Skip to content

Generators, bus ducts and step-up transformers: what to monitor in a power plant

Partial discharge through the stator RTDs, sensors on the bus duct and transformer moisture: 10 ppm when cold and 137 ppm when hot.

Watch the summary (2:49)

AI-generated video. The information must be validated by an Amperis engineer. Watch the video with its transcript

In a rotating machine it is the insulation that fails, and the measurement that finds it is partial discharge: a high-frequency current pulse best detected between 30 kHz and 30 MHz. This video follows the chain through a power plant: the stator of motors and generators, the bus duct that connects them to the transformer, and the generator step-up transformer, whose duty cycles are changing with renewables.

Key points

  • The stator RTDs, usually two to six per phase, also work as partial discharge sensors without affecting the temperature measurement. Comparing the magnitude at each one, the defect is near the highest reading, without opening the machine.
  • On the bus duct, the bolted joints go through thermal cycles every day. A ground path current sensor works at ground potential, outside the enclosure, and the pulse polarity shows whether the discharge comes from the machine or the bus.
  • On the isolated-phase bus of a power plant, a disconnect switch monitored for both partial discharge and temperature tripped twice on temperature. The discharge had been rising sharply for at least two months before the first trip, and the failure appeared at the corners of the part because of the skin effect: temperature confirmed it, partial discharge predicted it.
  • On the step-up transformer, a one- or two-gas monitor across the fleet pays off better than a full analyser on a single unit. In battery storage and wind, each part of the duty cycle attacks something different: thermal cycling, harmonics, moisture migration, through-faults and fast ramps.
  • Moisture moves from paper to oil with temperature: a 50 MVA unit reads 10 ppm at 20 °C and 137 ppm at 80 °C with the same water. That is why online relative saturation, which corrects for temperature, is more reliable than a laboratory ppm figure.

Partial discharge: a tiny current in a narrow window

A discharge in a void causes a small dip in voltage across the sample, and the charge that replaces it is a high-frequency current pulse. That pulse is what the instrument actually measures. Published work puts the best detection between 30 kHz and 30 MHz; above 30 MHz only a small fraction of the signal is still available. The band matters more than the sensitivity: listening in the wrong window finds nothing, however good the instrument.

The sensors are already in the winding

The stator RTDs, the temperature detectors buried in the winding, double as partial discharge sensors. They are more sensitive than a coupling capacitor, because the element covers a length of winding, whereas a coupling capacitor is a spot measurement. The method does not touch the RTD wiring, so the temperature measurement is unaffected, and there are typically two to six RTDs per phase, depending on the size of the machine. The pattern recognition rules developed for coupling capacitors still apply; only the sensitivity differs.

The highest reading is nearest the defect

This gives something conventional testing struggles with: location. Measure at every RTD around the stator, compare the magnitudes slot by slot, locate the defect near the one reading highest, trend that slot over time and act before the outage, not during it. The conventional alternative is a corona probe, which needs the machine opened and only reaches the zone you can physically get to.

The bus duct: nothing moves, so why watch it?

It is an inert system with no moving parts, which is the usual objection. But the bolted joints are thermally cycled every day the plant runs. Loose connections come from thermal cycling and incorrect torque; high-resistance joints from surface films, oxides or loss of plating; flex links are the usual location; cracks in the expansion joints let moisture in. And, according to IEEE statistics, about 75 % of failures in bus-duct systems are insulation related; contributing factors are loose bolted connections, temperature, humidity, underperforming cooling and contamination.

The sensor used there is elegant. A ground-path current sensor captures high-frequency pulses on the metal surface of the enclosure. It sits at earth potential, so there is no high-voltage risk in installing it, it is non-invasive (no modification to the bus itself), and the polarity of the pulse distinguishes the machine side from the bus side. It is combined with capsule temperature, humidity and pressure.

Isolated-phase bus: two months of warning in the discharge

On the isolated-phase bus system of a power plant, a disconnect switch was monitored by both partial discharge and temperature. Two trips were initiated when the temperature exceeded its set point, but the steep rise in discharge had begun at least two months earlier. The failure occurred at the corners, due to skin effect. Temperature confirmed it; discharge predicted it.

The step-up transformer: the one that cannot be swapped in a week

The generator step-up transformer is treated differently from a network transformer because it is not replaceable in a hurry and it never rests. Oil touches every component of the active part, so gas reports on all of it, and a sudden rise in dissolved gas is the best indicator of an incipient fault. About 90 % of the time the unit behaves entirely normally; the other 10 % is what the monitor exists for, and close surveillance can keep it running until a planned outage. For cost, the most effective strategy is a single or two-gas monitor across a whole fleet rather than a full analyser on one unit.

Renewable duty cycles: each stress attacks something different

A transformer in a battery storage or wind installation no longer has a steady load profile. It has a duty cycle:

Renewable duty cycles: each stress attacks something different
StressWhat it attacks
Thermal cyclinginsulation ageing
Harmonicseddy-current heating, extra temperature rise
Moisture migrationreduced dielectric strength
Through faultsmechanical winding displacement
Fast rampingthermal fatigue
High dV/dtinsulation stress

Conventional transformers were designed for relatively stable loading; these duty cycles are fundamentally different.

Why the sample misleads: 10 ppm cold, 137 hot

Nearly all the water lives in the solid insulation, not the oil, and heating drives it out of the paper and into the oil. A 50 MVA unit can read 10 ppm at 20 °C and 137 ppm at 80 °C: the water did not change, only the temperature did. That is why operators see ppm spikes on load after a “safe” cold sample. Online relative saturation accounts for temperature automatically; a laboratory ppm figure does not.

What goes wrong in practice

  • Treating a renewable-duty transformer like a conventional one.
  • Relying on the oil and winding gauges alone, with poor hot-spot visibility.
  • Ignoring harmonics: hidden overheating and accelerated ageing.
  • Static alarm thresholds: nuisance alarms, or missed events.
  • No baseline commissioning data, so no long-term trend is possible.

Five things to take away

  1. In rotating machines the insulation fails, so discharge is the measurement.
  2. Listen in the right frequency window, or the instrument finds nothing.
  3. The sensors are often already installed: use the stator RTDs.
  4. Bus duct is not inert: bolted joints are cycled every day.
  5. Renewable duty cycles are a different problem, not a smaller one.

The Dynamic Ratings RMM rotating machine monitor and the PD Profiler monitor partial discharge in service; the rest of the range is under partial discharge detection. For step-up transformers, see the E3 transformer monitor and the GRIDSCAN5000 hydrogen sensor. To discuss your plant, contact our engineers.

Related equipment

Related articles

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote