CAT-H - Handheld circuit breaker analyzer & timer

Accessible HTML version of the document: the same text as the PDF, with headings, tables and a description of each image. Download the original PDF (PDF · 7 pages · 378 KB) · Source page: CAT-H: handheld circuit breaker analyzer and timer

Timing, coil currents and substation battery in a 1.6 kg handheld instrument

CAT-H

1 break per phase · Built-in coil control

Image: CAT-H circuit breaker analyzer seen from the front: grey handheld unit with black corner bumpers, three input terminals on top, color touch screen showing test curves, a row of soft keys and an alphanumeric keypad.

Handheld circuit breaker analyzer & timer

Overview

Image: Three-quarter view of the CAT-H: color screen with current and timing curves, soft keys, alphanumeric keypad, red READY button and input terminals on top.

CAT-H: handheld circuit breaker analyzer & timer.

Circuit breaker diagnostics in a handheld instrument

The CAT-H is a digital instrument for circuit breaker condition assessment. It records the Trip and Close coil current waveforms, the timing of the main arcing contacts and the substation DC battery voltage. The timing channels record the closing and opening of the main contacts and also measure the resistance of the pre-insertion resistors, if present in the circuit breaker.

Operating modes

Trip (O), Close (C), Trip-free (CO), Reclose (O-C), Close-Trip (C-O) and Trip-Close-Trip (O-C-O). Multiple operations are initiated using a predefined delay time or by sensing the position of the breaker contacts.

Measurement triggering

The operation can be initiated from the control room, by a local switch or externally by a testing device. The measurement is triggered by the coil control channel, the DC current clamp channel or the DC voltage channel.

What it records and analyzes

  • Main arcing contacts operation.
  • Trip and Close coils operation.
  • Auxiliary contact operation.
  • DC supply voltage.
  • Integrity of control circuit wiring.

It displays numerical and graphical results and overlays up to 4 records, so operations can be compared and defects located on site in the substation.

Panel and connections

Image: CAT-H front panel and two views of its sides with the connections numbered 1 to 14: coil supply and coil control, DC clamp, DC voltage and main contact terminals on top; screen, soft keys and keypad on the front; power supply, flash drive and USB port on one side.

CAT-H front panel and side connections.

  • 1 · Coil supply input: voltage supply for coil control.
  • 2 · Coil control outputs: operate the circuit breaker Trip and Close coils.
  • 3 · DC current clamp input: coil current recording and measurement.
  • 4 · DC voltage channel input: voltage measurement of an analog signal.
  • 5 · Main contacts input (offline measurement): timing of the main and pre-insertion resistor contacts, and pre-insertion resistor resistance.
  • 6 · 5.7-inch color touch screen.
  • 7 · Soft keys: selection of settings and menus as an alternative to the touch screen.
  • 8 · Alphanumeric keypad: breaker data, test data and control functions.
  • 9 · Power indicator.
  • 10 · READY button: prepares the instrument for the start of the test.
  • 11 · Power ON/OFF button.
  • 12 · 12 V DC, 5 A power supply, with 85-264 V AC (47-63 Hz) adapter.
  • 13 · Flash drive: direct download of test results.
  • 14 · USB port for PC communication.

Applications and timing measurement

Image: Connection diagram: the CAT-H, at the bottom, is connected to the breaker control circuit (close and trip push buttons, close and trip coils and substation battery) through the coil control cable, the coil supply cables and a current clamp. A timing cable with red, yellow and blue clips goes to the interrupters of phases A, B and C, and another cable goes to ground.

CAT-H connection to a live tank circuit breaker with one break per phase.

  • Timing of up to 3 main contacts (1 break per phase), including pre-insertion resistors and auxiliary contact.
  • Resistance of the pre-insertion resistors.
  • Main contacts bounce time and pre-trigger time.
  • Synchronization between circuit breaker poles.
  • Measurement and graphical display of coil currents.
  • Built-in coil control to operate the Trip and Close coils.
  • State of the substation battery, or another analog signal, shown numerically and graphically.

Synchronization per IEC 62271-100 and ANSI C37.09

Timing measurement fulfils the requirements of both standards. The discrepancy between poles shall not exceed 1/6 cycle during opening (3.33 ms at 50 Hz; 2.78 ms at 60 Hz) or 1/4 cycle during closing (5.0 ms at 50 Hz; 4.17 ms at 60 Hz).

Testing with the breaker out of service

The CAT-H measures arcing contact timing with the circuit breaker isolated from the power grid, or at the factory or workshop. The breaker must be disconnected on both sides and grounded in accordance with safety regulations. The standards set no timing requirements for auxiliary contacts, but their operation should be checked.

Coil current and software

Image: Graph of coil current versus time with six marked points: 1, coil energized; 2, the armature starts to move; 3, the armature reaches its end stop; 4, maximum current, proportional to the coil DC resistance; 5, the auxiliary contact opens; 6, the current drops to zero. Below, arrows show the start time, the mechanism time, the auxiliary contact time and the time until the coil is de-energized.

Characteristic points of the coil current waveform.

What the coil current waveform reveals

IEC 62271-100 recommends recording the coil current: it gives information on the coil condition (plunger friction, burned insulation, short-circuited turns), on the latch that releases the mechanism and on the operating mechanism itself.

When the command is given, the current rises (1) until the plunger starts to move (2); its motion reduces the current until it hits the buffer (3). The current then rises to saturation (4), proportional to the coil resistance. When the auxiliary contact opens (5), the current drops to zero (6). Values or times outside specification at these points indicate friction, winding defects, auxiliary contact malfunction or insufficient mechanism energy.

PC software

  • Download of test results from the instrument to the PC.
  • Viewing, editing, printing and exporting of records.
  • Overlay of graphs to compare tests.
  • Two cursors and zoom to measure points and intervals.
  • Automatic unit conversion (cycles to seconds, mm to inches).

CAT-H — TECHNICAL DATA

Main contact inputs3 (3 × 1), one per phase. Closed ≤ 10 Ω; pre-insertion resistor 10 Ω to 5 kΩ; open ≥ 5 kΩ. Open circuit voltage 20 V DC ±20%; short circuit current 50 mA
Time resolution0.05 ms to 10 ms depending on test duration (sampling rate up to 20 kHz)
Time accuracy0.05% of reading ± resolution
OperationsClose (C), Trip (O), Close-Trip (C-O), Trip-Close (O-C), Trip-Close-Trip (O-C-O)
DC current clampsNominal 300 A RMS or 450 A DC peak; ranges 30/300 A; DC to 20 kHz (−3 dB)
DC voltage measurement±300 V; typical accuracy ±0.5% of reading ±0.5% FS; guaranteed ±1% of reading ±1% FS
Coil control2 channels (Trip and Close); ±300 V DC / AC peak, ±35 A DC to 5 kHz; electronic drivers with overcurrent and overvoltage protection
Coil supply input±300 V DC / AC peak, ±35 A DC to 5 kHz
Coil current measurement2 channels (Trip and Close), Hall-effect sensor; ±35 A DC to 5 kHz; accuracy ±(0.5% of reading + 0.1% FS); waveform with 0.1 ms resolution
External power supply12 V DC, 5 A; input 90-264 V AC, 50/60 Hz
Internal batteryLi-ion 2 × 3.7 V, 2900 mAh; 8 h under normal use
Display145 mm (5.7-inch) color touch screen
Internal memoryOver 30,000 numerical and graphical test results
StandardsSafety: Directive 2014/35/EU, IEC EN 61010-1 (class I, pollution degree 2, installation category II); EMC: Directive 2014/30/EU, EN 61326-1; CAN/CSA-C22.2 No. 61010-1
Environmental conditionsOperating −10 °C to +55 °C; storage and transport −40 °C to +70 °C; humidity 0 to 95% non-condensing
Dimensions and weight310 × 170 × 58 mm; 1.6 kg
Ingress protectionIP40
Warranty3 years, plus 1 additional year upon product registration

Specifications valid at +25 °C with standard accessories. Subject to change without notice.

CAT-H — ACCESSORIES

Instrument with included accessories: CATH000-N-00 (CAT-H with PC software on USB stick, mini USB cable, touch pen, plastic transport case and mains cable with power adapter).

CMP-08-SETA1Main contacts cable set 8 m with alligator clamps (A1) · standard
MC-CG-0302A1Main contacts connection 3 × 1 m and ground cable 2 m with clamps (A1) · standard
CO-05-00C5B1Coil control cable 5 m with banana plugs · standard
C2-05-02BPBPCoil supply cable set 2 × 5 m, 2.5 mm² · standard
S2-05-02BPBPVoltage sense cable set 2 × 5 m, 2.5 mm² · standard
TESTPR-GJ-B0 / -R0Test probes with grip jaws, black and red (2 of each) · standard
DOLPIN-CL-B0 / -R0Dolphin clips, black and red (2 of each) · standard
JCB-15-2REBP / JCR-15-2REBP15 cm jumper cables with retractable-insulation banana plugs, black and red (3 of each) · standard
CABLE-BAG-00Cable bag · standard
CMP-10-SETA1 / CMP-08-SETA2 / CMP-10-SETA2Contact cable sets 8 or 10 m with A1 or A2 clamps · optional
CMP-08-SETST / CMP-10-SETSTContact cable sets 8 or 10 m with SCT clamps · optional
CMPA-03-SET0 / CMPA-05-SET0Contact cable set adapter, 3 or 5 m · optional
MC-CG-0302A2 / MC-CG-0302STContacts connection 3 × 1 m and ground 2 m with A2 or SCT clamps · optional
CACL-0300-09Current clamp 30/300 A powered from the instrument, with 5 m extension and adapter · optional
CACL-0100-00Current clamp 10/100 A with internal battery, 5 m extension and adapter · optional
S2-02-02BPBP / S2-10-02BPBPVoltage sense cables 2 × 2 m or 2 × 10 m · optional
CO-10-00C5B1 / C2-10-02BPBPCoil control cable 10 m / coil supply cables 2 × 10 m · optional
TESTPR-SC-B0 / -R0Test probes with split test clamps, black and red · optional
LION-BAT-001 / FIR-RTBBAG-0Li-ion battery 7.4 V 2900 mAh in fire-retardant bag / fire-retardant bag · optional
RSTCH-PEN-00 / HARD-CASE-HHTouch pen / plastic transport case for CAT-H · optional
PWR-ADP5A-EU / -NA / -UK / -AUMains cable with 12 V / 5 A power adapter (EU, North America, UK, Australia) · optional

Cables are available in other lengths and terminations on request.