To verify protection against electric shock in LV installations with an IT earthing system, such as operating theatres, mines or industrial plants where supply continuity is critical, you need an IEC 61557 multifunction meter that lets you select the IT network and test RCDs in it. The AMPI-530-IT measures fault loop impedance from 0.13 to 1999.9 Ω, tests AC, A and B type RCDs from 10 to 1000 mA with trip times up to 400 ms in IT networks, measures insulation at 50 to 1000 V up to 9.99 GΩ and earth resistance by four methods, in an IP54 housing rated CAT IV 300 V.
AMPI-530-IT key data
- Standards and networks: measurements to IEC 61557 (loop to IEC 61557-3, insulation to IEC 61557-2, continuity to IEC 61557-4 and earth to IEC 61557-5); the TN, TT or IT network type is selected before measuring and, in an IT network, the AMPI-530-IT disables the PE touch electrode.
- Fault loop: ZL-PE, ZL-N and ZL-L from 0.13 to 1999.9 Ω with ±(5% m.v. + 0.03 Ω); in RCD-protected circuits, from 0.50 to 1999 Ω without tripping with ±(6% m.v. + 5 digits); operating voltage from 95 to 270 V (L-PE, L-N) and up to 440 V (L-L), 45 to 65 Hz.
- RCD testing: general, short-time delay and selective RCDs from 10 to 1000 mA; trip time tA at 0.5, 1, 2 and 5 IΔn with ±(2% m.v. + 2 digits), up to 300 ms in TN/TT networks, 400 ms in IT networks and 500 ms for selective RCDs; trip current IA from 0.2 to 2.0 IΔn for AC (±5% IΔn), A and B types (±10% IΔn).
- Insulation: test voltages of 50, 100, 250, 500 and 1000 V with ±(3% m.v. + 8 digits); at 1000 V it measures from 1 MΩ to 9.99 GΩ to IEC 61557-2; automatic testing of 3-, 4- and 5-core cables with the AutoISO-1000C adapter.
- Earth and continuity: 3- and 4-pole methods from 0.50 Ω to 1.99 kΩ with ±(2% m.v. + 3 digits), 3-pole with clamp, two clamps up to 99.9 kΩ and Wenner soil resistivity up to 99.9 kΩm; continuity of PE and equipotential bonding conductors with ±200 mA from 0.12 to 400 Ω with ±(2% m.v. + 3 digits).
- Recorder and light: single-phase recorder of voltage up to 500 V, current up to 3000 A AC depending on the clamp, powers, cosφ, power factor, harmonics up to the 40th and THD; light intensity up to 399.9 klx with an external probe; phase sequence from 95 to 500 V.
- Autonomy and memory: more than 3000 loop or RCD measurements and more than 1000 insulation or continuity measurements with the 4.8 V 4.2 Ah NiMH battery charged, 16 h of recording; 10 000-record tree memory downloaded over USB 2.0 or Bluetooth.
- Construction: double insulation to EN 61010-1 and IEC 61557, CAT IV 300 V / CAT III 600 V, IP54 housing, 0 to +50 °C, 288 × 223 × 75 mm and approx. 2.5 kg.
Advantages
Ready for IT networks
It tests general and selective RCDs from 10 to 1000 mA also in isolated IT systems, a capability that sets it apart from conventional multifunction meters.
Fault loop with 0.01 Ω resolution
It measures impedance with 23 A (44 A phase-to-phase) in the 95…440 V range and, with a 15 mA current, evaluates RCD-protected circuits without tripping the breaker.
Insulation up to 10 GΩ
Test voltages from 50 to 1000 V with automatic discharge, measurement through the UNI-Schuko plug and automatic testing of 3-, 4- and 5-core cables with the AutoISO-1000C adapter.
Earth, continuity and light intensity
Four earth measurement methods, soil resistivity by Wenner, bidirectional continuity with ±200 mA, quick PE check by touch electrode and light measurement with an external probe.
Recording and communication
It records voltage, current, powers, harmonics up to the 40th and THD; results are stored in a tree memory and downloaded over USB or Bluetooth.
Applications
- Verification of installations with IT earthing systems: hospitals, mining and industry.
- Electric shock protection measurements to IEC 61557 in LV installations.
- Testing of RCDs, PE continuity and earth resistance with four methods.
- Basic mains diagnostics with harmonics, THD and phase sequence.
About the product
The AMPI-530-IT shares the robust IP54 housing and the CAT IV 300 V category of the AMPI-530 family and is powered by LR14 cells or a NiMH battery with built-in charger; its distinctive feature is the ability to measure in isolated IT networks, completing loop, RCD, insulation, earth, continuity and light measurements with USB and Bluetooth communication.
Technical specifications
| Standards | IEC 61557; RCD testing also in IT systems |
| IT networks | Loop and RCD measurements in isolated systems |
| Fault loop | 0.13…1999.9 Ω; 23 A (44 A phase-to-phase); 15 mA with RCD |
| RCD testing | General and selective; 10…1000 mA; tA and IA |
| Insulation | 50/100/250/500/1000 V; up to 10 GΩ |
| Earth and continuity | 3p, 4p, 3p+clamp, 2 clamps; Wenner; ±200 mA |
| Recorder | U up to 500 V; harmonics to 40th; THD |
| Memory | 6000 cells, 10 000 records; tree structure |
| Communication | USB 2.0 and Bluetooth |
| Power supply | 4 × LR14 cells or NiMH 4.8 V 4.2 Ah; built-in charger |
| Protection | CAT IV 300 V / CAT III 600 V; IP54; 0…+50 °C |
| Dimensions and weight | 288 × 223 × 75 mm; approx. 2.5 kg |
| Loop and RCD accuracy | ZS ±(5% m.v. + 0.03 Ω); tA ±(2% m.v. + 2 digits); IA ±5% IΔn (AC), ±10% IΔn (A and B) |
| Trip time tA | Up to 300 ms (TN/TT), 400 ms (IT) and 500 ms (selective) |
| Insulation, earth and continuity accuracy | RISO ±(3% m.v. + 8 digits); RE ±(2% m.v. + 3 digits); R at ±200 mA ±(2% m.v. + 3 digits) |
Frequently asked questions
Can the AMPI-530-IT test type B RCDs?
Yes. It measures the trip current IA of type AC RCDs (3.3 to 1000 mA, with ±5% IΔn), type A RCDs, also with a 6 mA DC bias (3.5 to 700 mA), and type B RCDs with direct residual current (2.0 to 1000 mA), the latter two with ±10% IΔn, as well as the trip time at 0.5, 1, 2 and 5 IΔn.
How many measurements does the AMPI-530-IT make on one battery charge?
More than 3000 loop or RCD measurements (at 6 per minute) and more than 1000 insulation or continuity measurements with the 4.8 V 4.2 Ah NiMH battery charged, or about 16 hours of recording. It also runs on four LR14 cells, and the battery is charged inside the meter from the mains or from a 12 V car socket.
What makes the AMPI-530-IT different?
It is prepared for isolated IT networks, where it tests general and selective RCDs from 10 to 1000 mA in addition to all standard installation measurements.
Where are IT systems used?
In installations where supply continuity is critical, such as hospital operating theatres, mines and certain industrial plants; the meter covers their verification.
Which insulation voltages are available?
Test voltages of 50, 100, 250, 500 and 1000 V with measurements up to 10 GΩ and automatic discharge after the test.
Does it measure earth resistance?
Yes, with the 3-pole, 4-pole, 3-pole plus clamp and two-clamp methods, plus soil resistivity using the Wenner method.
How are results transferred?
Over USB 2.0 or Bluetooth from a tree memory with 6000 cells and 10 000 records, ready for report generation.