Dissolved gas analysis calculator: Duval triangles and pentagons, IEC 60599 and IEEE
Enter the chromatograph concentrations and get Duval Triangles 1 to 7, the Duval Pentagons, the IEC 60599 ratios, Rogers, Doernenburg, the IEEE C57.104 conditions and the IEEE C57.146 silicone thresholds.
Dissolved gas analysis: Duval triangles and pentagons, IEC 60599 and IEEE
Enter the chromatograph concentrations in ppm. Each results tab applies one method: Duval Triangles 1 to 7, Duval Pentagons, IEC 60599, IEEE C57.104 and the IEEE C57.146 silicone guide.
Result
When two methods disagree there may be a mixture of faults: each representation gives more weight to some gases than to others. No method replaces the gas generation rate.
IEC 60599, Figure B.3: transformers, reactors, bushings and cables filled with mineral oil. It uses CH4, C2H4 and C2H2 as a percentage of their sum. It always returns a zone, even with gases at noise level: read it only when there is real generation.
IEC 60599, Figure B.4: oil from the compartment of oil-type on-load tap changers, where arcing is part of normal operation. In some models the N zone is smaller, or normal operation falls in X3, T2 or T3: compare with healthy units of the same type. Vacuum-bottle tap changers use Triangle 1.
Duval (2009): Triangle 3 is Triangle 1 with the D1/D2, T1/T2 and T2/T3 boundaries shifted for each fluid. The results are valid only if the laboratory used the Ostwald coefficients of the fluid, which differ from those of mineral oil.
Duval Triangle 4 (H2, CH4, C2H6)
Duval Triangle 5 (CH4, C2H4, C2H6)
For mineral oil (Duval 2009; geometry from IEEE C57.104-2019, Tables D.3 and D.4). Triangle 4 uses the low-energy gases and applies to PD, T1 and T2 from Triangle 1; Triangle 5 uses the temperature gases and applies to T2 and T3. They separate stray gassing S and overheating O from hot spots with possible carbonisation of paper C.
Duval Triangle 6 · FR3 (H2, CH4, C2H6)
Duval Triangle 7 · FR3 (CH4, C2H4, C2H6)
Duval (2009): versions of Triangles 4 and 5 for FR3 natural ester, which forms far more C2H6 than mineral oil when heated at low temperature. Only the S zone changes; the others are kept until inspected cases are reported.
Duval Pentagon 1
Duval Pentagon 2
Duval and Lamarre (2014): the five hydrocarbons in a single chart. The point is the centroid of the polygon formed by their percentages, which is why it never goes beyond 40 % on an axis. Pentagon 1 gives the six basic faults and stray gassing; Pentagon 2 splits the thermal faults into T3-H, C and O. Mineral oil only.
IEC 60599:2022. CH4/H2 limit for PD: 0.1 in transformers, 0.2 in instrument transformers and 0.07 in bushings. Typical values are ranges observed across many networks, not limits: you should calculate those of your own population.
IEEE C57.104-2019, for mineral-oil transformers only. The tables are 90th and 95th percentiles of a large population of analyses and classify the analysis, not the condition of the transformer. For levels or variations far above Tables 2 and 3, consult a DGA expert (6.1.2.4).
IEEE C57.104-2008, for mineral-oil transformers with no history. The 2008 Table 1 limits correct those of 1991 (acetylene drops to 1 ppm for Condition 1). The 2019 edition replaces this approach with percentiles by unit type and age.
IEEE C57.146-2005, for silicone-immersed transformers. The thresholds are consensus values based on limited field data and do not apply to equipment with expulsion fuses or load-break switches in the fluid. The key gas profiles have been read from Figures B.1 to B.4 of the guide.
Indicative result. The calculation runs in your browser and is not sent to any server. This website may contain errors or omissions: before making any decision about an installation, the information must be checked and validated by a qualified engineer. Legal notice and terms of use
What this calculator does
It takes the chromatograph concentrations in ppm and applies each interpretation method in its own tab, so they can be compared without mixing them up:
- Summary: the result of every method in one table.
- Duval Triangles 1 to 7 and Duval Pentagons 1 and 2, with the point plotted on the figure.
- IEC 60599:2022: Table 1 by equipment type, the simplified scheme of Table 2, the typical values of Annex A, rates of increase, CO2/CO, O2/N2 and C2H2/H2.
- IEEE C57.104-2019: DGA Status 1, 2 or 3 with Tables 1 to 4 by transformer age and O2/N2 ratio, variations between analyses and multi-point regression rates.
- IEEE C57.104-2008: Conditions 1 to 4, the Table 3 sampling interval, litres of gas per day the Rogers and Doernenburg ratios and the key gas method.
- IEEE C57.146-2005: thresholds and key gases for silicone-immersed transformers.
If you enter previous analyses with their dates (up to five), the calculator adds the variations and the generation rates, which are the figures that really decide. If the sample is free gas from the Buchholz relay, it converts it to its dissolved equivalent with the IEC 60599 Ostwald coefficients.
Where the gases come from
Each degradation mechanism inside the transformer breaks certain molecules and not others, which is why the gas mixture identifies the fault:
- Hydrogen (H2): appears with almost everything, and is the first to show in partial discharges.
- Methane and ethane (CH4, C2H6): moderate overheating of the oil.
- Ethylene (C2H4): severe overheating, above 300 °C.
- Acetylene (C2H2): electrical arcing. It needs temperatures above 700 °C and is produced no other way.
- Carbon monoxide and dioxide (CO, CO2): degradation of cellulose, that is, of the insulating paper.
IEEE C57.104-2019 DGA Status
The 2019 edition no longer classifies the transformer with fixed limits: it classifies the analysis into three statuses based on statistics from a large population of transformers.
- Status 1: low gas levels and no sign of gassing. Routine sampling.
- Status 2: a gas between Table 1 (90th percentile) and Table 2 (95th percentile), or a confirmed increase between analyses. Investigate and sample more often.
- Status 3: a gas above Table 2, or a generation rate above Table 4. Probable active gassing.
Tables 1 and 2 depend on transformer age (unknown, 1 to 9, 10 to 30 or over 30 years) and on the O2/N2 ratio (up to 0.2 or above); without O2 and N2 the above-0.2 section is used. Table 3 sets the maximum variation between two consecutive analyses: if it is exceeded, a confirmation sample is needed within a month. Table 4 sets the maximum rate in ppm/year, calculated by linear regression of the last 3 to 6 analyses over the last two years, with at least four months of history; for acetylene any increase counts.
The calculator also applies the Annex D.8 criteria for CO and CO2 (high CO without hydrocarbons points to oil oxidation, not to a fault in paper) and reminds you that, with every gas below Table 1, the guide advises against identifying the fault type.
IEEE C57.104-2008 conditions
The calculator classifies the analysis into four conditions with Table 1 of the 2008 edition, which corrected the 1991 values and remains the most widely used field reference for units with no history. The condition is that of the worst gas or of the total combustible gas, not the average.
| Gas | Condition 1 limit (ppm) |
|---|---|
| H2 | 100 |
| CH4 | 120 |
| C2H6 | 65 |
| C2H4 | 50 |
| C2H2 | 1 |
| CO | 350 |
| CO2 | 2,500 |
| Total combustible gas | 720 |
With the previous analysis, Table 3 gives the sampling interval and operating procedure from the total combustible gas and its generation rate (below 10, 10 to 30 or above 30 ppm per day). With the oil volume, Equation (1) is also applied: more than 2.8 litres of combustible gas per day points to an active fault.
The 2019 edition replaced this approach with the DGA Status described in the previous section. The calculator applies both editions, each in its own tab.
IEC 60599
The standard uses three quotients — C2H2/C2H4, CH4/H2 and C2H4/C2H6 — and a table that translates them into six fault types: PD (partial discharges), D1 and D2 (low- and high-energy discharges) and T1, T2 and T3 (thermal faults below 300 °C, between 300 and 700 °C and above 700 °C). When the ratios fit no row, the calculator says so and applies the simplified scheme of Table 2, which at least distinguishes partial discharges, discharges and thermal faults.
The CH4/H2 limit for partial discharges depends on the equipment: 0.1 in transformers, 0.2 in instrument transformers and 0.07 in bushings, which also have their own simplified scheme (Table A.10). In a tap-changer compartment Table 1 does not apply: Duval Triangle 2 and the C2H4/C2H2 ratio are used there.
The calculator compares each gas with the 90 % typical values of Annex A and, with the previous analysis, the rate of increase with Table A.3. If every gas is at the low end of the typical values, the analysis is normal and the standard advises against diagnosing with the ratios. Three auxiliary ratios complete the reading: CO2/CO (paper involvement), O2/N2 (oxygen consumption, below 0.3) and C2H2/H2 (above 2, contamination from the tap changer).
Duval triangles
Each triangle takes three gases, expresses them as a percentage of their sum and places the point in a ternary diagram divided into zones. The calculator draws each triangle from the same inequalities it uses to classify the point, so the drawing and the diagnosis cannot disagree.
- Triangle 1 (CH4, C2H4, C2H2): the classic IEC 60599 triangle for mineral oil. Boundaries: 98 % CH4 for PD; 4, 13, 15 and 29 % C2H2; 20, 23, 40 and 50 % C2H4. The DT zone covers mixtures of thermal and electrical faults.
- Triangle 2 (same gases): for oil from oil-type on-load tap changers, where arcing is part of normal operation. Zone N for normal operation and zones D1, X1, X3, T2 and T3 for abnormal operation.
- Triangle 3: Triangle 1 with three boundaries shifted for each alternative fluid.
- Triangles 4 and 5: for low-temperature faults in mineral oil. Triangle 4 uses H2, CH4 and C2H6; Triangle 5, CH4, C2H4 and C2H6. They separate stray gassing of the oil (S), overheating below 250 °C (O) and hot spots with carbonisation of paper (C). IEEE C57.104-2019 says to apply Triangle 4 to faults that Triangle 1 identifies as PD, T1 or T2, and Triangle 5 to T2 or T3 faults.
- Triangles 6 and 7: the equivalents of 4 and 5 for FR3 natural ester, whose stray gassing produces much more ethane.
| Fluid | D1/D2 (% C2H4) | T1/T2 (% C2H4) | T2/T3 (% C2H4) |
|---|---|---|---|
| Mineral oil | 23 | 20 | 50 |
| Silicone | 9 | 16 | 46 (extrapolated) |
| Midel 7131 | 26 | 39 | 68 (extrapolated) |
| FR3 | 25 | 43 | 63 |
| BIOTEMP | 20 | 52 | 82 (extrapolated) |
Sources: IEC 60599:2022 (Figures B.3 and B.4) and M. Duval, The Duval Triangle for LTCs, alternative fluids and other applications (2009). Triangles 4 and 5 follow Tables D.3 and D.4 of IEEE C57.104-2019.
Duval pentagons
The pentagon (Duval and Lamarre, 2014) uses all five hydrocarbons at once. Each gas has its own axis, from the centre (0 %) to the vertex (100 %), in this order: H2, C2H6, CH4, C2H4 and C2H2. The five percentages form an irregular polygon and the point of the analysis is its centroid, which never goes beyond 40 % on an axis. The zone boundaries are those of Annex D of IEEE C57.104-2019.
- Pentagon 1: the six basic faults (PD, D1, D2, T1, T2, T3) and stray gassing S.
- Pentagon 2: the same discharges, but the thermal faults are split into T3-H (in oil only), C (with carbonisation of paper) and O (overheating below 250 °C).
They do not replace Triangles 1, 4 and 5. If the pentagons and the triangles disagree, a mixture of faults is the most likely explanation.
Rogers, Doernenburg and key gases
These are the two ratio methods of IEEE C57.104-2008. Rogers uses CH4/H2, C2H2/C2H4 and C2H4/C2H6 and assigns one of six cases, from unit normal to thermal fault above 700 °C. Doernenburg uses four ratios (CH4/H2, C2H2/C2H4, C2H2/CH4 and C2H6/C2H2) and checks that there is enough gas before diagnosing: if no key gas exceeds twice its L1 limit, or if neither ethane nor CO exceeds L1, there is no fault (Figure 4), and if a ratio has no gas above L1 it is not significant. For free gas from the relay it applies the gas-space columns.
The key gas method (Figure 3) compares the proportions of the six combustible gases with four typical profiles — overheated oil (ethylene), overheated cellulose (CO), partial discharge (hydrogen) and arcing (acetylene) — and shows the closest one together with the principal gas measured.
Silicone-immersed transformers
IEEE C57.146-2005 gives its own thresholds for silicone: 200 ppm H2, 100 CH4, 1 C2H2, 30 C2H4 and C2H6, 3,000 CO, 30,000 CO2 and 3,361 total combustible gas. Below them, normal surveillance; above them, resample to confirm and look for the fault type. The calculator also compares the proportions of the combustible gases with the guide’s four key gas profiles (overheated silicone, overheated cellulose, partial discharge and arcing) and shows the closest one. In silicone, any amount of acetylene may indicate a serious problem.
Worked example
Power transformer with H2 180, CH4 95, C2H6 30, C2H4 210, C2H2 4 and CO 320 ppm.
- Total combustible gas: 839 ppm. Condition 2 for the total, hydrogen and acetylene, and Condition 4 for ethylene, which is above 200 ppm: the worst gas decides.
- IEC 60599: C2H2/C2H4 = 0.02; CH4/H2 = 0.53; C2H4/C2H6 = 7.0. Hydrogen exceeds the highest typical value (150 ppm), so the ratios are significant, but they fit no row of Table 1; Table 2 gives a thermal fault.
- Duval Triangle 1: CH4 31 %, C2H4 68 %, C2H2 1 %, zone T3. As it is not PD, T1 or T2, Triangles 4 and 5 do not apply.
- Pentagon 1: zone T3. Pentagon 2: T3-H, a thermal fault in oil with no sign of paper carbonisation.
Reading: thermal fault above 700 °C, with some acetylene that calls for close monitoring. The usual suspect is a poor internal connection or a circulating current in the core or tank.
What this calculator does not do
It does not know whether the sample was taken properly, whether the unit has only recently returned to service after a repair or degassing, or anything of its history beyond the previous analysis you give it. The IEC 60599 typical values are ranges observed across many networks: you should calculate those of your own equipment population. And every graphical method returns a zone even when there is no real generation; the diagnosis only makes sense when the gases and their rate of increase are above typical levels.
What measures it
The analysis is run by a laboratory from an oil sample, or by a dielectric oil analyser on site. For critical units the alternative is on-line monitoring: hydrogen and dissolved gas sensors that flag a change in trend between samples, instead of waiting for the six-monthly analysis. Oil treatment — drying and degassing — is the other half of the job.
Frequently asked questions
- Which gas points to the most serious fault in a transformer?
- Acetylene (C2H2). It takes an electrical arc to produce it, so any appreciable amount in a transformer without a tap changer sharing the same oil volume calls for investigation. The Condition 1 limit in IEEE C57.104-2008 is 1 ppm: the strictest of all the gases.
- Does the Duval triangle work at low concentrations?
- No. The triangle normalises the three gases to a percentage of their sum, so it always returns a zone even when all three are at the chromatograph’s noise level. First confirm that there is real generation — concentrations above typical values, or an appreciable generation rate — and only then read the zone.
- Which Duval triangle should I use?
- Triangle 1 for transformers, reactors, bushings and cables filled with mineral oil. Triangle 2 for oil from the compartment of an oil-type on-load tap changer. Triangle 3 for esters and silicone. Triangles 4 and 5 refine low-temperature faults (PD, T1 and T2 in Triangle 1) and separate stray gassing of the oil from hot spots that carbonise paper; Triangles 6 and 7 do the same for FR3 ester.
- What does the Duval pentagon add to the triangle?
- It uses all five hydrocarbons at once (H2, CH4, C2H6, C2H4 and C2H2), whereas each triangle uses three. It does not replace Triangles 1, 4 and 5: it complements them. When the pentagon and the triangles give different zones there is usually a mixture of faults, because each representation weighs some gases more than others.
- What is the difference between the IEC 60599 ratios and the Duval triangle?
- The ratios use quotients between pairs of gases and leave gaps: some combinations fall in no row of the table. The triangle always gives an answer because it covers the whole space, which is both an advantage and a risk. The sensible approach is to apply both and to be suspicious when they disagree.
- What changes in IEEE C57.104-2019 compared with the 2008 edition?
- The 2008 edition classifies the transformer into four conditions with fixed concentration limits. The 2019 edition classifies the analysis into three statuses with percentiles that depend on age and O2/N2 ratio, and gives more weight to the trend: the variation between consecutive analyses and a rate calculated by regression over several analyses, which reduces the effect of laboratory scatter.