for coil control.
- 2 · Coil control outputs: operate the circuit breaker Trip and Close coils.
- 3 · DC current clamp input: coil current recording and measurement.
- 4 · DC voltage channel input: voltage measurement of an analog signal.
- 5 · Main contacts input (offline measurement): timing of the main and pre-insertion resistor contacts, and pre-insertion resistor resistance.
- 6 · 5.7-inch color touch screen.
- 7 · Soft keys: selection of settings and menus as an alternative to the touch screen.
- 8 · Alphanumeric keypad: breaker data, test data and control functions.
- 9 · Power indicator.
- 10 · READY button: prepares the instrument for the start of the test.
- 11 · Power ON/OFF button.
- 12 · 12 V DC, 5 A power supply, with 85-264 V AC (47-63 Hz) adapter.
- 13 · Flash drive: direct download of test results.
- 14 · USB port for PC communication.
Applications and timing measurement
CAT-H connection to a live tank circuit breaker with one break per phase.
- Timing of up to 3 main contacts (1 break per phase), including pre-insertion resistors and auxiliary contact.
- Resistance of the pre-insertion resistors.
- Main contacts bounce time and pre-trigger time.
- Synchronization between circuit breaker poles.
- Measurement and graphical display of coil currents.
- Built-in coil control to operate the Trip and Close coils.
- State of the substation battery, or another analog signal, shown numerically and graphically.
Synchronization per IEC 62271-100 and ANSI C37.09
Timing measurement fulfils the requirements of both standards. The discrepancy between poles shall not exceed 1/6 cycle during opening (3.33 ms at 50 Hz; 2.78 ms at 60 Hz) or 1/4 cycle during closing (5.0 ms at 50 Hz; 4.17 ms at 60 Hz).
Testing with the breaker out of service
The CAT-H measures arcing contact timing with the circuit breaker isolated from the power grid, or at the factory or workshop. The breaker must be disconnected on both sides and grounded in accordance with safety regulations. The standards set no timing requirements for auxiliary contacts, but their operation should be checked.
Coil current and software
Characteristic points of the coil current waveform.
What the coil current waveform reveals
IEC 62271-100 recommends recording the coil current: it gives information on the coil condition (plunger friction, burned insulation, short-circuited turns), on the latch that releases the mechanism and on the operating mechanism itself.
When the command is given, the current rises (1) until the plunger starts to move (2); its motion reduces the current until it hits the buffer (3). The current then rises to saturation (4), proportional to the coil resistance. When the auxiliary contact opens (5), the current drops to zero (6). Values or times outside specification at these points indicate friction, winding defects, auxiliary contact malfunction or insufficient mechanism energy.
PC software
- Download of test results from the instrument to the PC.
- Viewing, editing, printing and exporting of records.
- Overlay of graphs to compare tests.
- Two cursors and zoom to measure points and intervals.
- Automatic unit conversion (cycles to seconds, mm to inches).
CAT-H — TECHNICAL DATA
| Main contact inputs | 3 (3 × 1), one per phase. Closed ≤ 10 Ω; pre-insertion resistor 10 Ω to 5 kΩ; open ≥ 5 kΩ. Open circuit voltage 20 V DC ±20%; short circuit current 50 mA |
|---|---|
| Time resolution | 0.05 ms to 10 ms depending on test duration (sampling rate up to 20 kHz) |
| Time accuracy | 0.05% of reading ± resolution |
| Operations | Close (C), Trip (O), Close-Trip (C-O), Trip-Close (O-C), Trip-Close-Trip (O-C-O) |
| DC current clamps | Nominal 300 A RMS or 450 A DC peak; ranges 30/300 A; DC to 20 kHz (−3 dB) |
| DC voltage measurement | ±300 V; typical accuracy ±0.5% of reading ±0.5% FS; guaranteed ±1% of reading ±1% FS |
| Coil control | 2 channels (Trip and Close); ±300 V DC / AC peak, ±35 A DC to 5 kHz; electronic drivers with overcurrent and overvoltage protection |
| Coil supply input | ±300 V DC / AC peak, ±35 A DC to 5 kHz |
| Coil current measurement | 2 channels (Trip and Close), Hall-effect sensor; ±35 A DC to 5 kHz; accuracy ±(0.5% of reading + 0.1% FS); waveform with 0.1 ms resolution |
| External power supply | 12 V DC, 5 A; input 90-264 V AC, 50/60 Hz |
| Internal battery | Li-ion 2 × 3.7 V, 2900 mAh; 8 h under normal use |
| Display | 145 mm (5.7-inch) color touch screen |
| Internal memory | Over 30,000 numerical and graphical test results |
| Standards | Safety: Directive 2014/35/EU, IEC EN 61010-1 (class I, pollution degree 2, installation category II); EMC: Directive 2014/30/EU, EN 61326-1; CAN/CSA-C22.2 No. 61010-1 |
| Environmental conditions | Operating −10 °C to +55 °C; storage and transport −40 °C to +70 °C; humidity 0 to 95% non-condensing |
| Dimensions and weight | 310 × 170 × 58 mm; 1.6 kg |
| Ingress protection | IP40 |
| Warranty | 3 years, plus 1 additional year upon product registration |
Specifications valid at +25 °C with standard accessories. Subject to change without notice.
CAT-H — ACCESSORIES
Instrument with included accessories: CATH000-N-00 (CAT-H with PC software on USB stick, mini USB cable, touch pen, plastic transport case and mains cable with power adapter).
| CMP-08-SETA1 | Main contacts cable set 8 m with alligator clamps (A1) · standard |
|---|---|
| MC-CG-0302A1 | Main contacts connection 3 × 1 m and ground cable 2 m with clamps (A1) · standard |
| CO-05-00C5B1 | Coil control cable 5 m with banana plugs · standard |
| C2-05-02BPBP | Coil supply cable set 2 × 5 m, 2.5 mm² · standard |
| S2-05-02BPBP | Voltage sense cable set 2 × 5 m, 2.5 mm² · standard |
| TESTPR-GJ-B0 / -R0 | Test probes with grip jaws, black and red (2 of each) · standard |
| DOLPIN-CL-B0 / -R0 | Dolphin clips, black and red (2 of each) · standard |
| JCB-15-2REBP / JCR-15-2REBP | 15 cm jumper cables with retractable-insulation banana plugs, black and red (3 of each) · standard |
| CABLE-BAG-00 | Cable bag · standard |
| CMP-10-SETA1 / CMP-08-SETA2 / CMP-10-SETA2 | Contact cable sets 8 or 10 m with A1 or A2 clamps · optional |
| CMP-08-SETST / CMP-10-SETST | Contact cable sets 8 or 10 m with SCT clamps · optional |
| CMPA-03-SET0 / CMPA-05-SET0 | Contact cable set adapter, 3 or 5 m · optional |
| MC-CG-0302A2 / MC-CG-0302ST | Contacts connection 3 × 1 m and ground 2 m with A2 or SCT clamps · optional |
| CACL-0300-09 | Current clamp 30/300 A powered from the instrument, with 5 m extension and adapter · optional |
| CACL-0100-00 | Current clamp 10/100 A with internal battery, 5 m extension and adapter · optional |
| S2-02-02BPBP / S2-10-02BPBP | Voltage sense cables 2 × 2 m or 2 × 10 m · optional |
| CO-10-00C5B1 / C2-10-02BPBP | Coil control cable 10 m / coil supply cables 2 × 10 m · optional |
| TESTPR-SC-B0 / -R0 | Test probes with split test clamps, black and red · optional |
| LION-BAT-001 / FIR-RTBBAG-0 | Li-ion battery 7.4 V 2900 mAh in fire-retardant bag / fire-retardant bag · optional |
| RSTCH-PEN-00 / HARD-CASE-HH | Touch pen / plastic transport case for CAT-H · optional |
| PWR-ADP5A-EU / -NA / -UK / -AU | Mains cable with 12 V / 5 A power adapter (EU, North America, UK, Australia) · optional |
Cables are available in other lengths and terminations on request.