Stationary battery calculator: sizing, autonomy and capacity test
Work out the minimum capacity your load profile demands, the estimated autonomy against a constant current and the result of a discharge test corrected for temperature.
Sizing, autonomy and capacity test
Three calculations on the same bank: the minimum capacity the load profile demands, the estimated autonomy against a constant current, and the result of a discharge test corrected for temperature.
Indicative result. The calculation runs in your browser and is not sent to any server. This website may contain errors or omissions: before making any decision about an installation, the information must be checked and validated by a qualified engineer. Legal notice and terms of use
What this calculator does
Three calculations on the same bank, in three tabs:
- Sizing. From the load profile, the minimum capacity that has to be installed.
- Autonomy. How long an installed bank will last against a constant current.
- Capacity test. What percentage of rated capacity a real discharge delivered, corrected for temperature.
Sizing to IEEE 485
The full IEEE 485 method splits the load profile into sections and finds, for each one, the cell size that covers it using the manufacturer’s capacity curves. This calculator applies the simplified version used for a first pass:
- The ampere-hours the profile demands are added up: Σ (current × duration).
- The temperature factor for the lowest room temperature is applied. It interpolates between the IEEE 485 table points — 1.00 at 25 °C; 1.04 at 21.1 °C; 1.11 at 15.6 °C; 1.19 at 10 °C; 1.30 at 4.4 °C; 1.59 at −6.7 °C — and above 25 °C no credit is taken, which is the conservative choice.
- The ageing factor is applied, 1.25 by convention.
- The design margin is added, typically 10% to 15%.
The result is the minimum capacity in ampere-hours. It is not the final cell size: for that you have to enter the manufacturer’s curves with the real discharge rate, because a battery does not deliver the same capacity in 1 hour as in 8.
Estimated autonomy
The second tab uses the Peukert equation,
t = H × (C / (H × I))^n
where C is rated capacity, H the rate it is quoted at (8 or 10 hours on most stationary cells), I the discharge current and n the Peukert exponent, between 1.1 and 1.3 for lead-acid.
It is a familiar and convenient approximation, but an approximation: it drifts from reality on very fast discharges and at very small currents, and it takes no account of the end-of-discharge voltage or the initial state of charge. Use it to decide whether a bank is comfortable or tight; not to certify an autonomy.
Capacity test to IEEE 450
The only way to know a battery’s capacity is to discharge it. The third tab calculates
Capacity (%) = (time achieved / expected time) × 100
corrected for the mean cell temperature during the test with the IEEE 450 factor, 1 + 0.008 × (T − 25 °C). With cells at 30 °C the battery over-performs, and without correcting you would record a result about 4% better than the truth.
Reading: 90% or above, normal service; between 80% and 90%, shorten the test interval; below 80%, replace.
Worked example
125 V DC system in a substation whose room drops to 10 °C in winter. Profile: 120 A for the first minute, 25 A for 179 minutes and 80 A in the final minute.
- Profile demand: 120×(1/60) + 25×(179/60) + 80×(1/60) = 77.9 Ah
- Temperature factor at 10 °C: 1.19
- With ageing 1.25 and a 10% margin: 77.9 × 1.19 × 1.25 × 1.10 = 127 Ah
A 150 Ah cell at the 8-hour rate covers the profile comfortably; a 125 Ah one would be marginal and would have to be checked against the manufacturer’s curve before buying.
What this calculator does not do
It does not replace the section-by-section IEEE 485 method or the manufacturer’s curves, which govern the final sizing. It knows nothing about the cell type, the end-of-discharge voltage or the number of cells. And it says nothing about the condition of an installed bank: that is what the discharge test is for, and it is the one measurement no calculation can replace.
What measures it
The capacity test is run with a battery discharger able to hold the current constant and log the voltage of every cell throughout the discharge. The rest of the maintenance cycle — charging, cell testing and monitoring — is covered by the same battery maintenance and charging range.
If you would rather not pick the equipment by hand, the charger and discharger selector proposes a specific model from the bank voltage, the current and the type of test.
Frequently asked questions
- Why multiply by 1.25 when sizing a battery?
- That is the ageing factor. A stationary battery is considered spent when its capacity falls to 80% of rated, and 1/0.8 = 1.25. Sizing without it means the installation stops meeting its autonomy long before the battery reaches the end of its service life.
- Why correct for temperature?
- Because a lead-acid battery delivers less capacity the colder it is: at 10 °C you need around 19% more rated capacity to get the same ampere-hours as at 25 °C. Sizing is done with the lowest temperature expected in the room, not the average.
- When should a battery bank be replaced?
- IEEE 450 sets the criterion at 80% of rated capacity: below that the battery is replaced. Between 80% and 90% the recommendation is to shorten the interval between tests and trend the result, because the decline usually accelerates.