AMPI-530: multifunction installation tester

Multifunction installation testersSee the comparison

AMPI-530: multifunction installation tester

Multifunction electrical installation meter to IEC 61557

Standards
IEC 61557
Fault loop
0.13…1999.9 Ω
RCD testing
AC, A and B types
Insulation
50/100/250/500/1000 V
Earth and continuity
3p, 4p, 3p+clamp, 2 clamps
Recorder
U up to 500 V

Which model do you need? Talk to an engineer

+34 982 20 99 20

ISO 9001 · ISO 14001 · ISO 45001

Carrying out the verification measurements described in HD 60364-6 for a low-voltage installation (fault loop, RCDs, insulation, earth and continuity) with IEC 61557 methods is best done with a multifunction tester that also records basic mains parameters. The AMPI-530 measures the loop from 0.130 to 1999.9 Ω per IEC 61557-3 with 0.001 Ω resolution and ±(5 % m.v. + 0.03 Ω) up to 19.999 Ω, tests AC, A and B RCDs from 10 to 1000 mA per IEC 61557-6, measures insulation from 50 to 1000 V up to 9.99 GΩ, earth with clamps and soil resistivity, and records voltage, current, power and harmonics up to the 40th.

AMPI-530 key data

  • Fault loop: 0.130 to 1999.9 Ω per IEC 61557-3 with the 1.2 m lead, 0.001 Ω resolution and ±(5 % m.v. + 0.03 Ω) up to 19.999 Ω; prospective short-circuit current up to 40 kA; no-trip mode from 0.50 Ω that does not trip RCDs of IΔn ≥ 30 mA.
  • RCDs: general and selective AC, A and B types from 10 to 1000 mA per IEC 61557-6; tA with 1 ms resolution and ±(2 % m.v. + 2 digits); IA with ±5 % IΔn for sinusoidal and ±10 % IΔn for pulsating and DC current; touch voltage UB from 10 to 99.9 V.
  • Insulation: 50, 100, 250, 500 and 1000 V per IEC 61557-2, up to 9.99 GΩ at 1000 V; ±(3 % m.v. + 8 digits) up to 999 MΩ and ±(4 % m.v. + 6 digits) in the GΩ range; current below 2 mA, automatic discharge and testing of cables with up to 5 wires via an adapter.
  • Earth and resistivity: 3-pole from 0.50 Ω to 1.99 kΩ per IEC 61557-5 with ±(2 % m.v. + 4 digits) up to 9.99 Ω; with clamp ±(8 % m.v. + 4 digits) up to 1.99 kΩ; with two clamps ±(10 % m.v. + 4 digits) up to 19.9 Ω; Wenner resistivity up to 99.9 kΩm with 1 to 30 m spacing.
  • Continuity: 0.12 to 400 Ω per IEC 61557-4 with a minimum of 200 mA in both polarities, ±(2 % m.v. + 3 digits) and lead compensation.
  • Recorder and illuminance: voltage up to 500 V, current up to 3 kA with flexible clamps, power and cosφ with ±(7 % m.v. + 3 digits), harmonics up to the 40th with ±(5 % m.v. + 3 digits) up to the 15th, THD and 16 h of recording on battery; illuminance with an external class A or B probe.
  • Instrument: 4 LR14 cells or a 4.8 V 4.2 Ah NiMH battery for more than 3000 loop or RCD measurements, 10,000 records and 6000 recorder cells, USB and Bluetooth, IP54, CAT IV 300 V (CAT III 600 V), 288 × 223 × 75 mm and 2.5 kg.

Advantages

Complete diagnostics to IEC 61557

It measures Z L-PE, Z L-N and Z L-L fault loop impedance with 23 A (44 A phase-to-phase), also in RCD-protected circuits without tripping, and calculates the prospective short-circuit current automatically.

RCD testing from 10 to 1000 mA

It checks general and selective breakers of AC, A and B types, measuring the tripping time tA and the tripping current IA, starting from the positive or the negative half of the waveform.

Insulation up to 10 GΩ and continuity

Test voltages of 50 to 1000 V with automatic discharge, measurement through the UNI-Schuko plug and automatic testing of 3-, 4- and 5-core cables with the AutoISO-1000C adapter; PE continuity is verified with ±200 mA in both directions.

Earth by four methods plus a light meter

Earth resistance is measured with the 3-pole, 4-pole, 3-pole plus clamp and two-clamp methods, soil resistivity with the Wenner method, and an external probe measures light intensity.

Single-phase mains recorder

It records voltage up to 500 V, current up to 3 kA with clamps, frequency, powers, cosφ, harmonics up to the 40th and THD, with a tree memory of 6000 cells and 10 000 records and USB and Bluetooth transfer.

Applications

  • Verification of domestic and industrial electrical installations to IEC 61557.
  • Electric shock protection measurements for commissioning and maintenance.
  • Testing of RCDs, continuity of PE conductors and earth resistance.
  • Basic mains diagnostics: harmonics, THD, powers and phase sequence.

About the product

The AMPI-530 is a multifunction installation meter with an IP54 housing and CAT IV 300 V measuring category, powered by LR14 cells or a NiMH battery with built-in charger; the tree-structured memory and the USB and Bluetooth interfaces simplify downloading results and preparing reports.

Technical specifications

StandardsIEC 61557; measurements described in HD 60364-6
Fault loop0.13…1999.9 Ω; 23 A (44 A phase-to-phase); 15 mA with RCD
RCD testingAC, A and B types; 10…1000 mA; tA and IA
Insulation50/100/250/500/1000 V; up to 10 GΩ
Earth and continuity3p, 4p, 3p+clamp, 2 clamps; Wenner; ±200 mA
RecorderU up to 500 V; I up to 3 kA; harmonics to 40th; THD
Memory6000 cells, 10 000 records; tree structure
CommunicationUSB 2.0 and Bluetooth
Power supply4 × LR14 cells or NiMH 4.8 V 4.2 Ah; built-in charger
ProtectionCAT IV 300 V / CAT III 600 V; IP54; 0…+50 °C
Dimensions and weight288 × 223 × 75 mm; approx. 2.5 kg
Loop accuracy±(5 % m.v. + 0.03 Ω) up to 19.999 Ω (0.001 Ω res.); no-trip mode ±(6 % m.v. + 10 digits)
RCD and insulation accuracytA: ±(2 % m.v. + 2 digits); IA: ±5 % IΔn (sinusoidal); RISO: ±(3 % m.v. + 8 digits) up to 999 MΩ
Measurement standardsIEC 61557-2, -3, -4, -5 and -6

Frequently asked questions

Which multifunction tester covers the HD 60364-6 verification tests and also records harmonics?

The AMPI-530 combines IEC 61557 measurements (loop from 0.130 to 1999.9 Ω, AC, A and B RCDs from 10 to 1000 mA, insulation up to 9.99 GΩ, earth and 200 mA continuity) with a single-phase recorder for voltage up to 500 V, current up to 3 kA, power and harmonics up to the 40th, with 16 h of recording on battery.

What resolution does the AMPI-530 offer for fault loop measurement?

0.001 Ω from 0 to 19.999 Ω, with ±(5 % m.v. + 0.03 Ω); from 20.00 to 199.99 Ω it resolves 0.01 Ω with ±(5 % m.v. + 0.3 Ω), and the prospective short-circuit current is calculated up to 40 kA.

What does the AMPI-530 measure?

Fault loop impedance, RCD parameters, insulation resistance up to 10 GΩ, earth resistance and soil resistivity, continuity with ±200 mA, light intensity, phase sequence and single-phase mains parameters.

Can it measure the loop without tripping the RCD?

Yes. A 15 mA measuring function avoids tripping residual current devices with a rated current of 30 mA or higher.

Which RCDs can it test?

General and selective breakers of AC, A and B types with rated currents of 10, 30, 100, 300, 500 and 1000 mA, measuring both tripping time and tripping current.

How are the results downloaded?

The tree memory stores 6000 cells and 10 000 records, transferred over USB 2.0 or Bluetooth to prepare test reports on a computer.

How is the meter powered?

With four LR14 alkaline cells or a 4.8 V 4.2 Ah NiMH battery; the charger is built in and works from the mains or from a 12 V car socket.

Videos

AMPI-530 (5:26)
AMPI-530: multifunction installation tester to IEC 61557 for low-voltage installations: fault loop, RCDs, insulation up to 10 GΩ, continuity, earth resistance and phase sequence. How it is connected for each test, and how to read the results. Watch the video with its transcript

AI-generated video. The information must be validated by an Amperis engineer.

Downloads

PDFDownload the catalogue · AMPI-530: multifunction installation tester239 KB
Electrical test instrument selector Tell us what you need to measure and on which installation —insulation, earth, loop, RCDs, micro-ohmmeter and other measurements— and get the instrument that covers your specification, with its standard accessories and the ones worth adding. You can send us the selection with the technical report attached. Open the selector and find my equipment Close the selector

Undecided between several models? Compare them side by side: Insulation resistance testers compared · Multifunction installation testers compared · Earth resistance testers compared · Loop impedance testers compared

More in Multifunction installation testers

See all →

Got a test to solve? Talk to an engineer.

Tell us the asset, the voltage and the test you need, and we will propose the right instrument.

+34 982 20 99 20 Mon–Thu 09:00–14:00 · 15:30–19:00Fri 08:00–14:00 Request a quote